Reversing
Class 8738 / Refer to Catalog 8538CT9701
Class 8738 Fusible Disconnect Switch Type
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
Class 8738 and 8739 Type S reversing combination starters combine the requirements of motor overload and short circuit protection into one convenient package. Type S reversing combination starters are manufactured in accordance with NEMA standards, and are UL Listed (although some Form numbers may not be listed—contact your nearest Square D™/Schneider Electric sales office for further information). Class 8738 and 8739 reversing combination starters are designed to operate at 600 Vac, 50–60 Hz, and are available with one of four types of overload relays. See Introduction for more information. For Class J fuses, use Form Y1072 (no charge).
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic™ SSOLR protection), see Solid-State Overload Relay Forms
Class 8738 Full-Voltage Type, Fusible (With Class H Fuse Clips)
Reversing with Motor Logic™ SSOLR
(replace
●●● with the voltage code)[1]
Ratings |
NEMA 1 |
NEMA 4X |
NEMA 4X Watertight, Dusttight, Corrosion Resistant Polyester Enclosure |
NEMA 12/3R[2] |
||||
---|---|---|---|---|---|---|---|---|
Motor Voltage (Starter Voltage) |
Max. Hp Polyphase |
NEMA Size |
Fuse Clip Size (A) |
With |
Without |
|||
Type [3] |
Type [3] |
Type [3] |
Type [3] |
Type [3] |
||||
200 |
3 |
0 |
30 |
SBG12●●●H30 [4] |
SBW12●●●H30 [4] |
SBW22●●●H30 [4] |
SBA22●●●H30 [4] |
SBA12●●●H30 [4] |
5 |
1 |
30 |
SCG12●●●H30 [4] |
SCW12●●●H30 [4] |
SCW22●●●H30 [4] |
SCA22●●●H30 [4] |
SCA12●●●H30 [4] |
|
7.5 |
60 |
SCG13●●●H30 [4] |
SCW13●●●H30 [4] |
SCW23●●●H30 [4] |
SCA23●●●H30 [4] |
SCA13●●●H30 [4] |
||
10 |
2 |
60 |
SDG12●●●H30 [4] |
SDW12●●●H30 [4] |
SDW22●●●H30 [4] |
SDA22●●●H30 [4] |
SDA12●●●H30 [4] |
|
20 |
3 |
100 |
SEG15●●●H30 |
SEW15●●●H30 |
— |
SEA25●●●H30 |
SEA15●●●H30 |
|
40 |
4 |
200 |
SFG15●●●H30 |
SFW15●●●H30 |
— |
SFA25●●●H30 |
SFA15●●●H30 |
|
75 |
5 |
400 |
SGG15●●●H30 |
SGW15●●●H30 |
— |
SGA25●●●H30 |
SGA15●●●H30 |
|
230 |
3 |
0 |
30 |
SBG12●●●H30 [4] |
SBW12●●●H30 [4] |
SBW22●●●H30 [4] |
SBA22●●●H30 [4] |
SBA12●●●H30 [4] |
5 |
1 |
30 |
SCG12●●●H30 [4] |
SCW12●●●H30 [4] |
SCW22●●●H30 [4] |
SCA22●●●H30 [4] |
SCA12●●●H30 [4] |
|
7.5 |
60 |
SCG13●●●H30 [4] |
SCW13●●●H30 [4] |
SCW23●●●H30 [4] |
SCA23●●●H30 [4] |
SCA13●●●H30 [4] |
||
15 |
2 |
60 |
SDG12●●●H30 [4] |
SDW12●●●H30 [4] |
SDW22●●●H30 [4] |
SDA22●●●H30 [4] |
SDA12●●●H30 [4] |
|
25 |
3 |
100 |
SEG15●●●H30 |
SEW15●●●H30 |
— |
SEA25●●●H30 |
SEA15●●●H30 |
|
50 |
4 |
200 |
SFG15●●●H30 |
SFW15●●●H30 |
— |
SFA25●●●H30 |
SFA15●●●H30 |
|
100 |
5 |
400 |
SGG15●●●H30 |
SGW15●●●H30 |
— |
SGA25●●●H30 |
SGA1●●●H30 |
|
460 |
5 |
0 |
30 |
SBG13●●●H30 [4] |
SBW13●●●H30 [4] |
SBW23●●●H30 [4] |
SBA23●●●H30 [4] |
SBA13●●●H30 [4] |
10 |
1 |
30 |
SCG14●●●H30 [4] |
SCW14●●●H30 [4] |
SCW24●●●H30 [4] |
SCA24●●●H30 [4] |
SCA14●●●H30 [4] |
|
15 |
2 |
30 |
SDG16●●●H301 |
SDW16●●●H301 |
SDW26●●●H301 |
SDA26●●●H301 |
SDA16●●●H301 |
|
25 |
60 |
SDG14●●●H30 [4] |
SDW14●●●H30 [4] |
SDW24●●●H30 [4] |
SDA24●●●H30 [4] |
SDA14●●●H30 [4] |
||
50 |
3 |
100 |
SEG13●●●H30 |
SEW13●●●H30 |
— |
SEA23●●●H30 |
SEA13●●●H30 |
|
100 |
4 |
200 |
SFG13●●●H30 |
SFW13●●●H30 |
— |
SFA23●●●H30 |
SFA13●●●H30 |
|
200 |
5 |
400 |
SGG13●●●H30 |
SGW13●●●H30 |
— |
SGA23●●●H30 |
SGA13●●●H30 |
|
575 |
5 |
0 |
30 |
SBG13●●●H30 |
SBW13●●●H30 |
SBW23●●●H30 |
SBA23●●●H30 |
SBA13●●●H30 |
10 |
1 |
30 |
SCG14●●●H301 |
SCW14●●●H301 |
SCW24●●●H301 |
SCA24●●●H301 |
SCA14●●●H301 |
|
15 |
2 |
30 |
SDG16●●●H30 |
SDW16●●●H30 |
SDW26●●●H30 |
SDA26●●●H30 |
SDA16●●●H30 |
|
25 |
60 |
SDG14●●●H30 |
SDW14●●●H30 |
SDW24●●●H30 |
SDA24●●●H30 |
SDA14●●●H30 |
||
50 |
3 |
100 |
SEG13●●●H30 |
SEW13●●●H30 |
— |
SEA23●●●H30 |
SEA13●●●H30 |
|
100 |
4 |
200 |
SFG13●●●H30 |
SFW13●●●H30 |
— |
SFA23●●●H30 |
SFA13●●●H30 |
|
200 |
5 |
400 |
SGG13●●●H30 |
SGW13●●●H30 |
— |
SGA23●●●H30 |
SGA13●●●H30 |
Coil Voltage Codes
Voltage |
Code |
|
---|---|---|
60 Hz |
50 Hz |
|
— |
V01 |
note
For voltage codes used with control transformers, see Full Voltage Contactors and Starters.
