Types DPS and H through M
Class 8911 / Refer to Catalog 8910CT9301
Types DPS and H through M
Class 8911 definite purpose starters are inexpensive starters for applications with relatively low duty cycles. Typical applications include air compressors, agricultural equipment, pumps, and HVAC equipment. Definite purpose starters offer:
-
Low cost
-
Small size
-
Melting alloy overload block
-
Trip-free reset mechanism
-
Open type or enclosed
-
500,000 mechanical operations
2- and 3-Pole Starters—600 Vac Maximum
|
No. of |
Full Load |
Horsepower Ratings |
Open Type |
NEMA 1 |
No. of |
|||
|---|---|---|---|---|---|---|---|---|
|
115 V 1Ø |
230 V 1Ø |
230 V 3Ø |
460/575 V |
|||||
|
2-Pole |
30 |
2 |
5 |
— — — |
— — — |
DPSO32●●● DPSO42●●● DPSO52●●● |
DPSG32●●● DPSG42●●● DPSG52●●● |
1 |
|
3-Pole |
30 |
2 |
5 |
10 10 15 |
15/20 20/25 30 |
DPSO33●●● DPSO43●●● DPSO53●●● |
DPSG33●●● DPSG43●●● DPSG53●●● |
3 |
Replacement Magnet Coil for Class 8911 Type DPS
|
|||||||||||||||||
Coil Voltage Codes
|
|||||||||||||||||
|
Type DPSO—2 and 3-Pole and DSO 30–50 Full Load Amperes |
Type DPSG—2 and 3-Pole 30–40 Full Load Amperes |
Ratings—Overload Contacts and Auxiliary Contacts
|
Device |
Volts |
Pilot Duty –
AC Only |
Continuous |
|
|---|---|---|---|---|
|
Make |
Carry and Break |
|||
|
9998 SO1 |
120 or Less |
30 A |
3 A |
5 A |
|
120–600 |
3600 VA |
360 VA |
5 A |
|
How to Order
|
To Order Specify: |
Catalog Number |
|||
|---|---|---|---|---|
|
Class |
Typse |
Coil Voltage Code |
Form(s) |
|
8911 |
DPSG33 |
V02 |
||