Full Voltage
Class 8941
Selection
Duplex Motor Controllers are used to control two motors, and consist of two starters in a common enclosure. Two separate disconnect switches or circuit breakers with operators are included with all combination devices. Unless Form Y68 is specified, an alternation circuit (a Class 8501 Type XO40 relay) is included, which alternately operates first one motor and then the other on each successive closing of a pilot device. Both motors will be energized should a second pilot device close. All devices incorporate a terminal block to simplify wiring of pilot devices A and B. Typical applications include pump motors where a second pump is required for peak demand periods yet alternation is desirable to equalize pump wear.
3-Pole Polyphase—600 Vac Maximum (50–60 Hz)
Non-Combination Type—Without Disconnect—With
Electric Alternation
(replace ●●●
with the voltage code)
(Devices require 6 thermal
units. See Thermal Unit
Selection.)
NEMA |
Maximum Rating |
NEMA 1 |
NEMA 4/4X |
NEMA 12 |
Open Type |
|
---|---|---|---|---|---|---|
Voltage |
Hp |
Type [2] |
Type [2] |
Type [2] |
Type [2] |
|
0 |
200–230 |
3 |
NBG10●●● |
NBW10●●● |
NBA10●●● |
NBO10●●● |
1 |
200–230 |
7.5 |
NCG20●●● |
NCW20●●● |
NCA20●●● |
NCO20●●● |
2 |
200 |
10 |
NDG30●●● |
NDW30●●● |
NDA30●●● |
NDO30●●● |
3 |
200 |
25 |
NEG40●●● |
NEW40●●● |
NEA40●●● |
NEO40●●● |
4 |
200 |
40 |
NFG50●●● |
NFW50●●● |
NFA50●●● |
NFO50●●● |
3-Pole Polyphase—600 Vac Maximum (50–60 Hz) Combination Thermal Magnetic Circuit Breaker Type—With Electric Alternation (replace ●●● with the voltage code) (Devices require 6 thermal units. See Thermal Unit Selection.)
Motor |
Max. Hp |
Coil |
NEMA |
Circuit Breaker |
NEMA 1 |
NEMA 4/4X |
NEMA 12 |
|
---|---|---|---|---|---|---|---|---|
Frame |
Ampere |
Type [2] |
Type [2] |
Type [2] |
||||
200 |
2 |
208–60 |
0 |
HLL36015 |
15 |
CBG06 ●●● CBG08●●● |
CBW06 ●●● CBW08●●● |
CBA06 ●●● CBA08●●● |
5 |
1 |
HLL36035 |
35 |
CCG12●●● CCG15●●● |
CCW12●●● CCW15●●● |
CCA12●●● CCA15●●● |
||
10 |
2 |
HLL36060 |
60 |
CDG22●●● |
CDW22●●● |
CDA22●●● |
||
15 |
3 |
HLL36100 |
100 |
CEG32●●● CEG36●●● CEG38●●● |
CEW32●●● CEW36●●● CEW38●●● |
CEA32●●● CEA36●●● CEA38●●● |
||
30 40 |
4 |
JLL36200 |
200 250 |
CFG41●●● CFG44●●● |
CFW41●●● CFW44●●● |
CFA41●●● CFA44●●● |
||
230 |
2 |
240–60 |
0 |
HLL36015 |
15 |
CBG06●●● CBG08●●● |
CBW06●●● CBW08●●● |
CBA06●●● CBA08●●● |
5 |
1 |
HLL36035 |
35 |
CCG14●●● CCG16●●● |
CCW14●●● CCW16●●● |
CCA14●●● CCA16●●● |
||
10 |
2 |
HLL36060 |
60 |
CDG22●●● CDG24●●● |
CDW22●●● CDW24●●● |
CDA22●●● CDA24●●● |
||
25 |
3 |
HLL36150 |
150 |
CEG38●●● |
CEW38●●● |
CEA38●●● |
||
40 |
4 |
JLL36225 |
225 |
CFG43●●● CFG44●●● |
CFW43●●● CFW44●●● |
CFA43●●● CFA44●●● |
||
460 |
5 |
480–60 |
0 |
HLL36015 |
15 |
CBG10●●● |
CBW10●●● |
CBA10●●● |
7.5 |
1 |
HLL36025 |
25 |
CCG18●●● CCG20●●● |
CCW18●●● CCW20●●● |
CCA18●●● CCA20●●● |
||
15 |
2 |
HLL36045 |
45 |
CDG26●●● CDG28●●● CDG30●●● |
CDW26●●● CDW28●●● CDW30●●● |
CDA26●●● CDA28●●● CDA30●●● |
||
30 |
3 |
HLL36080 |
80 |
CEG39●●● CEG40●●● |
CEW39●●● CEW40●●● |
CEA39●●● CEA40●●● |
||
75 |
4 |
JLL36200 |
200 |
CFG45●●● CFG47●●● |
CFW45●●● CFW47●●● |
CFA45●●● CFA47●●● |
note
For voltage codes used with control transformers, see Full Voltage Contactors and Starters.