Form S (separate control) is used when a separate source of power
is available for the control (coil) voltage. Form S is available at
no charge.
Dimensions: NEMA 1, 12, and 3R
Factory Modifications
(Forms): Full Voltage Starters
Replacement
Parts (Class 9998): Magnetic Coils
Type S Accessories
(Class 9999): Contact Kits
For How to Order Information, see Catalog Interpretation, Type S Starters.
Non-Fusible and Fusible Disconnect Switch Type
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic™ SSOLR protection), see Solid-State Overload Relay Forms
Class 8738 Non-Fusible Disconnect Switch Type—Full-Voltage,
Reversing, with Motor Logic™ SSOLR
(replace
●●● with the voltage code)[1]
Ratings |
NEMA 1 |
NEMA 4X |
NEMA 4X |
NEMA 12/3R[2] |
||||
---|---|---|---|---|---|---|---|---|
Motor Voltage (Starter Voltage) |
Max. Hp Polyphase |
NEMA Size |
Fuse Clip Size (A) |
With |
Without |
|||
Type [7] |
Type [7] |
Type [7] |
Type [7] |
Type [7] |
||||
200 |
3 |
0 |
None |
SBG11●●●H30 [4] |
SBW11●●●H30 [4] |
SBW21●●●H30 [4] |
SBA21●●●H30 [4] |
SBA11●●●H30 [4] |
7-1/2 |
1 |
None |
SCG11●●●H30 [4] |
SCW11●●●H30 [4] |
SCW21●●●H30 [4] |
SCA21●●●H30 [4] |
SCA11●●●H30 [4] |
|
10 |
2 |
None |
SDG11●●●H30 [4] |
SDW11●●●H30 [4] |
SDW21●●●H30 [4] |
SDA21●●●H30 [4] |
SDA11●●●H30 [4] |
|
25 |
3 |
None |
SEG11●●●H30 |
SEW11●●●H30 |
— |
SEA21●●●H30 |
SEA11●●●H30 |
|
40 |
4 |
None |
SFG11●●●H30 |
SFW11●●●H30 |
— |
SFA21●●●H30 |
SFA11●●●H30 |
|
75 |
5 |
None |
SGG11●●●H30 |
SGW11●●●H30 |
— |
SGA21●●●H30 |
SGA11●●●H30 |
|
230 |
3 |
0 |
None |
SBG11●●●H30 [4] |
SBW11●●●H30 [4] |
SBW21●●●H30 [4] |
SBA21●●●H30 [4] |
SBA11●●●H30 [4] |
7-1/2 |
1 |
None |
SCG11●●●H30 [4] |
SCW11●●●H30 [4] |
SCW21●●●H30 [4] |
SCA21●●●H30 [4] |
SCA11●●●H30 [4] |
|
15 |
2 |
None |
SDG11●●●H30 [4] |
SDW11●●●H30 [4] |
SDW21●●●H30 [4] |
SDA21●●●H30 [4] |
SDA11●●●H30 [4] |
|
30 |
3 |
None |
SEG11●●●H30 |
SEW11●●●H30 |
— |
SEA21●●●H30 |
SEA11●●●H30 |
|
50 |
4 |
None |
SFG11●●●H30 |
SFW11●●●H30 |
— |
SFA21●●●H30 |
SFA11●●●H30 |
|
100 |
5 |
None |
SGG11●●●H30 |
SGW11●●●H30 |
— |
SGA21●●●H30 |
SGA11●●●H30 |
|
460 |
5 |
0 |
None |
SBG11●●●H30 [4] |
SBW11●●●H30 [4] |
SBW21●●●H30 [4] |
SBA21●●●H30 [4] |
SBA11●●●H30 [4] |
10 |
1 |
None |
SCG11●●●H30 [4] |
SCW11●●●H30 [4] |
SCW21●●●H30 [4] |
SCA21●●●H30 [4] |
SCA11●●●H30 [4] |
|
25 |
2 |
None |
SDG11●●●H30 [4] |
SDW11●●●H30 [4] |
SDW21●●●H30 [4] |
SDA21●●●H30 [4] |
SDA11●●●H30 [4] |
|
50 |
3 |
None |
SEG11●●●H30 |
SEW11●●●H30 |
— |
SEA21●●●H30 |
SEA11●●●H30 |
|
100 |
4 |
None |
SFG11●●●H30 |
SFW11●●●H30 |
— |
SFA21●●●H30 |
SFA11●●●H30 |
|
200 |
5 |
None |
SGG11●●●H30 |
SGW11●●●H30 |
— |
SGA21●●●H30 |
SGA11●●●H30 |
|
575 |
5 |
0 |
None |
SBG11●●●H30 [4] |
SBW11●●●H30 [4] |
SBW21●●●H30 [4] |
SBA21●●●H30 [4] |
SBA11●●●H30 [4] |
10 |
1 |
None |
SCG11●●●H30 [4] |
SCW11●●●H30 [4] |
SCW21●●●H30 [4] |
SCA21●●●H30 [4] |
