DOCA0005EN-14

Meter information

NOTE: E denotes the extension bit; the hex value assumes E = 0.

Data format

Primary VIF Extension

Description

bin

hex

0D

E000 1010

0A

Manufacturer

  • 18-bit ASCII = Schneider Electric

0D

E000 1100

0C

Model

0D

E000 1110

0E

Firmware version

03

E0001 0111

17

Meter error codes:

  • 0 = Code 101: EEPROM error
  • 1 = Code 102: No calibration table
  • 2 = Code 201: Mismatch between frequency settings and frequency measurements
  • 3 = Code 202: Mismatch between wiring settings and wiring inputs
  • 4 = Code 203: Phase sequence reversed
  • 5 = Code 204: Total active energy negative due to incorrect voltage or current connections
  • 6 = Code 205: Date and time are reset due to a power failure
  • 7 = Code 206: Pulse missing due to overspeed of energy pulse output
  • 8 = Code 207: Abnormal internal clock function
  • 9 = Internal data bus communications error

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.