Non-Reversing
Class 8538 / Refer to Catalog 8538CT9701
Fusible Disconnect Switch Type
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
Class 8538 and 8539 Type S combination starters combine the requirements of motor overload and short circuit protection into one package. These starters are manufactured according to NEMA standards and are UL Listed (some Form numbers may not be listed—contact the Customer Care Center). Class 8538 and 8539 combination starters operate at 600 Vac maximum, 50–60 Hz, and can be provided with one of four overloaded relay styles (refer to General Information).
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic SSOLR protection), see Solid-State Overload Relay Forms.
Class 8538 Fusible Full Voltage Type (Class H Fuse Clips), with Motor Logic SSOLR (replace ●●● with the voltage code)[1]
Ratings |
Fuse |
NEMA 1 |
NEMA 4X |
NEMA 4X |
NEMA 12/3R[2] |
||||
---|---|---|---|---|---|---|---|---|---|
Motor Voltage |
Max. Hp |
NEMA Size |
With |
Without |
|||||
Type [3] |
Type [3] |
Type [3] |
Type [3] |
Type [3] |
|||||
200 |
3 |
0 |
30 |
SBG12●●●H30 [4] |
SBW12●●●H30 [4] |
SBW22●●●H30 [4] |
SBA22●●●H30 [4] |
SBA12●●●H30 [4] |
Schneider Electric offers express shipping for factory modified NEMA Combo Starters. When you need them fast, our Laser™ Delivery program is the answer to getting your product when you need it most. Ask for Laser™ Delivery, then select the product and the modifications you need when you place your order. It’s as easy as that! |
5 |
1 |
30 |
SCG12●●●H30 [4] |
SCW12●●●H30 [4] |
SCW22●●●H30 [4] |
SCA22●●●H30 [4] |
SCA12●●●H30 [4] |
||
7-1/2 |
60 |
SCG13●●●H30 [4] |
SCW13●●●H30 [4] |
SCW23●●●H30 [4] |
SCA23●●●H30 [4] |
SCA13●●●H30 [4] |
|||
10 |
2 |
60 |
SDG12●●●H30 [4] |
SDW12●●●H30 [4] |
SDW22●●●H30 [4] |
SDA22●●●H30 [4] |
SDA12●●●H30 [4] |
||
20 |
3 |
100 |
SEG15●●●H30 |
SEW15●●●H30 |
SEW25●●●H30 |
SEA25●●●H30 |
SEA15●●●H30 |
||
25 |
200 |
SEG12●●●H30 |
SEW12●●●H30 |
— |
SEA22●●●H30 |
SEA12●●●H30 |
|||
40 |
4 |
200 |
SFG15●●●H30 |
SFW15●●●H30 |
— |
SFA25●●●H30 |
SFA15●●●H30 |
||
75 |
5 |
400 |
SGG15●●●H30 |
SGW15●●●H30 |
— |
SGA25●●●H30 |
SGA15●●●H30 |
||
150 |
6 |
600 |
SHG13●●●H30 |
— |
— |
SHA23●●●H30 |
SHA13●●●H30 |
||
230 |
3 |
0 |
30 |
SBG12●●●H30 [4] |
SBW12●●●H30 [4] |
SBW22●●●H30 [4] |
SBA22●●●H30 [4] |
SBA12●●●H30 [4] |
|
5 |
1 |
30 |
SCG12●●●H30 [4] |
SCW12●●●H30 [4] |
SCW22●●●H30 [4] |
SCA22●●●H30 [4] |
SCA12●●●H30 [4] |
||
7-1/2 |
60 |
SCG13●●●H30 [4] |
SCW13●●●H30 [4] |
SCW23●●●H30 [4] |
SCA23●●●H30 [4] |
SCA13●●●H30 [4] |
|||
15 |
2 |
60 |
SDG12●●●H30 |
SDW12●●●H30 [4] |
SDW22●●●H30 [4] |
SDA22●●●H30 [4] |
SDA12●●●H30 [4] |
||
25 |
3 |
100 |
SEG15●●●H30 |
SEW15●●●H30 |
SEW25●●●H30 |
SEA25●●●H30 |
SEA15●●●H30 |
||
30 |
200 |
SEG12●●●H30 |
SEW12●●●H30 |
— |
SEA22●●●H30 |
SEA12●●●H30 |
|||
50 |
4 |
200 |
SFG15●●●H30 |
SFW15●●●H30 |
— |
SFA25●●●H30 |
SFA15●●●H30 |
||
100 |
5 |
400 |
SGG15●●●H30 |
SGW15●●●H30 |
— |
SGA25●●●H30 |
SGA15●●●H30 |
||
200 |
6 |
600 |
SHG13●●●H30 |
— |
— |
SHA23●●●H30 |
SHA13●●●H30 |
||
460 |
5 |
0 |
30 |
SBG13●●●H30 [4] |
SBW13●●●H30 [4] |
SBW23●●●H30 [4] |
SBA23●●●H30 [4] |
SBA13●●●H30 [4] |
|
10 |
1 |
30 |
SCG14●●●H30 [4] |
SCW14●●●H30 [4] |
SCW24●●●H30 [4] |
SCA24●●●H30 [4] |
SCA14●●●H30 [4] |
||
15 |
2 |
30 |
SDG16●●●H301 |
SDW16●●●H301 |
SDW26●●●H301 |
SDA26●●●H301 |
SDA16●●●H301 |
||
25 |
60 |
SDG14●●●H30 [4] |
SDW14●●●H30 [4] |
SDW24●●●H30 [4] |
SDA24●●●H30 [4] |
SDA14●●●H30 [4] |
|||
50 |
3 |
100 |
SEG13●●●H30 |
SEW13●●●H30 |
SEW23●●●H30 |
SEA23●●●H30 |
SEA13●●●H30 |
||
100 |
4 |
200 |
SFG13●●●H30 |
SFW13●●●H30 |
— |
SFA23●●●H30 |
SFA13●●●H30 |
||
200 |
5 |
400 |
SGG13●●●H30 |
SGW13●●●H30 |
— |
SGA23●●●H30 |
SGA13●●●H30 |
||
400 |
6 |
600 |
SHG12●●●H30 |
— |
— |
SHA22●●●H30 |
SHA12●●●H30 |
||
575 |
5 |
0 |
30 |
SBG13●●●H30 |
SBW13●●●H30 |
SBW23●●●H30 |
SBA23●●●H30 |
SBA13●●●H30 |
|
10 |
1 |
30 |
SCG14●●●H30 |
SCW14●●●H30 |
SCW24●●●H30 |
SCA24●●●H30 |
SCA14●●●H30 |
||
15 |
2 |
30 |
SDG16●●●H301 |
SDW16●●●H301 |
SDW26●●●H301 |
SDA26●●●H301 |
SDA16●●●H301 |
||
25 |
60 |
SDG14●●●H30 |
SDW14●●●H30 |
SDW24●●●H30 |
SDA24●●●H30 |
SDA14●●●H30 |
|||
50 |
3 |
100 |
SEG13●●●H30 |
SEW13●●●H30 |
SEW23●●●H30 |
SEA23●●●H30 |
SEA13●●●H30 |
||
100 |
4 |
200 |
SFG13●●●H30 |
SFW13●●●H30 |
— |
SFA23●●●H30 |
SFA13●●●H30 |
||
200 |
5 |
400 |
SGG13●●●H30 |
SGW13●●●H30 |
— |
SGA23●●●H30 |
SGA13●●●H30 |
||
400 |
6 |
600 |
SHG12●●●H30 |
— |
— |
SHA22●●●H30 |
SHA12●●●H30 |
||
noteSome control transformers may require the use of oversized
enclosures. Refer to Control Transformer Selection.
|
Class 8538 Fusible Disconnect Switch Type (Class H Fuse Clips),
Single Phase, [5][6] with Melting Alloy Overload Relays
(see Thermal Unit
Selection)
Motor |
Max. |
Coil |
NEMA |
Poles |
Fuse Clip Size |
NEMA 1 |
NEMA 4 & 4X |
NEMA 4X |
NEMA 12/3R[2] |
|
---|---|---|---|---|---|---|---|---|---|---|
With |
Without |
|||||||||
Type |
Type |
Type |
Type |
Type |
||||||
120 |
1 |
120 |
0 |
2 |
30 |
|||||
240 |
2 3 7-1/2 |
240 |
0 |
2 |
30 |
For How to Order Information, see Catalog Interpretation, Type S Starters.