SCA11●●●H30 [4] |
|
25 |
2 |
None |
SDG11●●●H30 [4] |
SDW11●●●H30 [4] |
SDW21●●●H30 [4] |
SDA21●●●H30 [4] |
SDA11●●●H30 [4] |
|
50 |
3 |
None |
SEG11●●●H30 |
SEW11●●●H30 |
— |
SEA21●●●H30 |
SEA11●●●H30 |
|
100 |
4 |
None |
SFG11●●●H30 |
SFW11●●●H30 |
— |
SFA21●●●H30 |
SFA11●●●H30 |
|
200 |
5 |
None |
SGG11●●●H30 |
SGW11●●●H30 |
— |
SGA21●●●H30 |
SGA11●●●H30 |
Class 8738 Fusible Disconnect Switch Type with Class R Fuse
Clips—100,000 AIC Rating
(replace ●●●
with the voltage code)[1]
Ratings |
NEMA 1 |
NEMA 4 & 4X |
NEMA 4X |
NEMA 12/3R[2] |
||||
---|---|---|---|---|---|---|---|---|
Motor Voltage (Starter Voltage) |
Max. Hp Polyphase |
NEMA |
Fuse Clip Size (A) |
With |
Without |
|||
Type [7] |
Type [7] |
Type [7] |
Type [7] |
Type [7] |
||||
200 |
3 |
0 |
30 |
SBG32●●●H30 [4] |
SBW32●●●H30 [4] |
SBW42●●●H30 [4] |
SBA42●●●H30 [4] |
SBA32●●●H30 [4] |
5 |
1 |
30 |
SCG32●●●H30 [4] |
SCW32●●●H30 [4] |
SCW42●●●H30 [4] |
SCA42●●●H30 [4] |
SCA32●●●H30 [4] |
|
7-1/2 |
60 |
SCG33●●●H30 [4] |
SCW33●●●H30 [4] |
SCW43●●●H30 [4] |
SCA43●●●H30 [4] |
SCA33●●●H30 [4] |
||
10 |
2 |
60 |
SDG32●●●H30 [4] |
SDW32●●●H30 [4] |
SDW42●●●H30 [4] |
SDA42●●●H30 [4] |
SDA32●●●H30 [4] |
|
20 |
3 |
100 |
SEG35●●●H30 |
SEW35●●●H30 |
— |
SEA45●●●H30 |
SEA35●●●H30 |
|
40 |
4 |
200 |
SFG35●●●H30 |
SFW35●●●H30 |
— |
SFA45●●●H30 |
SFA35●●●H30 |
|
75 |
5 |
400 |
SGG35●●●H30 |
SGW35●●●H30 |
— |
SGA45●●●H30 |
SGA35●●●H30 |
|
230 |
3 |
0 |
30 |
SBG32●●●H30 [4] |
SBW32●●●H30 [4] |
SBW42●●●H30 [4] |
SBA42●●●H30 [4] |
SBA32●●●H30 [4] |
5 |
1 |
30 |
SCG32●●●H30 [4] |
SCW32●●●H30 [4] |
SCW42●●●H30 [4] |
SCA42●●●H30 [4] |
SCA32●●●H30 [4] |
|
7-1/2 |
60 |
SCG33●●●H30 [4] |
SCW33●●●H30 [4] |
SCW43●●●H30 [4] |
SCA43●●●H30 [4] |
SCA33●●●H30 [4] |
||
15 |
2 |
60 |
SDG32●●●H30 [4] |
SDW32●●●H30 [4] |
SDW42●●●H30 [4] |
SDA42●●●H30 [4] |
SDA32●●●H30 [4] |
|
25 |
3 |
100 |
SEG35●●●H30 |
SEW35●●●H30 |
— |
SEA45●●●H30 |
SEA3●●●H30 |
|
50 |
4 |
200 |
SFG35●●●H30 |
SFW35●●●H30 |
— |
SFA45●●●H30 |
SFA35●●●H30 |
|
100 |
5 |
400 |
SGG35●●●H30 |
SGW35●●●H30 |
— |
SGA45●●●H30 |
SGA35●●●H30 |
|
460 |
5 |
0 |
30 |
SBG33●●●H30 [4] |
SBW33●●●H30 [4] |
SBW43●●●H30 [4] |
SBA43●●●H30 [4] |
SBA33●●●H30 [4] |
10 |
1 |
30 |
SCG34●●●H30 [4] |
SCW34●●●H30 [4] |
SCW44●●●H30 [4] |
SCA44●●●H30 [4] |
SCA34●●●H30 [4] |
|
15 |
2 |
30 |
SDG36●●●H301 |
SDW36●●●H301 |
SDW46●●●H301 |
SDA46●●●H301 |
SDA36●●●H301 |
|
25 |
60 |
SDG34●●●H30 [4] |
SDW34●●●H30 [4] |
SDW44●●●H30 [4] |
SDA44●●●H30 [4] |
SDA34●●●H30 [4] |
||
50 |
3 |
100 |
SEG33●●●H30 |
SEW33●●●H30 |
— |
SEA43●●●H30 |
SEA33●●●H30 |
|
100 |
4 |
200 |
SFG33●●●H30 |
SFW33●●●H30 |
— |
SFA43●●●H30 |
SFA33●●●H30 |
|
200 |
5 |
400 |
SGG33●●●H30 |
SGW33●●●H30 |
— |
SGA43●●●H30 |
SGA33●●●H30 |
|
575 |
5 |
0 |
30 |
SBG33●●●H30 [4] |
SBW33●●●H30 [4] |
SBW43●●●H30 [4] |
SBA43●●●H30 [4] |
SBA33●●●H30 [4] |
10 |
1 |
30 |
