Crimp Lug Cable Assembly for Cabled Disconnect Unit Installation
![]() |
---|
Hazard of Electric Shock, Explosion, or Arc Flash
Failure to follow these instructions will result in death or serious injury.
|
-
Turn off all power supplying this equipment before working on or inside the equipment, and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
Access the horizontal bus in the motor control center (see Typical Cabled Disconnect Unit).
-
Remove the horizontal bus mounting nuts and washers (item 5) from the horizontal bus assembly (see Typical Horizontal Bus Assembly).
-
Insert the loom bolts (item 2) through the rear of the lug pad (item 3).
-
Using the mounting nuts and washers from Step 3, attach the lug pad to the horizontal bus mounting bolts (item 1).
-
Torque the horizontal bus mounting nuts to 820–840 lb-in (93–95 N•m).
-
Route the cable to the circuit breaker or fuse disconnect unit (see Typical Cabled Disconnect Unit); trim cable length as required.
-
Using the lug pad nuts and washers (item 6), attach the crimp lug cable assembly (item 4) to the loom bolts on the lug pad.
-
Torque the lug pad nuts to 820–840 lb-in (93–95 N•m).