Non-Fusible Disconnect Switch Type
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic SSOLR protection), see Solid-State Overload Relay Forms.
Class 8538 Non-Fusible Full Voltage Type, Non-Reversing, with Motor Logic SSOLR (replace ●●● with the voltage code)[1]
Ratings |
NEMA 1 |
NEMA 4X |
NEMA 4X |
NEMA 12/3R[2]Dusttight and Driptight Industrial Enclosure |
|||
---|---|---|---|---|---|---|---|
Motor |
Max. Hp |
NEMA |
With |
Without |
|||
Type [3] |
Type [3] |
Type [3] |
Type [3] |
Type [3] |
|||
200 |
3 10 |
0 |
SBG11●●●H30 [4] SCG11●●●H30 [4] SDG11●●●H30 [4] SEG11●●●H30 SFG11●●●H30 SGG11●●●H30 SHG11●●●H30 |
SBW11●●●H30 [4] SCW11●●●H30 [4] SDW11●●●H30 [4] SEW11●●●H30 SFW11●●●H30 SGW11●●●H30 — |
SBW21●●●H30 [4] SCW21●●●H30 [4] SDW21●●●H30 [4] SEW21●●●H30 — — — |
SBA21●●●H30 [4] SCA21●●●H30 [4] SDA21●●●H30 [4] SEA21●●●H30 SFA21●●●H30 SGA21●●●H30 SHA21●●●H30 |
SBA11●●●H30 [4] SCA11●●●H30 [4] SDA11●●●H30 [4] SEA11●●●H30 SFA11●●●H30 SGA11●●●H30 SHA11●●●H30 |
230 |
3 15 |
0 |
SBG11●●●H30 [4] SCG11●●●H30 [4] SDG11●●●H30 [4] SEG11●●●H30 SFG11●●●H30 SGG11●●●H30 SHG11●●●H30 |
SBW11●●●H30 [4] SCW11●●●H30 [4] SDW11●●●H30 [4] SEW11●●●H30 SFW11●●●H30 SGW11●●●H30 — |
SBW21●●●H30 [4] SCW21●●●H30 [4] SDW21●●●H30 [4] SEW21●●●H30 — — — |
SBA21●●●H30 [4] SCA21●●●H30 [4] SDA21●●●H30 [4] SEA21●●●H30 SFA21●●●H30 SGA21●●●H30 SHA21●●●H30 |
SBA11●●●H30 [4] SCA11●●●H30 [4] SDA11●●●H30 [4] SEA11●●●H30 SFA11●●●H30 SGA11●●●H30 SHA11●●●H30 |
460 |
5 |
0 |
SBG11●●●H30 [4] SCG11●●●H30 [4] SDG11●●●H30 [4] SEG11●●●H30 SFG11●●●H30 SGG11●●●H30 SHG11●●●H30 |
SBW11●●●H30 [4] SCW11●●●H30 [4] SDW11●●●H30 [4] SEW11●●●H30 SFW11●●●H30 SGW11●●●H30 — |
SBW21●●●H30 [4] SCW21●●●H30 [4] SDW21●●●H30 [4] SEW21●●●H30 — — — |
SBA21●●●H30 [4] SCA21●●●H30 [4] SDA21●●●H30 [4] SEA21●●●H30 SFA21●●●H30 SGA21●●●H30 SHA21●●●H30 |
SBA11●●●H30 [4] SCA11●●●H30 [4] SDA11●●●H30 [4] SEA11●●●H30 SFA11●●●H30 SGA11●●●H30 SHA11●●●H30 |
575 |
5 |
0 |
SBG11●●●H30 SCG11●●●H30 SDG11●●●H30 SEG11●●●H30 SFG11●●●H30 SGG11●●●H30 SHG11●●●H30 |
SBW11●●●H30 SCW11●●●H30 SDW11●●●H30 SEW11●●●H30 SFW11●●●H30 SGW11●●●H30 — |
SBW21●●●H30 SCW21●●●H30 SDW21●●●H30 SEW21●●●H30 — — — |
SBA21●●●H30 SCA21●●●H30 SDA21●●●H30 SEA21●●●H30 SFA21●●●H30 SGA21●●●H30 SHA21●●●H30 |
SBA11●●●H30 SCA11●●●H30 SDA11●●●H30 SEA11●●●H30 SFA11●●●H30 SGA11●●●H30 SHA11●●●H30 |
Class 8538 Non-Fusible Disconnect Switch Type, Single Phase,
with Melting Alloy Overload Relay [5] [6]
(see Thermal Unit
Selection)
Motor |
Max. |
Coil |
NEMA |
Poles |
NEMA 1 Enclosure |
NEMA 4 & 4X |
NEMA 4X |
NEMA 12/3R[2] |
|
---|---|---|---|---|---|---|---|---|---|
With |
Without |
||||||||
Type |
Type |
Type |
Type |
Type |
|||||
120 |
1 |
120 |
0 |
2 |
|||||
240 |
2 |
240 |
0 |
2 |
note
Some control transformers may require the use of oversized enclosures. Refer to Control Transformer Selection.
Coil Voltage Codes
Voltage |
Code |
|
---|---|---|
60 Hz |
50 Hz |
|
277 |
— — |
V01 V04 |
note
For voltage codes used with control transformers, see page Selection of Control Circuit Transformers. Form S (separate control) is used when a separate source of power is available for the control (coil) voltage. Form S is available at no charge.
For How to Order Information, see Catalog Interpretation, Type S Starters.
Fusible Disconnect Switch Type with Class R Fuse Clips
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic SSOLR protection), see Solid-State Overload Relay Forms.