For How to Order Information, see Catalog Interpretation, Type S Starters.
3-Pole Polyphase—600 Vac Maximum (50–60 Hz) Combination
Disconnect Switch Type—With Electric Alternation
(Devices require 6 thermal units. See Thermal Unit
Selection.)
Motor |
Max. |
Coil |
NEMA |
Fuse |
NEMA 1 |
NEMA 4/4X |
NEMA 12 |
---|---|---|---|---|---|---|---|
Type [2] |
Type [2] |
Type [2] |
|||||
200 |
3 |
208-60 |
0 |
None |
UBG10●●● DBG08●●● |
UBW10●●● DBW08●●● |
UBA10●●● DBA08●●● |
7.5 |
1 |
None |
UCG20●●● DCG18●●● |
UCW20●●● DCW18●●● |
UCA20●●● DCA18●●● |
||
10 |
2 |
None |
UDG30●●● DDG28●●● |
UDW30●●● DDW28●●● |
UDA30●●● DDA28●●● |
||
230 |
3 |
240-60 |
0 |
None |
UBG10●●● DBG08●●● |
UBW10●●● DBW08●●● |
UBA10●●● DBA08●●● |
7.5 |
1 |
None |
UCG20●●● DCG18●●● |
UCW20●●● DCW18●●● |
UCA20●●● DCA18●●● |
||
15 |
2 |
None |
UDG30●●● DDG28●●● |
UDW30●●● DDW28●●● |
UDA30●●● DDA28●●● |
||
460 |
5 |
480-60 |
0 |
None |
UBG10●●● DBG10●●● |
UBW10●●● DBW10●●● |
UBA10●●● DBA10●●● |
10 |
1 |
None |
UCG20●●● DCG20●●● |
UCW20●●● DCW20●●● |
UCA20●●● DCA20●●● |
||
25 |
2 |
None |
UDG30●●● DDG30●●● |
UDW30●●● DDW30●●● |
UDA30●●● DDA30●●● |
||
50 |
3 |
None |
UEG40●●● DEG40●●● |
UEW40●●● DEW40●●● |
UEA40●●● DEA40●●● |
Factory Modifications (Forms)
Factory Modifications (Forms)
Description [4] |
Enclosure |
Form |
NEMA Size |
|||
---|---|---|---|---|---|---|
0–1 |
2 |
3 |
4 |
|||
Pilot Devices in Cover[5] Start-Stop push buttons—one provided for each motor. |
1, 4, 12 |
A |
X |
X |
X |
X |
Hand-Off-Auto selector switch—one provided for each motor. |
1, 4,12 |
C |
X |
X |
X |
X |
No. 1 Lead—No. 2 Lead selector
switch for manual selection of lead pump. Red On pilot light—one provided for each motor. |
Any |
C13 |
X X |
X X |
X X |
X X |
Push-to-test, red On pilot light—one provided for each motor. Non-standard markings for pilot devices. Test push button for each starter. |
1, 4, 12 |
P21 |
X X X |
X X X |
X X X |
X X X |
Control Circuit Modifications Fused control circuit without transformer One fuse Two fuses Fused control circuit transformer,
two fuses in primary, with 600, 480, 240 or 208 V primary |
Any |
F4T |
X X |
X X |
X X |
X X |
Fused control circuit transformer,
two fuses in primary, one fuse in secondary— 100 VA additional capacity 200 VA additional capacity |
Any |
FF4T |
X X X |
X X X |
X X X[6] |
X X[6] X[6] |
Extra capacity control circuit transformer—two fuses in primary—one provided for each starter (see Capacity) 100 VA additional capacity 200 VA additional capacity Elapsed time meter for each starter |
|
|
X X |
X X |
X X |
—[7] X |
Pressure switch for each starter (Square D pressure switch 9012GAW25) Addition of 2 relays to modify controller for operation with single pole pilot devices Addition of 3 relays to modify controller for operation with single pole mercury float switches |
Any |
D |
X X X |
X X X |
X X X |
X X X |
Control circuit wired for separate 120 V source |
Any |
S |
X |
X |
X |
X |
Addition of 1 N.O. unwired interlock
per starter for use by customer Addition of 1 N.C. unwired interlock per starter for customer use |
Any |
X10 |
X X |
X X |
X X |
X X |
Modified wiring for use with double pole mercury float switches Deduct for omission of electrical alternating circuit Additional Control circuit
terminals—per wired terminal Unwired |
Any |
Y24 G50[8] |
X X X X |
X X X X |
X X X X |
X X X X |
Capacity
NEMA |
Standard Capacity |
100 VA Additional
Capacity |
200 VA Additional
Capacity |
---|---|---|---|
Class 9070 Type |
Class 9070 Type |
Class 9070 Type |
|
0, 1 |
TF100 |
TF200 |
TF300 |
2 |
TF100 |
TF200 |
TF300 |
3 |
TF150 |
TF300 |
TF500 |
4 |
TF300 |
TF500 |
TF500 |
For How to Order Information, see Catalog Interpretation, Type S Starters.
