Protection Submit Commands
List of Commands
The following table lists the protection submit commands, their corresponding command codes, and user profiles:
|
Command |
Command code |
User profile |
|---|---|---|
|
51593 |
No password required |
|
|
51594 |
No password required |
|
|
51595 |
No password required |
|
|
51596 |
No password required |
|
|
51598 |
No password required |
Submit Long Time Over Current Protection Settings
To get the long time over current protection settings, use the get long time over current protection setting command.
WARNING |
|---|
|
HAZARD OF NUISANCE TRIPPING OR FAILURE TO TRIP
Protection setting adjustments must be done only by qualified
electrical personnel.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
|
To submit the long time over current protection settings, set the command registers in the following way:
|
Address |
Register |
Unit |
Type |
Range |
Description |
|---|---|---|---|---|---|
|
0x1F3F |
8000 |
– |
INT16U |
51593 |
Requested command code |
|
0x1F40 |
8001 |
– |
INT16U |
26 |
Number of parameters of the command |
|
0x1F41 |
8002 |
– |
INT16U |
4609 (0x1201) |
Destination of the command |
|
0x1F42 |
8003 |
– |
INT16U |
0 |
Security type of the command |
|
0x1F43-0x1F44 |
8004-8005 |
– |
OCTET STRING |
0 |
Password of the command = 0 (no password required) |
|
0x1F45-0x1F46 |
8006-8007 |
– |
INT32U |
0–4294967294 |
Requested session key for the command |
|
0x1F47 |
8008 |
– |
INT16U |
– |
MSB: 0 LSB: Requested setting group = 1 (Setting group A) |
|
0x1F48 |
8009 |
– |
– |
0xFFFF |
Reserved |
|
0x1F49– 0x1F4A |
8010–8011 |
A |
FLOAT32 |
– |
Long time over current protection threshold (step 0.1 A) |
|
0x1F4B–0x1F4C |
8012–8013 |
s |
FLOAT32 |
0.5-24.0 (step 0.5) |
Long time over current protection time delay |
Submit Short Time Over Current Protection Settings
To get the short time over current protection settings, use the get short time over current protection settings command.
WARNING |
|---|
|
HAZARD OF NUISANCE TRIPPING OR FAILURE TO TRIP
Protection setting adjustments must be done only by qualified
electrical personnel.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
|
To submit the short time over current protection settings, set the command registers in the following way:
|
Address |
Register |
Unit |
Type |
Range |
Description |
|---|---|---|---|---|---|
|
0x1F3F |
8000 |
– |
INT16U |
51594 |
Requested command code |
|
0x1F40 |
8001 |
– |
INT16U |
26 |
Number of parameters of the command |
|
0x1F41 |
8002 |
– |
INT16U |
4609 (0x1201) |
Destination of the command |
|
0x1F42 |
8003 |
– |
INT16U |
0 |
Security type of the command |
|
0x1F43-0x1F44 |
8004-8005 |
– |
OCTET STRING |
0 |
Password of the command = 0 (no password required) |
|
0x1F45-0x1F46 |
8006-8007 |
– |
INT32U |
0–4294967294 |
Requested session key for the command |
|
0x1F47 |
8008 |
– |
INT16U |
– |
MSB: 0 LSB: Requested setting group = 1 (Setting group A) |
|
0x1F48 |
8009 |
– |
INT16U |
– |
MSB: 0 LSB: Short time over current protection curve
|
|
0x1F49– 0x1F4A |
8010–8011 |
– |
FLOAT32 |
1.5–10.0 (step 0.1) |
Short time over current protection threshold coefficient |
|
0x1F4B–0x1F4C |
8012–8013 |
s |
FLOAT32 |
0–0.4 |
Short time over current protection time delay |
Submit Instantaneous Protection Settings
To get the instantaneous protection, use the get instantaneous protection settings command.