Class 8538 Fusible (with Class R Fuse Clips) Full Voltage Type, Non-Reversing, with Motor Logic SSOLR (100,000 AIC Rated) (replace ●●● with the voltage code)[1]
Ratings |
NEMA 1 |
NEMA 4X |
NEMA 4X |
NEMA 12/3R[2] |
||||
---|---|---|---|---|---|---|---|---|
Motor Voltage |
Max. |
NEMA Size |
Fuse Clip |
With |
Without |
|||
Type [9] |
Type [9] |
Type [9] |
Type [9] |
Type [9] |
||||
200 |
3 5 7-1/2 10 |
0 |
30 |
SBG32●●●H30 [4] SCG32●●●H30 [4] SCG33●●●H30 [4] SDG32●●●H30 [4] SEG35●●●H30 SEG32●●●H30 SFG35●●●H30 SGG35●●●H30 SHG33●●●H30 |
SBW32●●●H30 [4] SCW32●●●H30 [4] SCW33●●●H30 [4] SDW32●●●H30 [4] SEW35●●●H30 SEW32●●●H30 SFW35●●●H30 SGW35●●●H30 — |
SBW42●●●H30 [4] SCW42●●●H30 [4] SCW43●●●H30 [4] SDW42●●●H30 [4] SEW45●●●H30 — — — — |
SBA42●●●H30 [4] SCA42●●●H30 [4] SCA43●●●H30 [4] SDA42●●●H30 [4] SEA45●●●H30 SEA42●●●H30 SFA45●●●H30 SGA45●●●H30 SHA43●●●H30 |
SBA32●●●H30 [4] SCA32●●●H30 [4] SCA33●●●H30 [4] SDA32●●●H30 [4] SEA35●●●H30 SEA32●●●H30 SFA35●●●H30 SGA35●●●H30 SHA33●●●H30 |
230 |
3 5 7-1/2 15 |
0 |
30 |
SBG32●●●H30 [4] SCG32●●●H30 [4] SCG33●●●H30 [4] SDG32●●●H30 [4] SEG35●●●H30 SEG32●●●H30 SFG35●●●H30 SGG35●●●H30 SHG33●●●H30 |
SBW32●●●H30 [4] SCW32●●●H30 [4] SCW33●●●H30 [4] SDW32●●●H30 [4] SEW35●●●H30 SEW32●●●H30 SFW35●●●H30 SGW35●●●H30 — |
SBW42●●●H30 [4] SCW42●●●H30 [4] SCW43●●●H30 [4] SDW42●●●H30 [4] SEW45●●●H30 — — — — |
SBA42●●●H30 [4] SCA42●●●H30 [4] SCA43●●●H30 [4] SDA42●●●H30 [4] SEA45●●●H30 SEA42●●●H30 SFA45●●●H30 SGA45●●●H30 SHA43●●●H30 |
SBA32●●●H30 [4] SCA32●●●H30 [4] SCA33●●●H30 [4] SDA32●●●H30 [4] SEA35●●●H30 SEA32●●●H30 SFA35●●●H30 SGA35●●●H30 SHA33●●●H30 |
460 |
5 |
0 |
30 |
SBG33●●●H30 [4] SCG34●●●H30 [4] SDG36●●●H301 SDG34●●●H30 [4] SEG33●●●H30 SFG33●●●H30 SGG33●●●H30 SHG32●●●H30 |
SBW33●●●H30 [4] SCW34●●●H30 [4] SDW36●●●H301 SDW34●●●H30 [4] SEW33●●●H30 SFW33●●●H30 SGW33●●●H30 — |
SBW43●●●H30 [4] SCW44●●●H30 [4] SDW46●●●H301 SDW44●●●H30 [4] SEW43●●●H30 — — — |
SBA43●●●H30 [4] SCA44●●●H30 [4] SDA46●●●H301 SDA44●●●H30 [4] SEA43●●●H30 SFA43●●●H30 SGA43●●●H30 SHA42●●●H30 |
SBA33●●●H30 [4] SCA34●●●H30 [4] SDA36●●●H301 SDA34●●●H30 [4] SEA33●●●H30 SFA33●●●H30 SGA33●●●H30 SHA32●●●H30 |
575 |
5 |
0 |
30 |
SBG33●●●H30 [4] SCG34●●●H30 [4] SDG36●●●H301 SDG34●●●H30 [4] SEG33●●●H30 SFG33●●●H30 SGG33●●●H30 SHG32●●●H30 |
SBW33●●●H30 [4] SCW34●●●H30 [4] SDW36●●●H301 SDW34●●●H30 [4] SEW33●●●H30 SFW33●●●H30 SGW33●●●H30 — |
SBW43●●●H30 [4] SCW44●●●H30 [4] SDW46●●●H301 SDW44●●●H30 [4] SEW43●●●H30 — — — |
SBA43●●●H30 [4] SCA44●●●H30 [4] SDA46●●●H301 SDA44●●●H30 [4] SEA43●●●H30 SFA43●●●H30 SGA43●●●H30 SHA42●●●H30 |
SBA33●●●H30 [4] SCA34●●●H30 [4] SDA36●●●H301 SDA34●●●H30 [4] SEA33●●●H30 SFA33●●●H30 SGA33●●●H30 SHA32●●●H30 |
note
Some control transformers may require the use of oversized enclosures. Refer to Control Transformer Selection.
Class 8538 Fusible Disconnect Switch Type (Class R Fuses), Single Phase with Melting Alloy Overload Relay[5][6] (see Thermal Unit Selection)
Motor |
Max. |
Coil |
NEMA Size |
Poles |
Fuse Clip |
NEMA 1 |
NEMA 4X |
NEMA 4X |
NEMA 12/3R |
|
---|---|---|---|---|---|---|---|---|---|---|
With |
Without |
|||||||||
Type |
Type |
Type |
Type |
Type |
||||||
120 |
1 |
120 |
0 |
2 |
30 |
|||||
240 |
2 7-1/2 |
240 |
0 |
2 |
30 |
Coil Voltage Codes
Voltage |
Code |
|
---|---|---|
60 Hz |
50 Hz |
|
— |
V01 |
note
For voltage codes used with control transformers, see Selection of Control
Circuit Transformers.
Form S (separate control)
is used when a separate source of power is available for the control
(coil) voltage. Form S is available at no charge.
For How to Order Information, see Catalog Interpretation, Type S Starters.
Full Voltage Type with Motor Logic™ Solid-State Overload Relays
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic™ SSOLR protection), see Solid-State Overload Relay Forms.
Class 8538 with Oversized Enclosures (replace ●●● with the voltage code)[1]
Ratings |
NEMA 1 |
NEMA 4X |
NEMA 12/3R[2] |
||||
---|---|---|---|---|---|---|---|
Motor Voltage |
Max. Hp |
NEMA |
Fuse Clip |
With |
Without |
||
Type [9] |
Type [9] |
Type [9] |
Type [9] |
||||
Class 8538 Non-Fusible Disconnect Switch Type—NEMA Size 0–2[12][6] |
|||||||
200 |
3 |
0 |
N/A |
SBG11S8●●●H30 [4] |
SBW11S8●●●H30 [4] |
SBA21S8●●●H30 [4] |
SBA11S8●●●H30 [4] |
7-1/2 |
1 |
N/A |
SCG11S8●●●H30 [4] |
SCW11S8●●●H30 [4] |
SCA21S8●●●H30 [4] |
SCA11S8●●●H30 [4] |
|
10 |
2 |
N/A |
SDG11S8●●●H30 [4] |
SDW11S8●●●H30 [4] |
SDA21S8●●●H30 [4] |
SDA11S8●●●H30 [4] |
|
230 |
3 |
0 |
N/A |
SBG11S8●●●H30 [4] |
SBW11S8●●●H30 [4] |
SBA21S8●●●H30 [4] |
SBA11S8●●●H30 [4] |
7-1/2 |
1 |
N/A |
SCG11S8●●●H30 [4] |
SCW11S8●●●H30 [4] |
SCA21S8●●●H30 [4] |
SCA11S8●●●H30 [4] |
|
15 |
2 |
N/A |
SDG11S8●●●H30 [4] |
SDW11S8●●●H30 [4] |
SDA21S8●●●H30 [4] |
SDA11S8●●●H30 [4] |
|
460 |
5 |
0 |
N/A |
SBG11S8●●●H30 [4] |
SBW11S8●●●H30 [4] |
SBA21S8●●●H30 [4] |
SBA11S8●●●H30 [4] |