SCG34●●●H30 [4] |
SCW34●●●H30 [4] |
SCW44●●●H30 [4] |
SCA44●●●H30 [4] |
SCA34●●●H30 [4] |
|
15 |
2 |
30 |
SDG36●●●H301 |
SDW36●●●H301 |
SDW46●●●H301 |
SDA46●●●H301 |
SDA36●●●H301 |
|
25 |
60 |
SDG34●●●H30 [4] |
SDW34●●●H30 [4] |
SDW44●●●H30 [4] |
SDA44●●●H30 [4] |
SDA34●●●H30 [4] |
||
50 |
3 |
100 |
SEG33●●●H30 |
SEW33●●●H30 |
— |
SEA43●●●H30 |
SEA33●●●H30 |
|
100 |
4 |
200 |
SFG33●●●H30 |
SFW33●●●H30 |
— |
SFA43●●●H30 |
SFA33●●●H30 |
|
200 |
5 |
400 |
SGG33●●●H30 |
SGW33●●●H30 |
— |
SGA43●●●H30 |
SGA33●●●H30 |
For How to Order Information, see Catalog Interpretation, Type S Starters.
Class 8739 / Refer to Catalog 8538CT9701
Electronic Motor Circuit Protector (MCP)
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic™ SSOLR protection), see Solid-State Overload Relay Forms
Class 8739 Full-Voltage Type, Reversing with Motor Logic SSOLR (replace ●●● with the voltage code)[1]
Ratings |
NEMA 1 |
NEMA 4X |
NEMA 4X |
NEMA 12/3R[2] |
||||
---|---|---|---|---|---|---|---|---|
Motor Voltage (Starter Voltage) |
NEMA Size |
Hp Range Polyphase |
Circuit Breaker (See Page 7-32 for Breaker Adjustment Range) |
With |
Without External Reset |
|||
Type [7] |
Type [7] |
Type [7] |
Type [7] |
Type [7] |
||||
200 |
0 |
0.25–3 |
HLL36030M71 |
SBG43●●●H30 [4] |
SBW43●●●H30 [4] |
SBW53●●●H30 [4] |
SBA53●●●H30 [4] |
SBA43●●●H30 [4] |
1 |
0.25–5 |
HLL36030M71 |
SCG44●●●H30 [4] |
SCW44●●●H30 [4] |
SCW54●●●H30 [4] |
SCA54●●●H30 [4] |
SCA44●●●H30 [4] |
|
7.5 |
HLL36050M72 |
SCG45●●●H30 [4] |
SCW45●●●H30 [4] |
SCW55●●●H30 [4] |
SCA55●●●H30 [4] |
SCA45●●●H30 [4] |
||
2 |
1.5–5 |
HLL36030M71 |
SDG42●●●H301 |
SDW42●●●H301 |
SDW52●●●H301 |
SDA52●●●H301 |
SDA42●●●H301 |
|
7.5–10 |
HLL36050M72 |
SDG43●●●H30 [4] |
SDW43●●●H30 [4] |
SDW53●●●H30 [4] |
SDA53●●●H30 [4] |
SDA43●●●H30 [4] |
||
3 |
15–25 |
HLL36100M73 |
SEG42●●●H30 |
SEW42●●●H30 |
SEW52●●●H30 |
SEA52●●●H30 |
SEA42●●●H30 |
|
4 |
30–40 |
JJL36250M75 |
SFG44●●●H30 |
SFW44●●●H30 |
SFW54●●●H30 |
SFA54●●●H30 |
SFA44●●●H30 |
|
5 |
50–60 |
JLL36250M75 |
SGG44●●●H30 |
SGW44●●●H30 |
— |
SGA54●●●H30 |
SGA44●●●H30 |
|
75 |
LJL36400M36 |
SGG45●●●H30 |
SGW45●●●H30 |
— |
SGA55●●●H30 |
SGA45●●●H30 |
||
6 |
100 |
LJL36400M36 |
SHG43●●●H30 |
SHW43●●●H30 |
— |
SHA53●●●H30 |
SHA43●●●H30 |
|
125–150 |
LJL36600M42 |
SHG45●●●H30 |
SHW45●●●H30 |
— |
SHA55●●●H30 |
SHA45●●●H30 |
||
230 |
0 |
0.25–3 |
HLL36030M71 |
SBG43●●●H30 [4] |
SBW43●●●H30 [4] |
SBW53●●●H30 [4] |
SBA53●●●H30 [4] |
SBA43●●●H30 [4] |
1 |
0.25–7.5 |
HLL36030M71 |
SCG44●●●H30 [4] |
SCW44●●●H30 [4] |
SCW54●●●H30 [4] |
SCA54●●●H30 [4] |
SCA44●●●H30 [4] |
|
2 |
1.5–7.5 |
HLL36030M71 |
SDG42●●●H301 |
SDW42●●●H301 |
SDW52●●●H301 |
SDA52●●●H301 |
SDA42●●●H301 |
|
10 |
HLL36050M72 |
SDG43●●●H30 [4] |
SDW43●●●H30 [4] |
SDW53●●●H30 [4] |
SDA53●●●H30 [4] |
SDA43●●●H30 [4] |
||
15 |
HLL36100M73 |
SDG44●●●H30 [4] |
SDW44●●●H30 [4] |