WARNING |
|---|
|
HAZARD OF NUISANCE TRIPPING OR FAILURE TO TRIP
Protection setting adjustments must be done only by qualified
electrical personnel.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
|
To submit the instantaneous protection settings, set the command registers in the following way:
|
Address |
Register |
Unit |
Type |
Range |
Description |
|---|---|---|---|---|---|
|
0x1F3F |
8000 |
– |
INT16U |
51595 |
Requested command code |
|
0x1F40 |
8001 |
– |
INT16U |
22 |
Number of parameters of the command |
|
0x1F41 |
8002 |
– |
INT16U |
4609 (0x1201) |
Destination of the command |
|
0x1F42 |
8003 |
– |
INT16U |
0 |
Security type of the command |
|
0x1F43-0x1F44 |
8004-8005 |
– |
OCTET STRING |
0 |
Password of the command = 0 (no password required) |
|
0x1F45-0x1F46 |
8006-8007 |
– |
INT32U |
0–4294967294 |
Requested session key for the command |
|
0x1F47 |
8008 |
– |
INT16U |
– |
MSB: Instantaneous over current protection mode
LSB: Requested setting group = 1 (Setting group A) |
|
0x1F48–0x1F49 |
8009–8010 |
FLOAT32 |
(1) |
Instantaneous over current protection threshold coefficient |
|
|
0x1F4A |
8011 |
INT16U |
MSB: 0 LSB: Instantaneous over current protection time delay mode = 0 (Standard) |
||
|
(1) Ii setting range:
|
|||||
Submit Ground Fault Protection Settings
To get the ground fault protection settings, use the get ground fault protection settings command.
WARNING |
|---|
|
HAZARD OF NUISANCE TRIPPING OR FAILURE TO TRIP
Protection setting adjustments must be done only by qualified
electrical personnel.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
|
To submit the ground fault protection settings, set the command registers in the following way:
|
Address |
Register |
Unit |
Type |
Range |
Description |
|---|---|---|---|---|---|
|
0x1F3F |
8000 |
– |
INT16U |
51596 |
Requested command code |
|
0x1F40 |
8001 |
– |
INT16U |
26 |
Number of parameters of the command |
|
0x1F41 |
8002 |
– |
INT16U |
4609 (0x1201) |
Destination of the command |
|
0x1F42 |
8003 |
– |
INT16U |
0 |
Security type of the command |
|
0x1F43-0x1F44 |
8004–8005 |
– |
OCTET STRING |
0 |
Password of the command = 0 (no password required) |
|
0x1F45-0x1F46 |
8006–8007 |
– |
INT32U |
0–4294967294 |
Requested session key for the command |
|
0x1F47 |
8008 |
– |
INT16U |
– |
MSB: Ground fault protection mode(1)
LSB: Requested setting group = 1 (Setting group A) |
|
0x1F48 |
8009 |
– |
INT16U |
– |
MSB: 0 LSB: Short time over current protection curve
|
|
0x1F49–0x1F4A |
8010–8011 |
A |
FLOAT32 |
– |
Ground fault protection threshold (step 10 A) |
|
0x1F4B–0x1F4C |
8012–8013 |
s |
FLOAT32 |
0–0.4 |
Ground fault protection time delay |
|
(1) If the ground fault protection mode is set to Off, the result of the command will be 0x10, Input argument is out of range. |
|||||
Submit Neutral Protection Settings
To get the neutral protection settings, use the get neutral protection settings command.
WARNING |
|---|
|
HAZARD OF NUISANCE TRIPPING OR FAILURE TO TRIP
Protection setting adjustments must be done only by qualified
electrical personnel.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
|
To submit the neutral protection settings, set the command registers in the following way:
|
Address |
Register |
Unit |
Type |
Range |
Description |
|---|---|---|---|---|---|
|
0x1F3F |
8000 |
– |
INT16U |
51598 |
Requested command code |
|
0x1F40 |
8001 |
– |
INT16U |
16 |
Number of parameters of the command |
|
0x1F41 |
8002 |
– |
INT16U |
4609 (0x1201) |
Destination of the command |
|
0x1F42 |
8003 |
– |
INT16U |
0 |
Security type of the command |
|
0x1F43-0x1F44 |
8004–8005 |
– |
OCTET STRING |
0 |
Password of the command = 0 (no password required) |
|
0x1F45-0x1F46 |
8006–8007 |
– |
INT32U |
0–4294967294 |
Requested session key for the command |
|
0x1F47 |
8008 |
– |
INT16U |
0-3 |
Neutral protection type:
|
WARNING