10 |
1 |
N/A |
SCG11S8●●●H30 [4] |
SCW11S8●●●H30 [4] |
SCA21S8●●●H30 [4] |
SCA11S8●●●H30 [4] |
|
25 |
2 |
N/A |
SDG11S8●●●H30 [4] |
SDW11S8●●●H30 [4] |
SDA21S8●●●H30 [4] |
SDA11S8●●●H30 [4] |
|
575 |
5 |
0 |
N/A |
SBG11S8●●●H30 [4] |
SBW11S8●●●H30 [4] |
SBA21S8●●●H30 [4] |
SBA11S8●●●H30 [4] |
10 |
1 |
N/A |
SCG11S8●●●H30 [4] |
SCW11S8●●●H30 [4] |
SCA21S8●●●H30 [4] |
SCA11S8●●●H30 [4] |
|
25 |
2 |
N/A |
SDG11S8●●●H30 [4] |
SDW11S8●●●H30 [4] |
SDA21S8●●●H30 [4] |
SDA11S8●●●H30 [4] |
|
Class 8538 Fusible Disconnect Switch Type—NEMA Size 0–2[12][6] |
|||||||
200 |
3 |
0 |
30 |
SBG12S8●●●H30 [4] |
SBW12S8●●●H30 [4] |
SBA22S8●●●H30 [4] |
SBA12S8●●●H30 [4] |
5 |
1 |
30 |
SCG12S8●●●H30 [4] |
SCW12S8●●●H30 [4] |
SCA22S8●●●H30 [4] |
SCA12S8●●●H30 [4] |
|
7-1/2 |
1 |
60 |
SCG13S8●●●H30 [4] |
SCW13S8●●●H30 [4] |
SCA23S8●●●H30 [4] |
SCA13S8●●●H30 [4] |
|
10 |
2 |
60 |
SDG12S8●●●H30 [4] |
SDW12S8●●●H30 [4] |
SDA22S8●●●H30 [4] |
SDA12S8●●●H30 [4] |
|
230 |
3 |
0 |
30 |
SBG12S8●●●H30 [4] |
SBW12S8●●●H30 [4] |
SBA22S8●●●H30 [4] |
SBA12S8●●●H30 [4] |
5 |
1 |
30 |
SCG12S8●●●H30 [4] |
SCW12S8●●●H30 [4] |
SCA22S8●●●H30 [4] |
SCA12S8●●●H30 [4] |
|
7-1/2 |
1 |
60 |
SCG13S8●●●H30 [4] |
SCW13S8●●●H30 [4] |
SCA23S8●●●H30 [4] |
SCA13S8●●●H30 [4] |
|
15 |
2 |
60 |
SDG12S8●●●H30 [4] |
SDW12S8●●●H30 [4] |
SDA22S8●●●H30 [4] |
SDA12S8●●●H30 [4] |
|
460 |
5 |
0 |
30 |
SBG13S8●●●H30 [4] |
SBW13S8●●●H30 [4] |
SBA23S8●●●H30 [4] |
SBA13S8●●●H30 [4] |
10 |
1 |
30 |
SCG14S8●●●H30 [4] |
SCW14S8●●●H30 [4] |
SCA24S8●●●H30 [4] |
SCA14S8●●●H30 [4] |
|
15 |
2 |
30 |
SDG16S8●●●H301 |
SDW16S8●●●H301 |
SDA26S8●●●H301 |
SDA16S8●●●H301 |
|
25 |
2 |
60 |
SDG14S8●●●H30 [4] |
SDW14S8●●●H30 [4] |
SDA24S8●●●H30 [4] |
SDA14S8●●●H30 [4] |
|
575 |
5 |
0 |
30 |
SBG13S8●●●H30 [4] |
SBW13S8●●●H30 [4] |
SBA23S8●●●H30 [4] |
SBA13S8●●●H30 [4] |
10 |
1 |
30 |
SCG14S8●●●H30 [4] |
SCW14S8●●●H30 [4] |
SCA24S8●●●H30 [4] |
SCA14S8●●●H30 [4] |
|
15 |
2 |
30 |
SDG16S8●●●H301 |
SDW16S8●●●H301 |
SDA26S8●●●H301 |
SDA16S8●●●H301 |
|
25 |
2 |
60 |
SDG14S8●●●H30 [4] |
SDW14S8●●●H30 [4] |
SDA24S8●●●H30 [4] |
SDA14S8●●●H30 [4] |
|
Class 8538 Fusible Disconnect Switch Type with Class R Fuse Clips—NEMA Size 0–2[12][6] |
|||||||
200 |
3 |
0 |
30 |
SBG32S8●●●H30 [4] |
SBW32S8●●●H30 [4] |
SBA42S8●●●H30 [4] |
SBA32S8●●●H30 [4] |
5 |
1 |
30 |
SCG32S8●●●H30 [4] |
SCW32S8●●●H30 [4] |
SCA42S8●●●H30 [4] |
SCA32S8●●●H30 [4] |
|
7-1/2 |
1 |
60 |
SCG33S8●●●H30 [4] |
SCW33S8●●●H30 [4] |
SCA43S8●●●H30 [4] |
SCA33S8●●●H30 [4] |
|
10 |
2 |
60 |
SDG32S8●●●H30 [4] |
SDW32S8●●●H30 [4] |
SDA42S8●●●H30 [4] |
SDA32S8●●●H30 [4] |
|
230 |
3 |
0 |
30 |
SBG32S8●●●H30 [4] |
SBW32S8●●●H30 [4] |
SBA42S8●●●H30 [4] |
SBA32S8●●●H30 [4] |
5 |
1 |
30 |
SCG32S8●●●H30 [4] |
SCW32S8●●●H30 |
SCA42S8●●●H30 |
SCA32S8●●●H30 |
|
7-1/2 |
1 |
60 |
SCG33S8●●●H30 |
SCW33S8●●●H30 [4] |
SCA43S8●●●H30 [4] |
SCA33S8●●●H30 [4] |
|
15 |
2 |
60 |
SDG32S8●●●H30 [4] |
SDW32S8●●●H30 [4] |
SDA42S8●●●H30 [4] |
SDA32S8●●●H30 [4] |
|
460 |
5 |
0 |
30 |
SBG33S8●●●H30 [4] |
SBW33S8●●●H30 [4] |
SBA43S8●●●H30 [4] |
SBA33S8●●●H30 [4] |
10 |
1 |
30 |
SCG34S8●●●H30 [4] |
SCW34S8●●●H30 [4] |
SCA44S8●●●H30 [4] |
SCA34S8●●●H30 [4] |
|
15 |
2 |
30 |
SDG36S8●●●H301 |
SDW36S8●●●H301 |
SDA46S8●●●H301 |
SDA36S8●●●H301 |
|
25 |
2 |
60 |
SDG34S8●●●H30 [4] |
SDW34S8●●●H30 [4] |
SDA44S8●●●H30 [4] |
SDA34S8●●●H30 [4] |
|
575 |
5 |
0 |
30 |
SBG33S8●●●H30 [4] |
SBW33S8●●●H30 [4] |
SBA43S8●●●H30 [4] |
SBA33S8●●●H30 [4] |
10 |
1 |
30 |
SCG34S8●●●H30 [4] |
SCW34S8●●●H30 [4] |
SCA44S8●●●H30 [4] |
SCA34S8●●●H30 [4] |
|
15 |
2 |
30 |
SDG36S8●●●H301 |
SDW36S8●●●H301 |
SDA46S8●●●H301 |
SDA36S8●●●H301 |
|
25 |
2 |
60 |
SDG34S8●●●H30 [4] |
SDW34S8●●●H30 [4] |
SDA44S8●●●H30 [4] |
SDA34S8●●●H30 [4] |
|
noteSome
control transformers may require the use of oversized enclosures.
Refer to Control Transformer Selection
|
Coil Voltage Codes
Voltage |
Code |
|
---|---|---|
60 Hz |
50 Hz |
|
24[13] 120[14] 208 240 277 480 600 Specify |
— 110 — 220 — 440 550 Specify |
V01 V02 V08 V03 V04 V06 V07 V99 |
noteFor
voltage codes used with control transformers, see Selection of Control
Circuit Transformers.
|
Class 8538 Fusible Disconnect Switch Type for Horizontal Mounting[6] (replace ●●● with the voltage code)[1]
Ratings |
NEMA 12/3R [2] Dusttight and Driptight Industrial Use Enclosure |
||||
---|---|---|---|---|---|
Motor Voltage |
Max. Hp |
NEMA |
Fuse Clip |
With External Reset |
Without External Reset |
Type [9] |
Type [9] |
||||
200 (208) |
2 |
1 |
30 |
SCA22S1●●●H30 |
SCA12S1●●●H30 |
7-1/2 |
1 |
60 |
SCA23S1●●●H30 |
SCA13S1●●●H30 |
|
230 (240) |
2 |
1 |
30 |
SCA22S1●●●H30 |
SCA12S1●●●H30 |
7-1/2 |
1 |
60 |
SCA23S1●●●H30 |
SCA13S1●●●H30 |
|
460 (480) |
10 |
1 |
30 |
SCA24S1●●●H30 |
SCA14S1●●●H30 |
575 (600) |
10 |
1 |
30 |
SCA24S1●●●H30 |
SCA14S1●●●H30 |
For How to Order Information, see Catalog Interpretation, Type S Starters.
