8536IB1905EN-05

Energy

This function block performs the following functions:

  • Returns the energy and power information of the selected avatar

  • Resets the energy registers of the selected avatar

  • Sets the energy preset values of the selected avatar

Energy Function Block

Modbus TCP Inputs—Energy

Input Name

Address

Starting Bit

Size (Bits)

Total Active Energy Preset Value

680

0

32

Total Reactive Energy Preset Value

682

0

32

Run Record ToU Channel 1

713

2

1

Run Record ToU Channel 2

713

3

1

Run Record ToU Channel 3

713

4

1

Run Record ToU Channel 4

713

5

1

Set Total Active Energy

713

6

1

Set Total Reactive Energy

713

7

1

Modbus TCP Outputs—Energy

Output Name

Address

Starting Bit

Size (Bits)

Total Active Energy

143

0

32

Total Reactive Energy

145

0

32

True Power Factor

481

0

8

Instantaneous Total Active Power

482

0

32

Instantaneous Total Reactive Power

484

0

32

Maximum Total Active Power Timestamp

2140

0

64

Maximum Total Active Power

2144

0

32

Maximum Total Reactive Power Timestamp

2148

0

64

Maximum Total Reactive Power

2152

0

32

Maximum True Power Factor Timestamp

2160

0

64

Maximum True Power Factor

2164

0

8

Minimum True Power Factor Timestamp

2168

0

64

Minimum True Power Factor

2172

0

8

ToU Total Active Energy Channel 1

2200

0

32

ToU Total Reactive Energy Channel 1

2202

0

32

ToU Total Active Energy Channel 2

2204

0

32

ToU Total Reactive Energy Channel 2

2206

0

32

ToU Total Active Energy Channel 3

2208

0

32

ToU Total Reactive Energy Channel 3

2210

0

32

ToU Total Active Energy Channel 4

2212

0

32

ToU Total Reactive Energy Channel 4

2214

0

32

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?