Energy
This function block performs the following functions:
-
Returns the energy and power information of the selected avatar
-
Resets the energy registers of the selected avatar
-
Sets the energy preset values of the selected avatar
Modbus TCP Inputs—Energy
|
Input Name |
Address |
Starting Bit |
Size (Bits) |
|---|---|---|---|
|
Total Active Energy Preset Value |
680 |
0 |
32 |
|
Total Reactive Energy Preset Value |
682 |
0 |
32 |
|
Run Record ToU Channel 1 |
713 |
2 |
1 |
|
Run Record ToU Channel 2 |
713 |
3 |
1 |
|
Run Record ToU Channel 3 |
713 |
4 |
1 |
|
Run Record ToU Channel 4 |
713 |
5 |
1 |
|
Set Total Active Energy |
713 |
6 |
1 |
|
Set Total Reactive Energy |
713 |
7 |
1 |
Modbus TCP Outputs—Energy
|
Output Name |
Address |
Starting Bit |
Size (Bits) |
|---|---|---|---|
|
Total Active Energy |
143 |
0 |
32 |
|
Total Reactive Energy |
145 |
0 |
32 |
|
True Power Factor |
481 |
0 |
8 |
|
Instantaneous Total Active Power |
482 |
0 |
32 |
|
Instantaneous Total Reactive Power |
484 |
0 |
32 |
|
Maximum Total Active Power Timestamp |
2140 |
0 |
64 |
|
Maximum Total Active Power |
2144 |
0 |
32 |
|
Maximum Total Reactive Power Timestamp |
2148 |
0 |
64 |
|
Maximum Total Reactive Power |
2152 |
0 |
32 |
|
Maximum True Power Factor Timestamp |
2160 |
0 |
64 |
|
Maximum True Power Factor |
2164 |
0 |
8 |
|
Minimum True Power Factor Timestamp |
2168 |
0 |
64 |
|
Minimum True Power Factor |
2172 |
0 |
8 |
|
ToU Total Active Energy Channel 1 |
2200 |
0 |
32 |
|
ToU Total Reactive Energy Channel 1 |
2202 |
0 |
32 |
|
ToU Total Active Energy Channel 2 |
2204 |
0 |
32 |
|
ToU Total Reactive Energy Channel 2 |
2206 |
0 |
32 |
|
ToU Total Active Energy Channel 3 |
2208 |
0 |
32 |
|
ToU Total Reactive Energy Channel 3 |
2210 |
0 |
32 |
|
ToU Total Active Energy Channel 4 |
2212 |
0 |
32 |
|
ToU Total Reactive Energy Channel 4 |
2214 |
0 |
32 |