Class 8539 / Refer to Catalog 8538CT9701
Electronic Motor Circuit Protector (MCP)
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic SSOLR protection), see Solid-State Overload Relay Forms.
Class 8539 Full Voltage Type, Non-Reversing, 200–240
V, with Motor Logic SSOLR
(replace ●●●
with the voltage code)[1]
Ratings |
NEMA 1 |
NEMA 4X |
NEMA 4X |
NEMA 12/3R[2] |
||||
---|---|---|---|---|---|---|---|---|
Motor Voltage |
Hp |
NEMA |
Circuit Breaker |
Type [9] |
Type [9] |
Type [9] |
With |
Without |
Type [9] |
Type [9] |
|||||||
200 |
0.25–3 |
0 |
HLL36030M71 |
SBG43●●●H30 [4] |
SBW43●●●H30 [4] |
SBW53●●●H30 [4] |
SBA53●●●H30 [4] |
SBA43●●●H30 [4] |
0.25–5 7.5 |
1 |
HLL36030M71 HLL36050M72 |
SCG44●●●H30 [4] SCG45●●●H30 [4] |
SCW44●●●H30 [4] SCW45●●●H30 [4] |
SCW54●●●H30 [4] SCW55●●●H30 [4] |
SCA54●●●H30 [4] SCA55●●●H30 [4] |
SCA44●●●H30 [4] SCA45●●●H30 [4] |
|
1.5–5 7.5–10 |
2 |
HLL36030M71 HLL36050M72 |
SDG42●●●H301 SDG43●●●H30 [4] |
SDW42●●●H301 SDW43●●●H30 [4] |
SDW52●●●H301 SDW53●●●H30 [4] |
SDA52●●●H301 SDA53●●●H30 [4] |
SDA42●●●H301 SDA43●●●H30 [4] |
|
15–25 |
3 |
HLL36100M73 |
SEG42●●●H30 |
SEW42●●●H30 |
SEW52●●●H30 |
SEA52●●●H30 |
SEA42●●●H30 |
|
30–40 |
4 |
JLL36250M75 |
SFG44●●●H30 |
SFW44●●●H30 |
SFW54●●●H30 |
SFA54●●●H30 |
SFA44●●●H30 |
|
50–60 75 |
5 |
JLL36250M75 LJL36400M36 |
SGG44●●●H30 SGG45●●●H30 |
SGW44●●●H30 SGW45●●●H30 |
— — |
SGA54●●●H30 SGA55●●●H30 |
SGA44●●●H30 SGA45●●●H30 |
|
100 125–150 |
6 |
LJL36400M36 LJL36600M42 |
SHG43●●●H30 SHG45●●●H30 |
— — |
— — |
SHA53●●●H30 SHA55●●●H30 |
SHA43●●●H30 SHA45●●●H30 |
|
230 |
0.25–3 |
0 |
HLL36030M71 |
SBG43●●●H30 [4] |
SBW43●●●H30 [4] |
SBW53●●●H30 [4] |
SBA53●●●H30 [4] |
SBA43●●●H30 [4] |
0.25–7.5 |
1 |
HLL36030M71 |
SCG44●●●H30 [4] |
SCW44●●●H30 [4] |
SCW54●●●H30 [4] |
SCA54●●●H30 [4] |
SCA44●●●H30 [4] |
|
1.5–7.5 10 15 |
2 |
HLL36030M71 HLL36050M72 HLL36100M73 |
SDG42●●●H301 SDG43●●●H30 [4] SDG44●●●H30 [4] |
SDW42●●●H301 SDW43●●●H30 [4] SDW44●●●H30 [4] |
SDW52●●●H301 SDW53●●●H30 [4] SDW54●●●H30 [4] |
SDA52●●●H301 SDA53●●●H30 [4] SDA54●●●H30 [4] |
SDA42●●●H301 SDA43●●●H30 [4] SDA44●●●H30 [4] |
|
15–30 |
3 |
HLL36100M73 |
SEG42●●●H30 |
SEW42●●●H30 |
SEW52●●●H30 |
SEA52●●●H30 |
SEA42●●●H30 |
|
40–50 |
4 |
JLL36250M75 |
SFG44●●●H30 |
SFW44●●●H30 |
SFW54●●●H30 |
SFA54●●●H30 |
SFA44●●●H30 |
|
60 75–100 |
5 |
JLL36250M75 LJL36400M36 |
SGG44●●●H30 SGG46●●●H30 |
SGW44●●●H30 SGW45●●●H30 |
— — |
SGA54●●●H30 SGA55●●●H30 |
SGA44●●●H30 SGA45●●●H30 |
|
125–150 200 |
6 |
LJL36600M42 PLL34080M68 |
SHG45●●●H30 SHG46●●●H30 |
— — |
— — |
SHA55●●●H30 SHA56●●●H30 |
SHA45●●●H30 SHA46●●●H30 |
note
Coil Voltage Codes
Voltage |
Code |
|
---|---|---|
60 Hz |
50 Hz |
|
277 |
— — |
V01 V04 |
note
Form S (separate control) is used when a separate source of power is available for the control (coil) voltage. Form S is available at no charge.
Dimensions: Approximate Dimensions
Factory
Modifications (Forms): Full Voltage Starters
Replacement
Parts (Class 9998): Magnetic Coils
Type S Accessories
(Class 9999): Contact Kits
For How to Order Information, see Catalog Interpretation, Type S Starters.
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic SSOLR protection), see Solid-State Overload Relay Forms.