SDW54●●●H30 [4] |
SDA54●●●H30 [4] |
SDA44●●●H30 [4] |
||
3 |
15–30 |
HLL36100M73 |
SEG42●●●H30 |
SEW42●●●H30 |
SEW52●●●H30 |
SEA52●●●H30 |
SEA42●●●H30 |
|
4 |
40–50 |
JJL36250M75 |
SFG44●●●H30 |
SFW44●●●H30 |
SFW54●●●H30 |
SFA54●●●H30 |
SFA44●●●H30 |
|
5 |
60 |
JLL36250M75 |
SGG44●●●H30 |
SGW44●●●H30 |
— |
SGA54●●●H30 |
SGA44●●●H30 |
|
75–100 |
LJL36400M36 |
SGG45●●●H30 |
SGW45●●●H30 |
— |
SGA55●●●H30 |
SGA45●●●H30 |
||
6 |
125–150 |
LJL36600M42 |
SHG45●●●H30 |
SHW45●●●H30 |
— |
SHA55●●●H30 |
SHA45●●●H30 |
|
200 |
PLL34080M68 |
SHG46●●●H30 |
SHW46●●●H30 |
— |
SHA56●●●H30 |
SHA46●●●H30 |
||
460 |
0 |
0.25–5 |
HLL36030M71 |
SBG43●●●H30 [4] |
SBW43●●●H30 [4] |
SBW53●●●H30 [4] |
SBA53●●●H30 [4] |
SBA43●●●H30 [4] |
1 |
0.25–10 |
HLL36030M71 |
SCG44●●●H30 [4] |
SCW44●●●H30 [4] |
SCW54●●●H30 [4] |
SCA54●●●H30 [4] |
SCA44●●●H30 [4] |
|
2 |
5–15 |
HLL36030M71 |
SDG42●●●H301 |
SDW42●●●H301 |
SDW52●●●H301 |
SDA52●●●H301 |
SDA42●●●H301 |
|
20–25 |
HLL36050M72 |
SDG43●●●H30 [4] |
SDW43●●●H30 [4] |
SDW53●●●H30 [4] |
SDA53●●●H30 [4] |
SDA43●●●H30 [4] |
||
3 |
20–25 30–50 |
HLL36050M72 |
SEG41●●●H30 SEG42●●●H30 |
SEW41●●●H30 SEW42●●●H30 |
SEW51●●●H30 SEW52●●●H30 |
SEA51●●●H30 SEA52●●●H30 |
SEA41●●●H30 SEA42●●●H30 |
|
4 |
60–100 |
JLL36250M75 |
SFG44●●●H30 |
SFW44●●●H30 |
SFW54●●●H30 |
SFA54●●●H30 |
SFA44●●●H30 |
|
5 |
125 150–200 |
JLL36250M75 LJL36400M36 |
SGG44●●●H30 SGG45●●●H30 |
SGW44●●●H30 SGW45●●●H30 |
— — |
SGA54●●●H30 SGA55●●●H30 |
SGA44●●●H30 SGA45●●●H30 |
|
6 |
250–350 400 |
LJL36600M42 PLL34080M68 |
SHG45●●●H30 SHG46●●●H30 |
SHW45●●●H30 SHW46●●●H30 |
— — |
SHA55●●●H30 SHA56●●●H30 |
SHA45●●●H30 SHA46●●●H30 |
|
575 |
0 |
0.25–5 |
HLL36030M71 |
SBG43●●●H30 [4] |
SBW43●●●H30 [4] |
SBW53●●●H30 [4] |
SBA53●●●H30 [4] |
SBA43●●●H30 [4] |
1 |
0.25–10 |
HLL36030M71 |
SCG44●●●H30 [4] |
SCW44●●●H30 [4] |
SCW54●●●H30 [4] |
SCA54●●●H30 [4] |
SCA44●●●H30 [4] |
|
2 |
5–20 |
HLL36030M71 |
SDG42●●●H301 |
SDW42●●●H301 |
SDW52●●●H301 |
SDA52●●●H301 |
SDA42●●●H301 |
|
25 |
HLL36050M72 |
SDG43●●●H30 [4] |
SDW43●●●H30 [4] |
SDW53●●●H30 [4] |
SDA53●●●H30 [4] |
SDA43●●●H30 [4] |
||
3 |
25–30 40–50 |
HLL36050M72 |
SEG41●●●H30 SEG42●●●H30 |
SEW41●●●H30 SEW42●●●H30 |
SEW51●●●H30 SEW52●●●H30 |
SEA51●●●H30 SEA52●●●H30 |
SEA41●●●H30 SEA42●●●H30 |
|
4 |
60–100 |
JLL36250M75 |
SFG44●●●H30 |
SFW44●●●H30 |
SFW54●●●H30 |
SFA54●●●H30 |
SFA44●●●H30 |
|
5 |
125–150 200 |
JLL36250M75 LJL36400M36 |
SGG44●●●H30 SGG45●●●H30 |
SGW44●●●H30 SGW45●●●H30 |
— — |
SGA54●●●H30 SGA55●●●H30 |
SGA44●●●H30 SGA45●●●H30 |
|
6 |
250 300–400 |
LJL36400M36 LJL36600M42 |
SHG43●●●H30 SHG45●●●H30 |
SHW43●●●H30 SHW45●●●H30 |
— — |
SHA53●●●H30 SHA55●●●H30 |
SHA43●●●H30 SHA45●●●H30 |
Coil Voltage Codes
Voltage |
Code |
|
---|---|---|
60 Hz |
50 Hz |
|
277 |
— — |
V01 V04 |
note
For voltage codes used with control transformers, see Full Voltage Contactors and Starters.
