Energy
System Voltage Basic Inputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Reset Maximum Voltage RMS |
BOOL |
1 |
1 |
0, 1 |
Reset the
Max. Voltage RMS value and associated timestamps. |
|
Reset Maximum Unbalance Voltage |
BOOL |
1 |
1 |
0, 1 |
Reset Max.
Unbalance Voltage to zero, and associated timestamp. |
|
Reset Upstream Voltage Fluctuation Status |
BOOL |
1 |
1 |
0, 1 |
Command
to reset Voltage Fluctuation Status. |
System Voltage Basic Outputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Upstream Voltage Fluctuation Status |
BOOL |
1 |
1 |
0, 1 |
On when
a Voltage Dip or Swell has occurred. Reset by command. |
|
Average Voltage RMS |
UINT |
16 |
1 |
0–1,000 |
Average RMS Voltage (V) on 3 phases |
|
Maximum Average Voltage RMS |
UINT |
16 |
1 |
0–65,535 |
Maximum voltage (V) measured by the system |
|
Maximum Average Voltage Timestamp |
DT |
64 |
— |
— |
Date and Time of the maximum average voltage |
|
Voltage RMS Phase 1 (V) |
UINT |
16 |
1 |
0–65,535 |
Average RMS voltage (V) between L1 and neutral |
|
Voltage RMS Phase 2 (V) |
UINT |
16 |
1 |
0–65,535 |
Average RMS voltage (V) between L2 and neutral |
|
Voltage RMS Phase 3 (V) |
UINT |
16 |
1 |
0–65,535 |
Average RMS voltage (V) between L3 and neutral |
|
Percentage of Unbalance Voltage (%) |
USINT |
8 |
1 |
0–100 |
% of unbalance voltage |
|
Maximum Unbalance Voltage % |
USINT |
8 |
1 |
0–100 |
Maximum unbalance voltage in % |
|
Maximum Unbalance Voltage Timestamp |
DT |
64 |
— |
— |
Date and Time of the maximum unbalance voltage |
|
Voltage Phase Sequence (ABC or ACB) |
BOOL |
1 |
1 |
0, 1 |
Measured
voltage phase sequence (ABC or ACB) |
|
Frequency (Hz) |
USINT |
8 |
1 |
0–255 |
Main power voltage frequency (Hz). This register returns the line frequency as measured on phase 1. |
System Voltage Enhanced Inputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Reset Voltage Dip Count |
BOOL |
1 |
1 |
0, 1 |
Command
to reset the Voltage Dip counter to 0. |
|
Reset Voltage Swell Count |
BOOL |
1 |
1 |
0, 1 |
Command
to reset the Voltage Swell counter to 0. |
System Voltage Enhanced Outputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Voltage Dip Record Register 1 (most recent) |
UINT |
16 |
1 |
0–65,335 |
Minimum voltage magnitude (V) for Voltage Dip Record 1 |
|
Voltage Dip Record Register 2 |
UINT |
16 |
1 |
0–65,335 |
Minimum voltage magnitude (V) for Voltage Dip Record 2 |
|
Voltage Dip Record Register 3 |
UINT |
16 |
1 |
0–65,335 |
Minimum voltage magnitude (V) for Voltage Dip Record 3 |
|
Voltage Dip Record Register 4 |
UINT |
16 |
1 |
0–65,335 |
Minimum voltage magnitude (V) for Voltage Dip Record 4 |
|
Voltage Dip Record Register 5 (least recent) |
UINT |
16 |
1 |
0–65,335 |
Minimum voltage magnitude (V) for Voltage Dip Record 5 |
|
Voltage Dip Record 1 Start Date |
DT |
64 |
— |
— |
Voltage Dip Record Register 1 Start Timestamp (Date, Time) |
|
Voltage Dip Record 2 Start Date |
DT |
64 |
— |
— |
Voltage Dip Record Register 2 Start Timestamp (Date, Time) |
|
Voltage Dip Record 3 Start Date |
DT |
64 |
— |
— |
Voltage Dip Record Register 3 Start Timestamp (Date, Time) |
|
Voltage Dip Record 4 Start Date |
DT |
64 |
— |
— |
Voltage Dip Record Register 4 Start Timestamp (Date, Time) |
|
Voltage Dip Record 5 Start Date |
DT |
64 |
— |
— |
Voltage Dip Record Register 5 Start Timestamp (Date, Time) |
|
Voltage Dip Record 1 Stop Date |
DT |
64 |
— |
— |
Voltage Dip Record Register 1 Stop Timestamp (Date, Time) |
|
Voltage Dip Record 2 Stop Date |
DT |
64 |
— |
— |
Voltage Dip Record Register 2 Stop Timestamp (Date, Time) |
|
Voltage Dip Record 3 Stop Date |
DT |
64 |
— |
— |
Voltage Dip Record Register 3 Stop Timestamp (Date, Time) |
|
Voltage Dip Record 4 Stop Date |
DT |
64 |
— |
— |
Voltage Dip Record Register 4 Stop Timestamp (Date, Time) |
|
Voltage Dip Record 5 Stop Date |
DT |
64 |
— |
— |
Voltage Dip Record Register 5 Stop Timestamp (Date, Time) |
|
Voltage Dip Count |
UINT |
16 |
1 |
0–65,335 |
Voltage Dip counter |
|
Voltage Swell Record Register 1 (most recent) |
UINT |
16 |
1 |
0–65,335 |
Maximum voltage magnitude (V) for Voltage Swell Record 1 |
|
Voltage Swell Record Register 2 |
UINT |
16 |
1 |
0–65,335 |
Maximum voltage magnitude (V) for Voltage Swell Record 2 |
|
Voltage Swell Record Register 3 |
UINT |
16 |
1 |
0–65,335 |
Maximum voltage magnitude (V) for Voltage Swell Record 3 |