Class 8539 Full Voltage Type, Non-Reversing, 460–600 V, with Motor Logic SSOLR and Electronic Motor Circuit Protector (MCP) (replace ●●● with the voltage code)[1]
Ratings |
NEMA 1 |
NEMA 4X |
NEMA 4X |
NEMA 12/3R[2] |
||||
---|---|---|---|---|---|---|---|---|
Motor Voltage (Starter Voltage) |
Hp Range Polyphase |
NEMA |
Circuit Breaker (See Page 7-32 for Breaker Adjustment Range) |
Type [9] |
Type [9] |
Type [9] |
With |
Without |
Type [9] |
Type [9] |
|||||||
460 |
0.25–5 |
0 |
HLL36030M71 |
SBG43●●●H30 [4] |
SBW43●●●H30 [4] |
SBW53●●●H30 [4] |
SBA53●●●H30 [4] |
SBA43●●●H30 [4] |
0.25–10 |
1 |
HLL36030M71 |
SCG44●●●H30 [4] |
SCW44●●●H30 [4] |
SCW54●●●H30 [4] |
SCA54●●●H30 [4] |
SCA44●●●H30 [4] |
|
5–15 |
2 |
HLL36030M71 HLL36050M72 |
SDG42●●●H301 SDG43●●●H30 |
SDW42●●●H301 SDW43●●●H30 [4] |
SDW52●●●H301 SDW53●●●H30 [4] |
SDA52●●●H301 SDA53●●●H30 [4] |
SDA42●●●H301 SDA43●●●H30 [4] |
|
20–25 |
3 |
HLL36050M72 HLL36100M73 |
SEG41●●●H30 SEG42●●●H30 |
SEW41●●●H30 SEW42●●●H30 |
SEW51●●●H30 SEW52●●●H30 |
SEA51●●●H30 SEA52●●●H30 |
SEA41●●●H30 SEA42●●●H30 |
|
60–100 |
4 |
JLL36250M75 |
SFG44●●●H30 |
SFW44●●●H30 |
SFW54●●●H30 |
SFA54●●●H30 |
SFA44●●●H30 |
|
125 |
5 |
JLL36250M75 LJL36400M36 |
SGG44●●●H30 SGG45●●●H30 |
SGW44●●●H30 SGW45●●●H30 |
— — |
SGA54●●●H30 SGA55●●●H30 |
SGA44●●●H30 SGA45●●●H30 |
|
250–350 |
6 |
LJL36600M42 PLL34080M68 |
SHG45●●●H30 SHG46●●●H30 |
— — |
— — |
SHA55●●●H30 SHA56●●●H30 |
SHA45●●●H30 SHA46●●●H30 |
|
575 |
0.25–5 |
0 |
HLL36030M71 |
SBG43●●●H30 [4] |
SBW43●●●H30 [4] |
SBW53●●●H30 [4] |
SBA53●●●H30 [4] |
SBA43●●●H30 [4] |
0.25–10 |
1 |
HLL36030M71 |
SCG44●●●H30 [4] |
SCW44●●●H30 [4] |
SCW54●●●H30 [4] |
SCA54●●●H30 [4] |
SCA44●●●H30 [4] |
|
5–20 |
2 |
HLL36030M71 HLL36050M72 |
SDG42●●●H301 SDG43●●●H30 [4] |
SDW42●●●H301 SDW43●●●H30 [4] |
SDW52●●●H301 SDW53●●●H30 [4] |
SDA52●●●H301 SDA53●●●H30 [4] |
SDA42●●●H301 SDA43●●●H30 [4] |
|
25–30 |
3 |
HLL36050M72 HLL36100M73 |
SEG41●●●H30 SEG42●●●H30 |
SEW41●●●H30 SEW42●●●H30 |
SEW51●●●H30 SEW52●●●H30 |
SEA51●●●H30 SEA52●●●H30 |
SEA41●●●H30 SEA42●●●H30 |
|
60–100 |
4 |
JLL36250M75 |
SFG44●●●H30 |
SFW44●●●H30 |
SFW54●●●H30 |
SFA54●●●H30 |
SFA44●●●H30 |
|
125–150 |
5 |
JLL36250M75 LJL36400M36 |
SGG44●●●H30 SGG45●●●H30 |
SGW44●●●H30 SGW45●●●H30 |
— — |
SGA54●●●H30 SGA55●●●H30 |
SGA44●●●H30 SGA45●●●H30 |
|
250 |
6 |
LJL36400M36 LJL36600M42 |
SHG43●●●H30 SHG45●●●H30 |
— — |
— — |
SHA53●●●H30 SHA55●●●H30 |
SHA43●●●H30 SHA45●●●H30 |
note
Coil Voltage Codes
Voltage |
Code |
|
---|---|---|
60 Hz |
50 Hz |
|
277 |
— — |
V01 V04 |
note
For voltage codes used with control transformers, see Selection of Control
Circuit Transformers.
Form S (separate control)
is used when a separate source of power is available for the control
(coil) voltage. Form S is available at no charge.
Dimensions: Approximate Dimensions
Factory
Modifications (Forms): Full Voltage Starters
Replacement
Parts (Class 9998): DP Starters
Type S Accessories
(Class 9999): Contact Kits
For How to Order Information, see Catalog Interpretation, Type S Starters.
NEMA Size 0–2 in Oversized Enclosure
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic™ SSOLR protection), see Solid-State Overload Relay Forms.
Class 8539 Electronic Motor Circuit Protectors (MCP) in Oversized
Enclosure, NEMA Size 0–2[1][19][20]
Full
Voltage Type, Non-Reversing with Motor Logic SSOLR (replace ●●●
with the voltage code)
Ratings |
NEMA 1 |
NEMA 4X |
NEMA 12/3R[2] |
||||
---|---|---|---|---|---|---|---|
Motor Voltage (Starter Voltage) |
Hp Range Polyphase |
NEMA |
Circuit Breaker (See Page 7-32 for Breaker Adjustment Range) |
With |
Without |
||
Type [9] |
Type [9] |
Type [9] |
Type [9] |
||||
200 |
0.25–3 |
0 |
HLL36030M71 |
SBG43S8●●●H30[4] |
SBW43S8●●●H30[4] |
SBA53S8●●●H30[4] |
SBA43S8●●●H30[4] |
0.25–5 |
1 |
HLL36030M71 HLL36050M72 |
SCG44S8●●●H30[4] SCG45S8●●●H30[4] |
SCW44S8●●●H30[4] SCW45S8●●●H30[4] |
SCA54S8●●●H30[4] SCA55S8●●●H30[4] |
SCA44S8●●●H30[4] SCA45S8●●●H30[4] |
|
1.5–5 |
2 |
HLL36030M71 HLL36050M72 |
SDG42S8●●●H301 SDG43S8●●●H30[4] |
SDW42S8●●●H301 SDW43S8●●●H30[4] |
SDA52S8●●●H301 SDA53S8●●●H30[4] |
SDA42S8●●●H301 SDA43S8●●●H30[4] |
|
230 |
0.25–3 |
0 |
HLL36030M71 |
SBG43S8●●●H30[4] |
SBW43S8●●●H30[4] |
SBA53S8●●●H30[4] |
SBA43S8●●●H30[4] |
0.25–7.5 |
1 |
HLL36030M71 |
SCG44S8●●●H30[4] |
SCW44S8●●●H30[4] |
SCA54S8●●●H30[4] |
SCA44S8●●●H30[4] |
|
1.5–7.5 |
2 |
HLL36030M71 HLL36050M72 HLL36100M73 |
SDG42S8●●●H301 SDG43S8●●●H30[4] SDG44S8●●●H30[4] |
SDW42S8●●●H301 SDW43S8●●●H30[4] SDW44S8●●●H30[4] |
SDA52S8●●●H301 SDA53S8●●●H30[4] SDA54S8●●●H30[4] |
SDA42S8●●●H301 SDA43S8●●●H30[4] SDA44S8●●●H30[4] |
|
460 |
0.25–5 |
0 |
HLL36030M71 |
SBG43S8●●●H30[4] |
SBW43S8●●●H30[4] |
SBA53S8●●●H30[4] |
SBA43S8●●●H30[4] |
0.25–10 |
1 |
HLL36030M71 |
SCG44S8●●●H30[4] |
SCW44S8●●●H30[4] |
SCA54S8●●●H30[4] |
SCA44S8●●●H30[4] |
|
5–15 |
2 |
HLL36030M71 HLL36050M72 |
SDG42S8●●●H301 SDG43S8●●●H30[4] |
SDW42S8●●●H301 SDW43S8●●●H30[4] |
SDA52S8●●●H301 SDA53S8●●●H30[4] |
SDA42S8●●●H301 SDA43S8●●●H30[4] |
|
575 |
0.25–5 |
0 |
HLL36060M71 |
SBG43S8●●●H30[4] |
SBW43S8●●●H30[4] |
SBA53S8●●●H30[4] |
SBA43S8●●●H30[4] |
0.25–10 |
1 |
HLL36030M71 |
SCG44S8●●●H30[4] |
SCW44S8●●●H30[4] |
SCA54S8●●●H30[4] |
SCA44S8●●●H30[4] |
|
5–20 |
2 |
HLL36030M71 HLL36050M72 |
SDG42S8●●●H301 SDG43S8●●●H30[4] |
SDW42S8●●●H301 SDW43S8●●●H30[4] |
SDA52S8●●●H301 SDA53S8●●●H30[4] |
SDA42S8●●●H301 SDA43S8●●●H30[4] |
note
Some control transformers may require the use of oversized enclosures. Refer to Control Transformer Selection.
Coil Voltage Codes
Voltage |
Code |
|
---|---|---|
60 Hz |
50 Hz |
|
277 |
— — |
V01 V04 |
note
For voltage codes used with control transformers, see Selection of Control
Circuit Transformers.
Form S (separate control)
is used when a separate source of power is available for the control
(coil) voltage. Form S is available at no charge.
