DOCA0384EN-01

Protection Submit Commands

List of Commands

The following table lists the protection submit commands, their corresponding command codes, and user profiles:

Command

Command code

User profile

Submit long time over current protection settings

51593

No password required

Submit short time over current protection settings

51594

No password required

Submit instantaneous protection settings

51595

No password required

Submit ground fault protection settings

51596

No password required

Submit neutral protection settings

51598

No password required

Submit Long Time Over Current Protection Settings

To get the long time over current protection settings, use the get long time over current protection setting command.

WARNING
HAZARD OF NUISANCE TRIPPING OR FAILURE TO TRIP
Protection setting adjustments must be done only by qualified electrical personnel.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

To submit the long time over current protection settings, set the command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F3F

8000

INT16U

51593

Requested command code

0x1F40

8001

INT16U

26

Number of parameters of the command

0x1F41

8002

INT16U

4609 (0x1201)

Destination of the command

0x1F42

8003

INT16U

0

Security type of the command

0x1F43-0x1F44

8004-8005

OCTET STRING

0

Password of the command = 0 (no password required)

0x1F45-0x1F46

8006-8007

INT32U

0–4294967294

Requested session key for the command

0x1F47

8008

INT16U

MSB: 0

LSB: Requested setting group = 1 (Setting group A)

0x1F48

8009

0xFFFF

Reserved

0x1F49– 0x1F4A

8010–8011

A

FLOAT32

Long time over current protection threshold (step 0.1 A)

0x1F4B–0x1F4C

8012–8013

s

FLOAT32

0.5-24.0 (step 0.5)

Long time over current protection time delay

Submit Short Time Over Current Protection Settings

To get the short time over current protection settings, use the get short time over current protection settings command.

WARNING
HAZARD OF NUISANCE TRIPPING OR FAILURE TO TRIP
Protection setting adjustments must be done only by qualified electrical personnel.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

To submit the short time over current protection settings, set the command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F3F

8000

INT16U

51594

Requested command code

0x1F40

8001

INT16U

26

Number of parameters of the command

0x1F41

8002

INT16U

4609 (0x1201)

Destination of the command

0x1F42

8003

INT16U

0

Security type of the command

0x1F43-0x1F44

8004-8005

OCTET STRING

0

Password of the command = 0 (no password required)

0x1F45-0x1F46

8006-8007

INT32U

0–4294967294

Requested session key for the command

0x1F47

8008

INT16U

MSB: 0

LSB: Requested setting group = 1 (Setting group A)

0x1F48

8009

INT16U

MSB: 0

LSB: Short time over current protection curve

  • 0 = Definite time (I2t = Off)

  • 1 = Inverse time (I2t = On)

0x1F49– 0x1F4A

8010–8011

FLOAT32

1.5–10.0 (step 0.1)

Short time over current protection threshold coefficient

0x1F4B–0x1F4C

8012–8013

s

FLOAT32

0–0.4
(step 0.1)

Short time over current protection time delay

Submit Instantaneous Protection Settings

To get the instantaneous protection, use the get instantaneous protection settings command.

WARNING
HAZARD OF NUISANCE TRIPPING OR FAILURE TO TRIP
Protection setting adjustments must be done only by qualified electrical personnel.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

To submit the instantaneous protection settings, set the command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F3F

8000

INT16U

51595

Requested command code

0x1F40

8001

INT16U

22

Number of parameters of the command

0x1F41

8002

INT16U

4609 (0x1201)

Destination of the command

0x1F42

8003

INT16U

0

Security type of the command

0x1F43-0x1F44

8004-8005

OCTET STRING

0

Password of the command = 0 (no password required)

0x1F45-0x1F46

8006-8007

INT32U

0–4294967294

Requested session key for the command

0x1F47

8008

INT16U

MSB: Instantaneous over current protection mode

  • 0 = Off

  • 1 = On

LSB: Requested setting group = 1 (Setting group A)

0x1F48–0x1F49

8009–8010

 

FLOAT32

(1)

Instantaneous over current protection threshold coefficient

0x1F4A

8011

 

INT16U

 

MSB: 0

LSB: Instantaneous over current protection time delay mode = 0 (Standard)

(1) Ii setting range:

  • for MicroLogic Active 2.0: 1.5 to 10.0 (step 0.1)

  • for MicroLogic Active 5.0 and 6.0: 2.0 to 15.0 (step 0.1)

Submit Ground Fault Protection Settings

To get the ground fault protection settings, use the get ground fault protection settings command.

WARNING
HAZARD OF NUISANCE TRIPPING OR FAILURE TO TRIP
Protection setting adjustments must be done only by qualified electrical personnel.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

To submit the ground fault protection settings, set the command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F3F

8000

INT16U

51596

Requested command code

0x1F40

8001

INT16U

26

Number of parameters of the command

0x1F41

8002

INT16U

4609 (0x1201)

Destination of the command

0x1F42

8003

INT16U

0

Security type of the command

0x1F43-0x1F44

8004–8005

OCTET STRING

0

Password of the command = 0 (no password required)

0x1F45-0x1F46

8006–8007

INT32U

0–4294967294

Requested session key for the command

0x1F47

8008

INT16U

MSB: Ground fault protection mode(1)

  • 0 = Off (protection disabled)

  • 1 = On (protection enabled)

LSB: Requested setting group = 1 (Setting group A)

0x1F48

8009

INT16U

MSB: 0

LSB: Short time over current protection curve

  • 0 = Definite time (I2t = Off)

  • 1 = Inverse time (I2t = On)

0x1F49–0x1F4A

8010–8011

A

FLOAT32

Ground fault protection threshold (step 10 A)

0x1F4B–0x1F4C

8012–8013

s

FLOAT32

0–0.4
(step 0.1)

Ground fault protection time delay

(1) If the ground fault protection mode is set to Off, the result of the command will be 0x10, Input argument is out of range.

Submit Neutral Protection Settings

To get the neutral protection settings, use the get neutral protection settings command.

WARNING
HAZARD OF NUISANCE TRIPPING OR FAILURE TO TRIP
Protection setting adjustments must be done only by qualified electrical personnel.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

To submit the neutral protection settings, set the command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F3F

8000

INT16U

51598

Requested command code

0x1F40

8001

INT16U

16

Number of parameters of the command

0x1F41

8002

INT16U

4609 (0x1201)

Destination of the command

0x1F42

8003

INT16U

0

Security type of the command

0x1F43-0x1F44

8004–8005

OCTET STRING

0

Password of the command = 0 (no password required)

0x1F45-0x1F46

8006–8007

INT32U

0–4294967294

Requested session key for the command

0x1F47

8008

INT16U

0-3

Neutral protection type:

  • 0 = Off

  • 1 = 0.5

  • 2 = 1.0

  • 3 = Oversized