Approximate Dimensions (in.)
note
NEMA 1 Enclosure—Non-Combination (Figure 1)
Starter Size |
A |
B |
C |
D |
E |
F |
G |
H |
---|---|---|---|---|---|---|---|---|
0, 1, or 2 |
20.5 |
24.13 |
8.69 |
17.88 |
21.5 |
1.31 |
1.31 |
0.31 Dia. |
3 or 4 |
22.13 |
34 |
9.75 |
16 |
35.5 |
3.06 |
0.75 |
0.44 Dia. |
NEMA 1 Enclosure—Combination (Figure 2)
Starter Size |
A |
B |
C |
D |
E |
F |
G |
H |
J |
K |
---|---|---|---|---|---|---|---|---|---|---|
0, 1, or 2 |
20.38 |
35 |
9.63 |
17 |
32.5 |
3.31 |
1.25 |
1.25 |
1.25 |
0.44 Dia. |
3 or
4 |
32 |
44 |
10.75 |
24 |
46 |
4.88 |
1 |
2.5 |
2.5 |
0.56 Dia. |
NEMA 4 Enclosure—Non-Combination (Figure 3)
Starter Size |
A |
B |
C |
D |
E |
F |
G |
H |
J |
---|---|---|---|---|---|---|---|---|---|
0, 1, or 2 |
20.5 |
24 |
8 |
25 |
15.38 |
26 |
2.56 |
0.5 |
0.31 |
3 or 4 |
22 |
34 |
9.13 |
35 |
17 |
36 |
2.5 |
0.5 |
0.56 |
NEMA 4 Enclosure—Combination (Figure 4)
Starter Size |
A |
B |
C |
D |
E |
F |
G |
H |
J |
K |
---|---|---|---|---|---|---|---|---|---|---|
0, 1, or 2 |
20.5 |
35 |
9.56 |
36 |
15.38 |
37 |
2.56 |
0.5 |
0.31 |
3.31 |
3 or
4 |
32 |
44 |
10.69 |
46 |
26 |
47 |
3 |
0.5 |
0.56 |
4.88 |
NEMA 12/3R Enclosure—Non-Combination (Figure 3)
Starter Size |
A |
B |
C |
D |
E |
F |
G |
H |
J |
---|---|---|---|---|---|---|---|---|---|
0, 1, or 2 |
20.5 |
24.25 |
8 |
25.5 |
14.38 |
26.5 |
3.06 |
0.5 |
0.44 |
3 or 4 |
22 |
34 |
9.13 |
35.5 |
16 |
36.5 |
3 |
0.5 |
0.44 |
NEMA 12/3R Enclosure—Combination (Figure 4)
Starter Size |
A |
B |
C |
D |
E |
F |
G |
H |
J |
K |
---|---|---|---|---|---|---|---|---|---|---|
0, 1, or 2 |
20.5 |
35 |
9.56 |
36.5 |
14.38 |
37.5 |
3 |
0.5 |
0.44 |
3.31 |
3 or
4 |
32.25 |
44.25 |
10.69 |
46 |
24 |
47 |
4.13 |
0.5 |
0.56 |
4.88 |
Coil Voltage Codes
Voltage |
Code |
|
---|---|---|
60 Hz |
50 Hz |
|
24 [9] 120 [10] 208 240 480 600 Specify |
— 110 — 220 380 440 550 Specify |
V01 V02 V08 V03 V05 V06 V07 V99 |
note
Illustrations may not represent the actual enclosure; they are intended for dimensional information only. Dimensions are in inches.