Form S (separate control) is used when a separate source of power
is available for the control (coil) voltage. Form S is available at
no charge.
Dimensions: NEMA 1, 12, and 3R
Factory Modifications
(Forms): Full Voltage Starters
Replacement
Parts (Class 9998): Magnetic Coils
Type S Accessories
(Class 9999): Contact Kits
For How to Order Information, see Catalog Interpretation, Type S Starters.
Thermal Magnetic Circuit Breaker
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic™ SSOLR protection), see Solid-State Overload Relay Forms
Class 8739 Full-Voltage Type, Reversing, 200–240 V, with Motor Logic SSOLR (replace ●●● with the voltage code)[1]
Ratings |
NEMA 1 |
NEMA 4X |
NEMA 4X |
NEMA 12/3R [2] |
|||||
---|---|---|---|---|---|---|---|---|---|
Motor |
Max. |
NEMA |
Circuit Breaker |
Type [3] |
Type [3] |
Type [3] |
With |
Without |
|
Type |
Ampere |
Type [3] |
Type [3] |
||||||
200 |
2 3 |
0 |
HLL36015 HLL36020 |
15 20 |
SBG1●●●H30 [4] SBG3●●●H30 [4] |
SBW1●●●H30 [4] SBW3●●●H30 [4] |
SBW11●●●H30 [4] SBW13●●●H30 [4] |
SBA11●●●H30 [4] SBA13●●●H30 [4] |
SBA1●●●H30 [4] SBA3●●●H30 [4] |
5 7.5 |
1 |
HLL36035 |
35 50 |
SCG5●●●H30 [4] SCG2●●●H30 [4] |
SCW5●●●H30 [4] SCW2●●●H30 [4] |
SCW15●●●H30 [4] SCW12●●●H30 [4] |
SCA15●●●H30 [4] SCA12●●●H30 [4] |
SCA5●●●H30 [4] SCA2●●●H30 [4] |
|
10 |
2 |
HLL36060 |
60 |
SDG1●●●H30 [4] |
SDW1●●●H30 [4] |
SDW11●●●H30 [4] |
SDA11●●●H30 [4] |
SDA1●●●H30 [4] |
|
15 20 25 |
3 |
HLL36100 |
100 125 150 |
SEG3●●●H30 SEG1●●●H30 SEG5●●●H30 |
SEW3●●●H30 SEW1●●●H30 SEW5●●●H30 |
SEW13●●●H30 SEW11●●●H30 SEW15●●●H30 |
SEA13●●●H30 SEA11●●●H30 SEA15●●●H30 |
SEA3●●●H30 SEA1●●●H30 SEA5●●●H30 |
|
30 40 |
4 |
JLL36200 |
200 250 |
SFG3●●●H30 SFG4●●●H30 |
SFW3●●●H30 SFW4●●●H30 |
SFW13●●●H30 SFW14●●●H30 |
SFA13●●●H30 SFA14●●●H30 |
SFA3●●●H30 SFA4●●●H30 |
|
50 60–75 |
5 |
JLL36250 |
250 400 |
SGG6●●●H30 SGG4●●●H30 |
SGW6●●●H30 SGW4●●●H30 |
— — |
SGA16●●●H30 SGA14●●●H30 |
SGA6●●●H30 SGA4●●●H30 |
|
100–125 150 |
6 |
LLL36600U33X |
600 800 |
SHG4●●●H30 SHG5●●●H30 |
SHW4●●●H30 SHW5●●●H30 |
— — |
SHA14●●●H30 SHA15●●●H30 |
SHA4●●●H30 SHA5●●●H30 |
|
230 |
2 3 |
0 |
HLL36015 |
15 20 |
SBG1●●●H30 [4] SBG3●●●H30 [4] |
SBW1●●●H30 [4] SBW3●●●H30 [4] |
SBW11●●●H30 [4] SBW13●●●H30 [4] |
SBA11●●●H30 [4] SBA13●●●H30 [4] |
SBA1●●●H30 [4] SBA3●●●H30 [4] |
5 7.5 |
1 |
HLL36035 |
35 45 |
SCG5●●●H30 [4] SCG6●●●H30 [4] |
SCW5●●●H30 [4] SCW6●●●H30 [4] |
SCW15●●●H30 [4] SCW16●●●H30 [4] |
SCA15●●●H30 [4] SCA16●●●H30 [4] |
SCA5●●●H30 [4] SCA6●●●H30 [4] |
|
10 15 |
2 |
HLL36060 |
60 90 |
SDG1●●●H30 [4] SDG7●●●H30 [4] |
SDW1●●●H30 [4] SDW7●●●H30 [4] |
SDW11●●●H30 [4] SDW17●●●H30 [4] |
SDA11●●●H30 [4] SDA17●●●H30 [4] |
SDA1●●●H30 [4] SDA7●●●H30 [4] |
|
20 25–30 |
3 |
HLL36100 HLL36150 |
100 150 |
SEG3●●●H30 SEG5●●●H30 |