Dimensions: Approximate Dimensions
Factory
Modifications (Forms): Full Voltage Starters
Replacement
Parts (Class 9998): Magnetic Coils
Type S Accessories
(Class 9999): Contact Units for Melting Alloy Type Overload Relays
For How to Order Information, see Catalog Interpretation, Type S Starters.
Thermal Magnetic Circuit Breaker
Full Voltage Type
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic SSOLR protection), see Solid-State Overload Relay Forms.
Class 8539 Full Voltage, Thermal-Magnetic Circuit Breaker Type, Non-Reversing, with Motor Logic SSOLR (replace ●●● with the voltage code)[1]
Ratings |
NEMA 1 |
NEMA 4X |
NEMA 4X |
NEMA 12/3R[2] |
|||||
---|---|---|---|---|---|---|---|---|---|
Motor |
Max. Hp |
NEMA |
Circuit Breaker |
Type [23] |
Type [23] |
Type [23] |
With |
Without |
|
Type |
Ampere |
Type [23] |
Type [23] |
||||||
200 |
2 |
0 |
HLL36015 HLL36020 |
15 |
SBG1●●●H30 [4] SBG3●●●H30 [4] |
SBW1●●●H30 [4] SBW3●●●H30 [4] |
SBW11●●●H30 [4] SBW13●●●H30 [4] |
SBA11●●●H30 [4] SBA13●●●H30 [4] |
SBA1●●●H30 [4] SBA3●●●H30 [4] |
5 |
1 |
HLL36035 |
35 |
SCG5●●●H30 [4] SCG2●●●H30 [4] |
SCW5●●●H30 [4] SCW2●●●H30 [4] |
SCW15●●●H30 [4] SCW12●●●H30 [4] |
SCA15●●●H30 [4] SCA12●●●H30 [4] |
SCA5●●●H30 [4] SCA2●●●H30 [4] |
|
10 |
2 |
HLL36060 |
60 |
SDG1●●●H30 [4] |
SDW1●●●H30 [4] |
SDW11●●●H30 [4] |
SDA11●●●H30 [4] |
SDA1●●●H30 [4] |
|
15 |
3 |
HLL36100 |
100 |
SEG3●●●H30 SEG1●●●H30 SEG5●●●H30 |
SEW3●●●H30 SEW1●●●H30 SEW5●●●H30 |
SEW13●●●H30 SEW11●●●H30 SEW15●●●H30 |
SEA13●●●H30 SEA11●●●H30 SEA15●●●H30 |
SEA3●●●H30 SEA1●●●H30 SEA5●●●H30 |
|
30 |
4 |
JLL36200 |
200 |
SFG3●●●H30 SFG4●●●H30 |
SFW3●●●H30 SFW4●●●H30 |
SFW13●●●H30 SFW14●●●H30 |
SFA13●●●H30 SFA14●●●H30 |
SFA3●●●H30 SFA4●●●H30 |
|
50 |
5 |
JLL36250 |
250 |
SGG6●●●H30 SGG4●●●H30 |
SGW6●●●H30 SGW4●●●H30 |
— — |
SGA16●●●H30 SGA14●●●H30 |
SGA6●●●H30 SGA4●●●H30 |
|
100–125 |
6 |
LLL36600U33X |
600 |
SHG4●●●H30 SHG5●●●H30 |
— — |
— — |
SHA14●●●H30 SHA15●●●H30 |
SHA4●●●H30 SHA5●●●H30 |
|
230 |
2 |
0 |
HLL36015 |
15 |
SBG1●●●H30 [4] SBG3●●●H30 [4] |
SBW1●●●H30 [4] SBW3●●●H30 [4] |
SBW11●●●H30 [4] SBW13●●●H30 [4] |
SBA11●●●H30 [4] SBA13●●●H30 [4] |
SBA1●●●H30 [4] SBA3●●●H30 [4] |
5 |
1 |
HLL36035 |
35 |
SCG5●●●H30 [4] SCG6●●●H30 [4] |
SCW5●●●H30 [4] SCW6●●●H30 [4] |
SCW15●●●H30 [4] SCW16●●●H30 [4] |
SCA15●●●H30 [4] SCA16●●●H30 [4] |
SCA1●●●H30 [4] SCA6●●●H30 [4] |
|
10 |
2 |
HLL36060 |
60 |
SDG1●●●H30 [4] SDG7●●●H30 [4] |
SDW1●●●H30 [4] SDW7●●●H30 [4] |
SDW11●●●H30 [4] SDW17●●●H30 [4] |
SDA11●●●H30 [4] SDA17●●●H30 [4] |
SDA1●●●H30 [4] SDA7●●●H30 [4] |
|
20 |
3 |
HLL36100 |
100 |
SEG3●●●H30 SEG5●●●H30 |
SEW3●●●H30 SEW5●●●H30 |
SEW13●●●H30 SEW15●●●H30 |
SEA13●●●H30 SEA15●●●H30 |
SEA3●●●H30 SEA5●●●H30 |
|
40 |
4 |
JLL36225 |
225 |
SFG1●●●H30 SFG4●●●H30 |
SFW1●●●H30 SFW4●●●H30 |
SFW11●●●H30 SFW14●●●H30 |
SFA11●●●H30 SFA14●●●H30 |
SFA1●●●H30 SFA4●●●H30 |
|
60 |
5 |
JLL36250 |
250 |
SGG6●●●H30 SGG4●●●H30 SGG2●●●H30 |
SGW6●●●H30 SGW4●●●H30 SGW2●●●H30 |
— — — |
SGA16●●●H30 SGA14●●●H30 SGA12●●●H30 |
SGA6●●●H30 SGA4●●●H30 SGA2●●●H30 |
|
125 |
6 |
LLL36600U33X |
600 |
SHG4●●●H30 SHG5●●●H30 |
— — |
— — |
SHA14●●●H30 SHA15●●●H30 |
SHA4●●●H30 SHA5●●●H30 |
note
Coil Voltage Codes
Voltage |
Code |
|
---|---|---|
60 Hz |
50 Hz |
|
277 |
— — |
V01 V04 |
note
For voltage codes used with control transformers, see Selection of Control Circuit Transformers. Form S (separate control) is used when a separate source of power is available for the control (coil) voltage. Form S is provided at no charge.
Dimensions: Approximate Dimensions
Factory
Modifications (Forms): Full Voltage Starters
Replacement
Parts (Class 9998): Magnetic Coils
Type S Accessories
(Class 9999): Contact Kits
For How to Order Information, see Catalog Interpretation, Type S Starters.
Line Voltage Type
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic SSOLR protection), see Solid-State Overload Relay Forms.
