Diagnostics
Avatar Diagnostics Inputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Reset Max IRMS |
BOOL |
1 |
1 |
0, 1 |
Command
to reset the Maximum Average IRMS current value and Time Stamp. |
Avatar Diagnostics Outputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Upstream Voltage Present 1 |
BOOL |
1 |
1 |
0, 1 |
The avatar
has detected that Upstream main power of its first Device is
present (Breaker closed). |
|
Upstream Voltage Present 2 |
BOOL |
1 |
1 |
0, 1 |
the avatar
has detected that Upstream main power of its second Device (if
available) is present. |
|
Upstream Voltage Present 3 |
BOOL |
1 |
1 |
0, 1 |
The avatar
has detected that Upstream main power of its third Device (if available)
is present. |
|
Upstream Voltage Present 4 |
BOOL |
1 |
1 |
0, 1 |
The avatar
has detected that Upstream main power of its fourth Device (if available)
is present. |
|
Max Average IRMS |
UINT |
16 |
0.1 |
0–65,535 |
Indicates the maximum current (A) measured by the device in its lifetime. |
|
Max Average IRMS Time Stamp |
DT |
64 |
— |
— |
Provides the date and time when Maximum average IRMS current value has been recorded. |
|
IRMS Phase 1 |
UDINT |
32 |
0.001 |
0 to 4,294,967,295 |
Phase L1 IRMS value (A) |
|
IRMS Phase 2 |
UDINT |
32 |
0.001 |
0 to 4,294,967,295 |
Phase L2 IRMS value (A) |
|
IRMS Phase 3 |
UDINT |
32 |
0.001 |
0 to 4,294,967,295 |
Phase L3 IRMS value (A) |
Avatar Read Alarm Counters Inputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Reset Alarm Counter |
BOOL |
1 |
1 |
0, 1 |
Resets all
alarm counters to 0. |
Avatar Read Alarm Counters Outputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Thermal Overload Alarm Count |
UINT |
16 |
1 |
0–65,535 |
Counter of alarms related to Thermal Overload protection. |
|
Jam Alarm Count |
UINT |
16 |
1 |
0–65,535 |
Counter of alarms related to Jam protection. |
|
Undercurrent Alarm Count |
UINT |
16 |
1 |
0–65,535 |
Counter of alarms related to Undercurrent protection. |
|
Overcurrent Alarm Count |
UINT |
16 |
1 |
0–65,535 |
Counter of alarms related to Overcurrent protection. |
|
Current Phase Unbalance Alarm Count |
UINT |
16 |
1 |
0–65,535 |
Counter of alarms related to Phase Unbalance protection. |
|
Ground Current Alarm Count |
UINT |
16 |
1 |
0–65,535 |
Counter of alarms related to Ground Current protection. |
|
Motor Overheat Alarm Count |
UINT |
16 |
1 |
0–65,535 |
Counter of Motor Overheat Alarm events. |
|
All Alarms Count |
UINT |
16 |
1 |
0–65,535 |
Counter of all alarms related to protections. |
Avatar Read Trip Counters Inputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Reset Trip Counter |
BOOL |
1 |
1 |
0, 1 |
Reset all
trip counters. |
Avatar Read Trip Counters Outputs
I/O Name |
Datatype |
Size (bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Thermal Overload Trip Count |
UINT |
16 |
1 |
0–65,535 |
Counter of trips related to Thermal Overload protection. |
|
Jam Trip Count |
UINT |
16 |
1 |
0–65,535 |
Counter of trips related to Jam protection. |
|
Undercurrent Trip Count |
UINT |
16 |
1 |
0–65,535 |
Counter of trips related to Undercurrent protection. |
|
Long Start Trip Count |
UINT |
16 |
1 |
0–65,535 |
Counter of trips related to Long Start protection. |
|
Overcurrent Trip Count |
UINT |
16 |
1 |
0–65,535 |
Counter of trips related to Overcurrent protection. |
|
Motor Overheat Trip Count |
UINT |
16 |
1 |
0–65,535 |
Counter of Motor Overheat trip events. |
|
Stall Trip Count |
UINT |
16 |
1 |
0–65,535 |
Counter of trips related to Stall protection. |
|
Current Phase Unbalance Trip Count |
UINT |
16 |
1 |
0–65,535 |
Counter of trips related to Phase Unbalance protection. |
|
Phase Configuration Trip Count |
UINT |
16 |
1 |
0–65,535 |
Counter of trips related to Phase Configuration protection. |
|
Ground Current Trip Count |
UINT |
16 |
1 |
0–65,535 |
Counter of trips related to Ground Current protection. |
|
Phase Reversal Trip Count |
UINT |
16 |
1 |
0–65,535 |
Counter of trips related to Phase Reversal protection. |
|
Current Phase Loss Trip Count |
UINT |
16 |
1 |
0–65,535 |
Counter of trips related to Phase Loss protection. |
|
All Trips Count |
UINT |
16 |
1 |
0–65,535 |
Counter of all trips related to protections. |
Avatar Trip Register Outputs
I/O Name |
Datatype |
Size (bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Trip Record Register 1 |
TRIPREC |
80 |
— |
0, — |
Date and Trip reason record 1 |
|
Trip Record Register 2 |
TRIPREC |
80 |
— |
0, — |
Date and Trip reason record 2 |
|
Trip Record Register 3 |
TRIPREC |
80 |
— |
0, — |
Date and Trip reason record 3 |
|
Trip Record Register 4 |
TRIPREC |
80 |
— |
0, — |
Date and Trip reason record 4 |
|
Trip Record Register 5 |
TRIPREC |
80 |
— |
0, — |
Date and Trip reason record 5 |