SEW3●●●H30 SEW5●●●H30 |
SEW13●●●H30 SEW15●●●H30 |
SEA13●●●H30 SEA15●●●H30 |
SEA3●●●H30 SEA5●●●H30 |
|
40 50 |
4 |
JLL36225 |
225 250 |
SFG1●●●H30 SFG4●●●H30 |
SFW1●●●H30 SFW4●●●H30 |
SFW11●●●H30 SFW14●●●H30 |
SFA11●●●H30 SFA14●●●H30 |
SFA1●●●H30 SFA4●●●H30 |
|
60 75 100 |
5 |
JLL36250 |
250 400 600 |
SGG6●●●H30 SGG4●●●H30 SGG2●●●H30 |
SGW6●●●H30 SGW4●●●H30 SGW2●●●H30 |
— — — |
SGA16●●●H30 SGA14●●●H30 SGA12●●●H30 |
SGA6●●●H30 SGA4●●●H30 SGA2●●●H30 |
|
125 150–200 |
6 |
LLL36600U33X MJL36800 |
600 800 |
SHG4●●●H30 SHG5●●●H30 |
SHW4●●●H30 SHW5●●●H30 |
— — |
SHA14●●●H30 SHA15●●●H30 |
SHA4●●●H30 SHA5●●●H30 |
Coil Voltage Codes
Voltage |
Code |
|
---|---|---|
60 Hz |
50 Hz |
|
277 |
— — |
V01 V04 |
note
For voltage codes used with control transformers, see Full Voltage Contactors and Starters.
Form S (separate control) is used when a separate source of power
is available for the control (coil) voltage. Form S is available at
no charge.
Dimensions: NEMA 1, 12, and 3R
Factory Modifications
(Forms): Full Voltage Starters
Replacement
Parts (Class 9998): Magnetic Coils
Type S Accessories
(Class 9999): Contact Kits
For How to Order Information, see Catalog Interpretation, Type S Starters.
Thermal Magnetic Circuit Breaker
3-Pole Polyphase—600 Vac Maximum—50–60 Hz
For Form H30• (special lower-FLA factory-assembled starter combinations with Motor Logic SSOLR protection), see Solid-State Overload Relay Forms
Class 8739 Full-Voltage Type, Reversing, 460–600 V, with Motor Logic™ SSOLR (replace ●●● with the voltage code)[1]
Ratings |
NEMA 1 |
NEMA 4X |
NEMA 4X |
NEMA 12/3R[2] |
|||||
---|---|---|---|---|---|---|---|---|---|
Motor Voltage (Starter Voltage) |
Max. Hp Polyphase |
NEMA Size |
Circuit Breaker |
Type [3] |
Type [3] |
Type [3] |
With |
Without |
|
Type |
Ampere Rating |
Type [3] |
Type [3] |
||||||
460 |
5 |
0 |
HLL36015 |
15 |
SBG1●●●H30 [4] |
SBW1●●●H30 [4] |
SBW11●●●H30 [4] |
SBA11●●●H30 [4] |
SBA1●●●H30 [4] |
7-1/2 10 |
1 |
HLL36025 |
25 30 |
SCG3●●●H30 [4] SCG7●●●H30 [4] |
SCW3●●●H30 [4] SCW7●●●H30 [4] |
SCW13●●●H30 [4] SCW17●●●H30 [4] |
SCA13●●●H30 [4] SCA17●●●H30 [4] |
SCA3●●●H30 [4] SCA7●●●H30 [4] |
|
15 20 25 |
2 |
HLL36045 |
45 60 70 |
SDG3●●●H30 [4] SDG1●●●H30 [4] SDG5●●●H30 [4] |
SDW3●●●H30 [4] SDW1●●●H30 [4] SDW5●●●H30 [4] |
SDW13●●●H30 [4] SDW11●●●H30 [4] SDW15●●●H30 [4] |
SDA13●●●H30 [4] SDA11●●●H30 [4] SDA15●●●H30 [4] |
SDA3●●●H30 [4] SDA1●●●H30 [4] SDA5●●●H30 [4] |
|
30 40 50 |
3 |
HLL36080 |
80 100 150 |
SEG6●●●H30 SEG3●●●H30 SEG5●●●H30 |
SEW6●●●H30 SEW3●●●H30 SEW5●●●H30 |
SEW16●●●H30 SEW13●●●H30 SEW15●●●H30 |
SEA16●●●H30 SEA13●●●H30 SEA15●●●H30 |
SEA6●●●H30 SEA3●●●H30 SEA5●●●H30 |
|
60 75 100 |
4 |
JJL36105 |
150 200 250 |
SFG5●●●H30 SFG3●●●H30 SFG4●●●H30 |
SFW5●●●H30 SFW3●●●H30 SFW4●●●H30 |
