System Energy
This function block performs the following functions:
-
Returns the energy information of the System Avatar
-
Resets the energy registers of the System Avatar
-
Sets the energy preset values of the System Avatar
Modbus TCP Inputs—System Energy
Input Name |
Address |
Starting Bit |
Size (Bits) |
---|---|---|---|
Reset Maximum Voltage RMS |
711 |
0 |
1 |
Reset Maximum Unbalance Voltage |
711 |
1 |
1 |
Reset Upstream Voltage Fluctuation Status |
711 |
2 |
1 |
Reset Voltage Dip Count |
711 |
8 |
1 |
Reset Voltage Swell Count |
711 |
9 |
1 |
Reset Maximum Total Active Power |
712 |
0 |
1 |
Reset Maximum Total Reactive Power |
712 |
1 |
1 |
Reset Minimum True Power Factor |
712 |
8 |
1 |
Reset Maximum True Power Factor |
712 |
9 |
1 |
Reset Total Active Energy |
713 |
0 |
1 |
Reset Total Reactive Energy |
713 |
1 |
1 |
Modbus TCP Outputs—System Energy
Output Name |
Address |
Starting Bit |
Size (Bits) |
---|---|---|---|
Total Active Energy |
143 |
0 |
32 |
Total Reactive Energy |
145 |
0 |
32 |
Frequency (Hz) |
474 |
0 |
8 |
Average Voltage RMS |
476 |
0 |
16 |
Voltage RMS Phase 1 (V) |
477 |
0 |
16 |
Voltage RMS Phase 2 (V) |
478 |
0 |
16 |
Voltage RMS Phase 3 (V) |
479 |
0 |
16 |
Percentage of Unbalance Voltage (%) |
480 |
0 |
8 |
True Power Factor |
481 |
0 |
8 |
Instantaneous Total Active Power |
482 |
0 |
32 |
Instantaneous Total Reactive Power |
484 |
0 |
32 |
Voltage Dip Count |
1550 |
0 |
16 |
Voltage Swell Count |
1551 |
0 |
16 |
Upstream Voltage Fluctuation Status |
1553 |
0 |
1 |
Voltage Dip Record Register 1 (most recent) |
1600 |
0 |
16 |
Voltage Dip Record 1 Start Date |
1601 |
0 |
64 |
Voltage Dip Record 1 Stop Date |
1605 |
0 |
64 |
Voltage Dip Record Register 2 |
1609 |
0 |
16 |
Voltage Dip Record 2 Start Date |
1610 |
0 |
64 |
Voltage Dip Record 2 Stop Date |
1614 |
0 |
64 |
Voltage Dip Record Register 3 |
1618 |
0 |
16 |
Voltage Dip Record 3 Start Date |
1619 |
0 |
64 |
Voltage Dip Record 3 Stop Date |
1623 |
0 |
64 |
Voltage Dip Record Register 4 |
1627 |
0 |
16 |
Voltage Dip Record 4 Start Date |
1628 |
0 |
64 |
Voltage Dip Record 4 Stop Date |
1632 |
0 |
64 |
Voltage Dip Record Register 5 (least recent) |
1636 |
0 |
16 |
Voltage Dip Record 5 Start Date |
1637 |
0 |
64 |
Voltage Dip Record 5 Stop Date |
1641 |
0 |
64 |
Voltage Swell Record Register 1 (most recent) |
1650 |
0 |
16 |
Voltage Swell Record 1 Start Date |
1651 |
0 |
64 |
Voltage Swell Record 1 Stop Date |
1655 |
0 |
64 |
Voltage Swell Record Register 2 |
1659 |
0 |
16 |
Voltage Swell Record 2 Start Date |
1660 |
0 |
64 |
Voltage Swell Record 2 Stop Date |
1664 |
0 |
64 |
Voltage Swell Record Register 3 |
1668 |
0 |
16 |
Voltage Swell Record 3 Start Date |
1669 |
0 |
64 |
Voltage Swell Record 3 Stop Date |
1673 |
0 |
64 |
Voltage Swell Record Register 4 |
1677 |
0 |
16 |
Voltage Swell Record 4 Start Date |
1678 |
0 |
64 |
Voltage Swell Record 4 Stop Date |
1682 |
0 |
64 |
Voltage Swell Record Register 5 (least recent) |
1686 |
0 |
16 |
Voltage Swell Record 5 Start Date |
1687 |
0 |
64 |
Voltage Swell Record 5 Stop Date |
1691 |
0 |
64 |
Maximum Average Voltage Timestamp |
2120 |
0 |
64 |
Maximum Average Voltage RMS |
2124 |
0 |
16 |
Maximum Unbalance Voltage Timestamp |
2128 |
0 |
64 |
Maximum Unbalance Voltage % |
2132 |
0 |
8 |
Maximum Total Active Power Timestamp |
2140 |
0 |
64 |
Maximum Total Active Power |
2144 |
0 |
32 |
Maximum Total Reactive Power Timestamp |
2148 |
0 |
64 |
Maximum Total Reactive Power |
2152 |
0 |
32 |
Maximum True Power Factor Timestamp |
2160 |
0 |
64 |
Maximum True Power Factor |
2164 |
0 |
8 |
Minimum True Power Factor Timestamp |
2168 |
0 |
64 |
Minimum True Power Factor |
2172 |
0 |
8 |
Voltage Phase Sequence (ABC or ACB) |
3202 |
0 |
1 |