Energy
|
Energy values – 64-bit integer |
||||||
|---|---|---|---|---|---|---|
|
Address |
Register |
Action |
Size |
Type |
Units |
Description |
|
Total Energy (cannot be reset) |
||||||
|
0x0C83 |
3204 |
R |
4 |
Int64 |
Wh |
Total Active Energy Import |
|
Partial Energy |
||||||
|
0x0CB7 |
3256 |
R |
4 |
Int64 |
Wh |
Partial Active Energy Import |
|
Phase Energy |
||||||
|
0x0DBD |
3518 |
R |
4 |
Int64 |
Wh |
Active Energy Import Phase 1 |
|
0x0DC1 |
3522 |
R |
4 |
Int64 |
Wh |
Active Energy Import Phase 2 |
|
0x0DC5 |
3526 |
R |
4 |
Int64 |
Wh |
Active Energy Import Phase 3 |
|
Energy values – 32-bit floating point |
||||||
|---|---|---|---|---|---|---|
|
Address |
Register |
Action |
Size |
Type |
Units |
Description |
|
Total Energy (cannot be reset) |
||||||
|
0xB02B |
45100 |
R |
2 |
Float32 |
kWh |
Total Active Energy Import |
|
Partial Energy |
||||||
|
0xB033 |
45108 |
R |
2 |
Float32 |
kWh |
Partial Active Energy Import |
|
Phase Energy |
||||||
|
0xB037 |
45112 |
R |
2 |
Float32 |
kWh |
Active Energy Import Phase 1 |
|
0xB039 |
45114 |
R |
2 |
Float32 |
kWh |
Active Energy Import Phase 2 |
|
0xB03B |
45116 |
R |
2 |
Float32 |
kWh |
Active Energy Import Phase 3 |