8536IB1905EN-05

Diagnostics

Avatar Diagnostics Inputs

I/O Name

Datatype

Size (Bits)

Scale

Value

Description

Reset Max IRMS

BOOL

1

1

0, 1

Command to reset the Maximum Average IRMS current value and Time Stamp.
0 = Off, 1 = On

Avatar Diagnostics Outputs

I/O Name

Datatype

Size (Bits)

Scale

Value

Description

Upstream Voltage Present 1

BOOL

1

1

0, 1

The avatar has detected that Upstream main power of its first Device  is present (Breaker closed).
0 = no voltage presence detected
1 = voltage presence detected

Upstream Voltage Present 2

BOOL

1

1

0, 1

the avatar has detected that Upstream main power of its second  Device (if available) is present.
0 = no voltage presence detected
1 = voltage presence detected

Upstream Voltage Present 3

BOOL

1

1

0, 1

The avatar has detected that Upstream main power of its third Device (if available) is present.
0 = no voltage presence detected
1 = voltage presence detected

Upstream Voltage Present 4

BOOL

1

1

0, 1

The avatar has detected that Upstream main power of its fourth Device (if available) is present.
0 = no voltage presence detected
1 = voltage presence detected

Max Average IRMS

UINT

16

0.1

0–65,535
in steps of 1

Indicates the maximum current (A) measured by the device in its lifetime.

Max Average IRMS Time Stamp

DT

64

Provides the date and time when Maximum average IRMS current value has been recorded.

IRMS Phase 1

UDINT

32

0.001

0 to 4,294,967,295
in steps of 1

Phase L1 IRMS value (A)

IRMS Phase 2

UDINT

32

0.001

0 to 4,294,967,295
in steps of 1

Phase L2 IRMS value (A)

IRMS Phase 3

UDINT

32

0.001

0 to 4,294,967,295
in steps of 1

Phase L3 IRMS value (A)

Avatar Read Alarm Counters Inputs

I/O Name

Datatype

Size (Bits)

Scale

Value

Description

Reset Alarm Counter

BOOL

1

1

0, 1

Resets all alarm counters to 0.
0 = Off, 1 = On

Avatar Read Alarm Counters Outputs

I/O Name

Datatype

Size (Bits)

Scale

Value

Description

Thermal Overload Alarm Count

UINT

16

1

0–65,535
in steps of 1

Counter of alarms related to Thermal Overload protection.

Jam Alarm Count

UINT

16

1

0–65,535
in steps of 1

Counter of alarms related to Jam protection.

Undercurrent Alarm Count

UINT

16

1

0–65,535
in steps of 1

Counter of alarms related to Undercurrent protection.

Overcurrent Alarm Count

UINT

16

1

0–65,535
in steps of 1

Counter of alarms related to Overcurrent protection.

Current Phase Unbalance Alarm Count

UINT

16

1

0–65,535
in steps of 1

Counter of alarms related to Phase Unbalance protection.

Ground Current Alarm Count

UINT

16

1

0–65,535
in steps of 1

Counter of alarms related to Ground Current protection.

Motor Overheat Alarm Count

UINT

16

1

0–65,535
in steps of 1

Counter of Motor Overheat Alarm events.

All Alarms Count

UINT

16

1

0–65,535
in steps of 1

Counter of all alarms related to protections.

Avatar Read Trip Counters Inputs

I/O Name

Datatype

Size (Bits)

Scale

Value

Description

Reset Trip Counter

BOOL

1

1

0, 1

Reset all trip counters.
0 = Off, 1 = On

Avatar Read Trip Counters Outputs

I/O Name

Datatype

Size (bits)

Scale

Value

Description

Thermal Overload Trip Count

UINT

16

1

0–65,535
in steps of 1

Counter of trips related to Thermal Overload protection.

Jam Trip Count

UINT

16

1

0–65,535
in steps of 1

Counter of trips related to Jam protection.

Undercurrent Trip Count

UINT

16

1

0–65,535
in steps of 1

Counter of trips related to Undercurrent protection.

Long Start Trip Count

UINT

16

1

0–65,535
in steps of 1

Counter of trips related to Long Start protection.

Overcurrent Trip Count

UINT

16

1

0–65,535
in steps of 1

Counter of trips related to Overcurrent protection.

Motor Overheat Trip Count

UINT

16

1

0–65,535
in steps of 1

Counter of Motor Overheat trip events.

Stall Trip Count

UINT

16

1

0–65,535
in steps of 1

Counter of trips related to Stall protection.

Current Phase Unbalance Trip Count

UINT

16

1

0–65,535
in steps of 1

Counter of trips related to Phase Unbalance protection.

Phase Configuration Trip Count

UINT

16

1

0–65,535
in steps of 1

Counter of trips related to Phase Configuration protection.

Ground Current Trip Count

UINT

16

1

0–65,535
in steps of 1

Counter of trips related to Ground Current protection.

Phase Reversal Trip Count

UINT

16

1

0–65,535
in steps of 1

Counter of trips related to Phase Reversal protection.

Current Phase Loss Trip Count

UINT

16

1

0–65,535
in steps of 1

Counter of trips related to Phase Loss protection.

All Trips Count

UINT

16

1

0–65,535
in steps of 1

Counter of all trips related to protections.

Avatar Trip Register Outputs

I/O Name

Datatype

Size (bits)

Scale

Value

Description

Trip Record Register 1

TRIPREC

80

0, —

Date and Trip reason record 1

Trip Record Register 2

TRIPREC

80

0, —

Date and Trip reason record 2

Trip Record Register 3

TRIPREC

80

0, —

Date and Trip reason record 3

Trip Record Register 4

TRIPREC

80

0, —

Date and Trip reason record 4

Trip Record Register 5

TRIPREC

80

0, —

Date and Trip reason record 5