Splicing Without P Gasketing
-
Turn off all power supplying this equipment before working on or inside the equipment, and follow lockout/tagout procedures. Always use a properly rated voltage sensing device to confirm the power is off.
-
If splicing to an existing MCC, remove the end plate and any gasketing from the existing MCC.
-
Remove the white paper backing from the new gaskets (supplied by Schneider Electric) to expose the adhesive. This adhesive temporarily holds the gaskets in place while the sections are being positioned.
-
Apply flat gaskets to the outside of the front and rear vertical corner channels. The gaskets should not extend above the top of the corner channels.
-
Apply flat gaskets to the outside of the top and bottom tie channels. The gaskets should not extend above the top of the tie channels.
-
Applying thumb pressure, firmly press the gaskets in place from top to bottom. Verify that the gaskets are flat along the entire length.
-
Join sections together following the appropriate steps in Joining Type 1, Type 1 Gasketed, and Type 12 Sections or Joining Type 1 Sprinkler-Resistant Sections.