|
Voltage Swell Record Register 4 |
UINT |
16 |
1 |
0–65,335 |
Maximum voltage magnitude (V) for Voltage Swell Record 4 |
|
Voltage Swell Record Register 5 (least recent) |
UINT |
16 |
1 |
0–65,335 |
Maximum voltage magnitude (V) Voltage Swell Record 5 |
|
Voltage Swell Record 1 Start Date |
DT |
64 |
— |
— |
Voltage Swell Record Register 1 Start Timestamp (Date, Time) |
|
Voltage Swell Record 2 Start Date |
DT |
64 |
— |
— |
Voltage Swell Record Register 2 Start Timestamp (Date, Time) |
|
Voltage Swell Record 3 Start Date |
DT |
64 |
— |
— |
Voltage Swell Record Register 3 Start Timestamp (Date, Time) |
|
Voltage Swell Record 4 Start Date |
DT |
64 |
— |
— |
Voltage Swell Record Register 4 Start Timestamp (Date, Time) |
|
Voltage Swell Record 5 Start Date |
DT |
64 |
— |
— |
Voltage Swell Record Register 5 Start Timestamp (Date, Time) |
|
Voltage Swell Record 1 Stop Date |
DT |
64 |
— |
— |
Voltage Swell Record Register 1 Stop Timestamp (Date, Time) |
|
Voltage Swell Record 2 Stop Date |
DT |
64 |
— |
— |
Voltage Swell Record Register 2 Stop Timestamp (Date, Time) |
|
Voltage Swell Record 3 Stop Date |
DT |
64 |
— |
— |
Voltage Swell Record Register 3 Stop Timestamp (Date, Time) |
|
Voltage Swell Record 4 Stop Date |
DT |
64 |
— |
— |
Voltage Swell Record Register 4 Stop Timestamp (Date, Time) |
|
Voltage Swell Record 5 Stop Date |
DT |
64 |
— |
— |
Voltage Swell Record Register 5 Stop Timestamp (Date, Time) |
|
Voltage Swell Count |
UINT |
16 |
1 |
0–65,335 |
Voltage Swell counter |
System Power Basic Inputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Reset Maximum Total Active Power |
BOOL |
1 |
1 |
0, 1 |
Reset the
Active Power Max. value and associated timestamp. |
|
Reset Maximum Total Reactive Power |
BOOL |
1 |
1 |
0, 1 |
Reset the
Reactive Power Max. value and associated timestamp. |
|
Reset Minimum True Power Factor |
BOOL |
1 |
1 |
0, 1 |
Reset the
true Power Factor Min. value to 1 and associated timestamp. |
|
Reset Maximum True Power Factor |
BOOL |
1 |
1 |
0, 1 |
Reset the
true Power Factor Max. value to 0 and associated timestamp. |
System Power Basic Outputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Instantaneous Total Active Power |
DINT |
32 |
0.001 |
–2,147,483,648 to 2,147,483,647 |
Returns the total Active Power (kW) for the avatar. |
|
Maximum Total Active Power |
DINT |
32 |
0.001 |
–9,999,999 to 9,999,999 |
Returns the maximum value of total active power (kW) for the avatar. |
|
Maximum Total Active Power Timestamp |
DT |
64 |
— |
— |
Provide date and time when maximum total Active Power value has been recorded. |
|
Instantaneous Total Reactive Power |
DINT |
32 |
0.001 |
–9,999,999 to 9,999,999 |
Returns the total Reactive Power value (kVAR) for the avatar. |
|
Maximum Total Reactive Power |
DINT |
32 |
0.001 |
–9,999,999 to 9,999,999 |
Returns the maximum value of Reactive Power (kVAR) for the avatar. |
|
Maximum Total Reactive Power Timestamp |
DT |
64 |
— |
— |
Provides date and time when total maximum total Reactive Power value has been recorded. |
|
True Power Factor |
USINT |
8 |
0.01 |
0–100 |
Returns the true Power factor value. |
|
Minimum True Power Factor |
USINT |
8 |
0.01 |
0–100 |
Returns the true Power factor minimum value. |
|
Maximum True Power Factor |
USINT |
8 |
0.01 |
0–100 |
Returns the true Power factor maximum value. |
|
Minimum True Power Factor Timestamp |
DT |
64 |
— |
— |
Provide date and time when Minimum Power Factor value has been recorded. |
|
Maximum True Power Factor Timestamp |
DT |
64 |
— |
— |
Provide date and time when Maximum Power Factor value has been recorded. |
System Energy Basic Inputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Reset Total Reactive Energy |
BOOL |
1 |
1 |
0, 1 |
Resets System
Avatar accumulation of reactive energy to zero, does not affect load
or application level energy data. |
|
Reset Total Active Energy |
BOOL |
1 |
1 |
0, 1 |
Command
to set the Total Active Energy value to Total Active Energy Preset
value. |
System Energy Basic Outputs
I/O Name |
Datatype |
Size (Bits) |
Scale |
Value |
Description |
|
---|---|---|---|---|---|---|
Total Active Energy |
UDINT |
32 |
0.001 |
0–4,294,967,295 |
Returns the Total Active Energy value (kWh). |
|
Total Reactive Energy |
UDINT |
32 |
0.001 |
0–999,999,999 |
Returns the Total Reactive Energy value (kVARh). |