SFW15●●●H30 SFW13●●●H30 SFW14●●●H30 |
SFA15●●●H30 SFA13●●●H30 SFA14●●●H30 |
SFA5●●●H30 SFA3●●●H30 SFA4●●●H30 |
|
125–150 200 |
5 |
LLL36400U33X |
400 600 |
SGG4●●●H30 SGG2●●●H30 |
SGW4●●●H30 SGW2●●●H30 |
— — |
SGA14●●●H30 SGA12●●●H30 |
SGA4●●●H30 SGA2●●●H30 |
|
250 300–400 |
6 |
LLL36600U33X |
600 800 |
SHG4●●●H30 SHG5●●●H30 |
SHW4●●●H30 SHW5●●●H30 |
— — |
SHA14●●●H30 SHA15●●●H30 |
SHA4●●●H30 SHA5●●●H30 |
|
575 |
5 |
0 |
HLL36015 |
15 |
SBG1●●●H30 |
SBW1●●●H30 |
SBW11●●●H30 |
SBA11●●●H30 |
SBA1●●●H30 |
7-1/2 10 |
1 |
HLL36020 |
20 25 |
SCG8●●●H30 SCG3●●●H30 |
SCW8●●●H30 SCW3●●●H30 |
SCW18●●●H30 SCW13●●●H30 |
SCA18●●●H30 SCA13●●●H30 |
SCA8●●●H30 SCA3●●●H30 |
|
15 20 25 |
2 |
HLL36035 |
35 45 60 |
SDG8●●●H301 SDG3●●●H30 SDG1●●●H30 |
SDW8●●●H301 SDW3●●●H30 SDW1●●●H30 |
SDW18●●●H301 SDW13●●●H30 SDW11●●●H30 |
SDA18●●●H301 SDA13●●●H30 SDA12●●●H30 |
SDA8●●●H301 SDA3●●●H30 SDA1●●●H30 |
|
30 40 50 |
3 |
HLL36070 |
70 90 100 |
SEG4●●●H30 SEG6●●●H30 SEG3●●●H30 |
SEW4●●●H30 SEW6●●●H30 SEW3●●●H30 |
SEW14●●●H30 SEW16●●●H30 SEW13●●●H30 |
SEA14●●●H30 SEA16●●●H30 SEA13●●●H30 |
SEA4●●●H30 SEA6●●●H30 SEA3●●●H30 |
|
60–75 100 |
4 |
JLL36150 |
150 250 |
SFG5●●●H30 SFG4●●●H30 |
SFW5●●●H30 SFW4●●●H30 |
SFW15●●●H30 SFW14●●●H30 |
SFA15●●●H30 SFA14●●●H30 |
SFA5●●●H30 SFA4●●●H30 |
|
125–150 200 |
5 |
JLL36250 |
250 400 |
SGG6●●●H30 SGG4●●●H30 |
SGW6●●●H30 SGW4●●●H30 |
— — |
SGA16●●●H30 SGA14●●●H30 |
SGA6●●●H30 SGA4●●●H30 |
|
250–350 400 |
6 |
LLL36600U33X MJL36800 |
600 800 |
SHG4●●●H30 SHG5●●●H30 |
SHW4●●●H30 SHW5●●●H30 |
— — |
SHA14●●●H30 SHA15●●●H30 |
SHA4●●●H30 SHA5●●●H30 |
Coil Voltage Codes
Voltage |
Code |
|
---|---|---|
60 Hz |
50 Hz |
|
— |
V01 |
note
Form S (separate control) is used when a separate source of power is available for the control (coil) voltage. Form S is available at no charge.
For How to Order Information, see Catalog Interpretation, Type S Starters.
Class 8738 UL Listed Short Circuit Ratings
NEMA |
Fuse Clip |
Enclosure [15] |
Ampere Interrupting |
---|---|---|---|
0–3 |
Standard |
Standard |
5,000 |
0–3 |
Class R |
Standard |
100,000 |
4–5 |
Standard |
Standard |
10,000 |
4–5 |
Class R |
Standard |
100,000 |
Class 8739 UL Listed Short Circuit Ratings
Motor Circuit Protector Type |
|||
---|---|---|---|
NEMA |
Voltage |
Enclosure [15] |
Ampere Interrupting |
0–1 |
480 |
Standard |
100,000 |
0–1 |
481 – 600 |
Standard |
35,000 |
2–5 |
480 |
Standard |
100,000 |
2–5 |
481 – 600 |
Standard |
50,000 |
6 |
480 |
Standard |
65,000 |
6 |
600 |
Standard |
18,000 |
Thermal Magnetic Circuit Breaker Type |
|||
0–1 |
480 |
Standard |
100,000 |
0–1 |
481–600 |
Standard |
35,000 |
2–5 |
480 |
Standard |
100,000 |
2–5 |
481–600 |
Standard |
50,000 |
6 |
480 |
Standard |
65,000 |
6 |
600 |
Standard |
18,000 |