Diagnostics
This function block performs the following functions for the selected avatar:
-
Returns diagnostic information
-
Resets the Maximum IRMS register
-
Returns the values of the trip counters and resets all trip counters
-
Returns the values of the trip registers
-
Returns the values of the alarm counters and resets all alarm counters
Modbus TCP Inputs—Diagnostics
|
Input Name |
Address |
Starting Bit |
Size (Bits) |
|---|---|---|---|
|
Reset Trip Counter |
710 |
0 |
1 |
|
Reset Alarm Counter |
710 |
1 |
1 |
|
Reset Maximum IRMS |
710 |
2 |
1 |
Modbus TCP Outputs—Diagnostics
|
Output Name |
Address |
Starting Bit |
Size (Bits) |
|---|---|---|---|
|
Maximum Average IRMS |
32 |
0 |
16 |
|
Ground Current Trip Count |
102 |
0 |
16 |
|
Thermal Overload Trip Count |
103 |
0 |
16 |
|
Long Start Trip Count |
104 |
0 |
16 |
|
Jam Trip Count |
105 |
0 |
16 |
|
Current Phase Unbalance Trip Count |
106 |
0 |
16 |
|
Undercurrent Trip Count |
107 |
0 |
16 |
|
Thermal Overload Alarm Count |
116 |
0 |
16 |
|
All Trips Count |
122 |
0 |
16 |
|
All Alarms Counter |
123 |
0 |
16 |
|
Stall Trip Count |
129 |
0 |
16 |
|
Overcurrent Trip Count |
130 |
0 |
16 |
|
Current Phase Loss Trip Count |
131 |
0 |
16 |
|
Motor Overheat Trip Count |
132 |
0 |
16 |
|
Phase Reversal Trip Count |
135 |
0 |
16 |
|
Trip Record Register 1 |
150 |
0 |
80 |
|
Trip Record Register 2 |
180 |
0 |
80 |
|
Trip Record Register 3 |
210 |
0 |
80 |
|
Trip Record Register 4 |
240 |
0 |
80 |
|
Trip Record Register 5 |
270 |
0 |
80 |
|
IRMS Phase 1 |
502 |
0 |
32 |
|
IRMS Phase 2 |
504 |
0 |
32 |
|
IRMS Phase 3 |
506 |
0 |
32 |
|
Phase Configuration Trip Count |
1500 |
0 |
16 |
|
Ground Current Alarm Count |
1502 |
0 |
16 |
|
Jam Alarm Count |
1505 |
0 |
16 |
|
Current Phase Unbalance Alarm Count |
1506 |
0 |
16 |
|
Undercurrent Alarm Count |
1507 |
0 |
16 |
|
Overcurrent Alarm Count |
1530 |
0 |
16 |
|
Motor Overheat Alarm Count |
1532 |
0 |
16 |
|
Max Average IRMS Time Stamp |
2104 |
0 |
64 |
|
Upstream Voltage Present 1 |
3202 |
12 |
1 |
|
Upstream Voltage Present 2 |
3202 |
13 |
1 |
|
Upstream Voltage Present 3 |
3202 |
14 |
1 |
|
Upstream Voltage Present 4 |
3202 |
15 |
1 |