Class 8539 Line Voltage, Thermal-Magnetic Circuit Breaker Type, Non-Reversing, with Motor Logic SSOLR (replace ●●● with the voltage code)[1]
Ratings |
NEMA® 1 |
NEMA 4X |
NEMA 4X |
NEMA 12/3R[2] |
|||||
---|---|---|---|---|---|---|---|---|---|
Motor Voltage (Starter |
Max. Hp Polyphase |
NEMA |
Circuit Breaker |
Type [23] |
Type [23] |
Type [23] |
With |
Without |
|
Type |
Ampere |
Type [23] |
Type [23] |
||||||
460 |
5 |
0 |
HLL36015 |
15 |
SBG1●●●H30 [4] |
SBW1●●●H30 [4] |
SBW11●●●H30 [4] |
SBA11●●●H30 [4] |
SBA1●●●H30 [4] |
7.5 10 |
1 |
HLL36025 |
25 30 |
SCG3●●●H30 [4] SCG7●●●H30 [4] |
SCW3●●●H30 [4] SCW7●●●H30 [4] |
SCW13●●●H30 [4] SCW17●●●H30 [4] |
SCA13●●●H30 [4] SCA17●●●H30 [4] |
SCA3●●●H30 [4] SCA7●●●H30 [4] |
|
15 20 25 |
2 |
HLL36045 |
45 60 70 |
SDG3●●●H30 [4] SDG1●●●H30 [4] SDG5●●●H30 [4] |
SDW3●●●H30 [4] SDW1●●●H30 [4] SDW5●●●H30 [4] |
SDW13●●●H30 [4] SDW11●●●H30 [4] SDW15●●●H30 [4] |
SDA13●●●H30 [4] SDA11●●●H30 [4] SDA15●●●H30 [4] |
SDA3●●●H30 [4] SDA1●●●H30 [4] SDA5●●●H30 [4] |
|
30 40 50 |
3 |
HLL36080 |
80 100 150 |
SEG7●●●H30 SEG3●●●H30 SEG5●●●H30 |
SEW7●●●H30 SEW3●●●H30 SEW5●●●H30 |
SEW17●●●H30 SEW13●●●H30 SEW15●●●H30 |
SEA17●●●H30 SEA13●●●H30 SEA15●●●H30 |
SEA7●●●H30 SEA3●●●H30 SEA5●●●H30 |
|
60 75 100 |
4 |
JLL36150 |
150 200 250 |
SFG5●●●H30 SFG3●●●H30 SFG4●●●H30 |
SFW5●●●H30 SFW3●●●H30 SFW4●●●H30 |
SFW15●●●H30 SFW13●●●H30 SFW14●●●H30 |
SFA15●●●H30 SFA13●●●H30 SFA14●●●H30 |
SFA5●●●H30 SFA3●●●H30 SFA4●●●H30 |
|
125–150 200 |
5 |
LLL36400U33X |
400 600 |
SGG4●●●H30 SGG2●●●H30 |
SGW4●●●H30 SGW2●●●H30 |
— — |
SGA14●●●H30 SGA12●●●H30 |
SGA4●●●H30 SGA2●●●H30 |
|
250 300–400 |
6 |
LLL36600U33X |
600 800 |
SHG4●●●H30 SHG5●●●H30 |
— — |
— — |
SHA14●●●H30 SHA15●●●H30 |
SHA4●●●H30 SHA5●●●H30 |
|
575 |
5 |
0 |
HLL36015 |
15 |
SBG1●●●H30 [4] |
SBW1●●●H30 [4] |
SBW11●●●H30 [4] |
SBA11●●●H30 [4] |
SBA1●●●H30 [4] |
7.5 10 |
1 |
HLL36020 |
20 25 |
SCG8●●●H30 [4] SCG3●●●H30 [4] |
SCW8●●●H30 [4] SCW3●●●H30 [4] |
SCW18●●●H30 [4] SCW13●●●H30 [4] |
SCA18●●●H30 [4] SCA13●●●H30 [4] |
SCA8●●●H30 [4] SCA3●●●H30 [4] |
|
15 20 25 |
2 |
HLL36035 |
35 45 60 |
SDG8●●●H301 SDG3●●●H30 [4] SDG1●●●H30 [4] |
SDW8●●●H301 SDW3●●●H30 [4] SDW1●●●H30 [4] |
SDW18●●●H301 SDW13●●●H30 [4] SDW11●●●H30 [4] |
SDA18●●●H301 SDA13●●●H30 [4] SDA11●●●H30 [4] |
SDA8●●●H301 SDA3●●●H30 [4] SDA1●●●H30 [4] |
|
30 40 50 |
3 |
HLL36070 HLL36100 |
70 90 100 |
SEG4●●●H30 SEG6●●●H30 SEG3●●●H30 |
SEW4●●●H30 SEW6●●●H30 SEW3●●●H30 |
SEW14●●●H30 SEW16●●●H30 SEW13●●●H30 |
SEA14●●●H30 SEA16●●●H30 SEA13●●●H30 |
SEA4●●●H30 SEA6●●●H30 SEA3●●●H30 |
|
60–75 100 |
4 |
JLL36150 |
150 250 |
SFG5●●●H30 SFG4●●●H30 |
SFW5●●●H30 SFW4●●●H30 |
SFW15●●●H30 SFW14●●●H30 |
SFA15●●●H30 SFA14●●●H30 |
SFA5●●●H30 SFA4●●●H30 |
|
125–150 200 |
5 |
JLL36250 |
250 400 |
SGG6●●●H30 SGG4●●●H30 |
SGW6●●●H30 SGW4●●●H30 |
— — |
SGA16●●●H30 SGA14●●●H30 |
SGA6●●●H30 SGA4●●●H30 |
|
250–350 400 |
6 |
LLL36600U33X |
600 800 |
SHG4●●●H30 SHG5●●●H30 |
— — |
— — |
SHA14●●●H30 SHA15●●●H30 |
SHA4●●●H30 SHA5●●●H30 |
Class 8539 Thermal Magnetic Circuit Breaker Type, Single Phase[6][26] with Melting Alloy Overload Relays
Motor Voltage |
Max. Hp |
Coil Voltage |
NEMA Size |
Poles |
Circuit Breaker |
Ampere Rating |
NEMA 1 |
NEMA 4 & 4X |
NEMA 4 & 4X |
NEMA 12/3R[2] |
|
---|---|---|---|---|---|---|---|---|---|---|---|
With |
Without |
||||||||||
Type |
Type |
Type |
Type |
Type |
|||||||
120 |
1 2 3 |
120 |
0 1 2 |
2 |
HLL26030 |
30 50 80 |
|||||
240 |
2 3 7.5 |
240 |
0 1 2 |
2 |
HLL26025 |
25 35 80 |
noteSome control transformers may require
the use of oversized enclosures. |
Class 8538, 8539 / Refer to Catalog 8538CT9701
Application Data
Class 8539—UL Listed Short Circuit Ratings
Motor Circuit Protector Type |
|||
---|---|---|---|
NEMA Size |
Enclosure |
AIC at 480 Vac (RMS) |
AIC at 600 Vac (RMS) |
0, 1 |
Standard[27] |
100,000 |
35,000 |
2 thru 5 |
Standard[27] |
100,000 |
50,000 |
6 |
Standard[27] |
65,000 |
18,000 |
Electronic Motor Circuit Protector (MCP) Selection by HP Ratings of Induction-type Squirrel-Cage Motors
3Ø, 60 Hz Voltages |
Full-Load |
Suffix |
|||
---|---|---|---|---|---|
200 Vac |
230 Vac |
460 Vac |
575 Vac |
||
.5–5 |
.5–7.5 |
.75–15 |
1–20 |
1.5–25 |
M71 |
5–10 |
5–15 |
10–30 |
15–40 |
14–42 |
M72 |
10–25 |
15–30 |
25–60 |
30–75 |
30–80 |
M73 |
20–40 |
25–50 |
50–100 |
60–125 |
58–130 |
M74 |
40–60 |
50–75 |
100–150 |
125–200 |
114–217 |
M75 |
noteThe MCP adjustable trip range is determined by the suffix of the circuit breaker catalog number. This table indicates the trip range which corresponds to a given suffix number. The MCP motor circuit protector should be adjusted to a level just above locked-rotor current of the motor. This setting will provide optimum overcurrent protection for the motor. For more information on MCP instantaneous-trip circuit breakers, refer to the MCP circuit breaker section of this catalog. |
Class 8539, UL Listed Short Circuit Ratings
Thermal Magnetic Circuit Breaker Type |
|||
---|---|---|---|
NEMA Size |
Enclosure |
AIC at 480 Vac (RMS) |
AIC at 600 Vac (RMS) |
0, 1 |
Standard [27] |
100,000 |
35,000 |
2 thru 5 |
Standard [27] |
100,000 |
50,000 |
6 |
Standard [27] |
65,000 |
18,000 |
Class 8538—UL Listed Short Circuit Ratings
NEMA Size |
NEMA Fuse |
Enclosure |
Available Amperes |
---|---|---|---|
0–3 |
Class H or K |
Standard [28] |