Standard Dataset Common Registers
Circuit Breaker Status Register
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Bit |
Description |
|---|---|---|---|---|---|---|---|---|---|---|---|
|
0x7CFF |
32000 |
R |
– |
INT16U |
– |
A/E |
A/E/P/H |
A/E |
X |
– |
Quality of each bit of register 32001:
|
|
0x7D00 |
32001 |
R |
– |
INT16U |
– |
A/E |
A/E/P/H |
A/E |
X |
– |
Circuit breaker status register |
|
A/E |
A/E/P/H |
A/E |
X |
0 |
OF status indication contact
|
||||||
|
A/E |
A/E/P/H |
A/E |
X |
1 |
SD trip indication contact
Bit always equal to 0 for MasterPacT, ComPacT NS and PowerPacT P- and R-frame circuit breakers with motor mechanism. |
||||||
|
A/E |
A/E/P/H |
A/E |
X |
2 |
SDE fault trip indication contact
|
||||||
|
– |
A/E/P/H |
A/E |
X |
3 |
CH spring charged contact (only with MasterPacT)
Bit always equal to 0 for ComPacT NS and PowerPacT P- and R-frame circuit breakers with motor mechanism. |
||||||
|
– |
– |
– |
– |
4 |
Reserved |
||||||
|
– |
A/E/P/H |
A/E |
X |
5 |
PF ready to close contact (only with MasterPacT)
Bit always equal to 0 for ComPacT NS and PowerPacT P- and R-frame circuit breakers with motor mechanism. |
||||||
|
– |
– |
– |
– |
6–14 |
Reserved |
||||||
|
A/E |
A/E/P/H |
A/E |
– |
15 |
Data availability If this bit is set at 1, all other bits of the register are not significant. |
IO Status Registers
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Bit |
Description |
|---|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D01 |
32002 |
R |
– |
INT16U |
– |
A/E |
A/E/P/H |
– |
X |
– |
Quality of each bit of register 32003:
|
|
0x7D02 |
32003 |
R |
– |
INT16U |
– |
A/E |
A/E/P/H |
– |
X |
– |
IO1 module and M2C status |
|
A/E |
A/E/P/H |
– |
X |
0 |
Digital input 1 status:
|
||||||
|
A/E |
A/E/P/H |
– |
X |
1 |
Digital input 2 status:
|
||||||
|
A/E |
A/E/P/H |
– |
X |
2 |
Digital input 3 status:
|
||||||
|
A/E |
A/E/P/H |
– |
X |
3 |
Digital input 4 status:
|
||||||
|
A/E |
A/E/P/H |
– |
X |
4 |
Digital input 5 status:
|
||||||
|
A/E |
A/E/P/H |
– |
X |
5 |
Digital input 6 status:
|
||||||
|
A/E |
A/E/P/H |
– |
X |
6 |
Digital output 1 status:
|
||||||
|
A/E |
A/E/P/H |
– |
X |
7 |
Digital output 2 status:
|
||||||
|
A/E |
A/E/P/H |
– |
X |
8 |
Digital output 3 status:
|
||||||
|
– |
– |
– |
X |
9 |
Digital M2C output 1 status:
|
||||||
|
– |
– |
– |
X |
10 |
Digital M2C output 2 status:
|
||||||
|
– |
– |
– |
– |
11–14 |
Reserved |
||||||
|
A/E |
A/E/P/H |
– |
– |
15 |
Data availability If this bit is set at 1, all other bits of the register are not significant. |
||||||
|
0x7D03 |
32004 |
R |
– |
INT16U |
– |
A/E |
A/E/P/H |
– |
X |
– |
Quality of each bit of register 32005:
|
|
0x7D04 |
32005 |
R |
– |
INT16U |
– |
A/E |
A/E/P/H |
– |
X |
– |
IO2 module status |
|
0 |
Digital input 1 status:
|
||||||||||
|
1 |
Digital input 2 status:
|
||||||||||
|
2 |
Digital input 3 status:
|
||||||||||
|
3 |
Digital input 4 status:
|
||||||||||
|
4 |
Digital input 5 status:
|
||||||||||
|
5 |
Digital input 6 status:
|
||||||||||
|
6 |
Digital output 1 status:
|
||||||||||
|
7 |
Digital output 2 status:
|
||||||||||
|
8 |
Digital output 3 status:
|
||||||||||
|
– |
– |
– |
– |
9–14 |
Reserved |
||||||
|
A/E |
A/E/P/H |
– |
– |
15 |
Data availability If this bit is set at 1, all other bits of the register are not significant. |
Tripping Cause
The tripping cause register provides information about the cause of the trip for the standard protection functions. When a tripping cause bit is at 1 in the tripping cause register, it indicates that a trip has occurred and has not been reset.
-
For MicroLogic trip units for ComPacT NSX and PowerPacT H-, J-, and L-frame circuit breakers, the tripping cause bit is reset by pressing the OK key (on the keypad of the MicroLogic trip unit) twice (once for validation, once for confirmation).
-
For MicroLogic A/E/P/H trip units for MasterPacT NT/NW, ComPacT NS and PowerPacT P- and R-frame circuit breakers, the tripping cause bit is reset as soon as the circuit breaker is closed again.
-
For MicroLogic X control units for MasterPacT MTZ circuit breakers, the tripping cause bit is reset by pressing the test/reset button (located beside the trip cause LEDs on the MicroLogic X control unit). Press and hold the button for 3 to 15 seconds to reset all the trip causes.
-
For MicroLogic Active control units for MasterPacT MTZ circuit breakers, the tripping cause bit is reset by pressing the
button located on the front face of the MicroLogic Active control unit. Press and hold the
button for more than 3 seconds to reset all the trip causes.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Bit |
Description |
|---|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D05 |
32006 |
R |
– |
INT16U |
– |
A/E |
A/E/P/H |
A/E |
– |
– |
Quality of each bit of register 32007:
|
|
0x7D06 |
32007 |
R |
– |
INT16U |
– |
A/E |
A/E/P/H |
A/E |
X |
Tripping cause for the standard protection functions |
|
|
A/E |
A/E/P/H |
A/E |
X |
0 |
Long-time protection Ir |
||||||
|
A/E |
A/E/P/H |
A/E |
X |
1 |
Short-time protection Isd |
||||||
|
A/E |
A/E/P/H |
A/E |
X |
2 |
Instantaneous protection Ii |
||||||
|
A/E |
A/E/P/H |
A/E |
X |
3 |
Ground-fault protection Ig |
||||||
|
E |
A/P/H |
A/P/H |
X |
4 |
Earth-leakage protection IΔn |
||||||
|
A/E |
A/E/P/H |
A/E |
X |
5 |
Integrated instantaneous protection (SELLIM and DIN/DINF) |
||||||
|
A/E |
– |
– |
X |
6 |
Internal failure (STOP) |
||||||
|
– |
A/E |
A/E |
– |
Other protections |
|||||||
|
– |
P/H |
E |
– |
Internal failure (temperature) |
|||||||
|
– |
A/E/P/H |
A/E |
– |
7 |
Internal failure (overvoltage) |
||||||
|
– |
P/H |
E |
X |
8 |
Other protection (see register 32009) |
||||||
|
– |
– |
– |
– |
9 |
Reserved |
||||||
|
E |
– |
– |
– |
10 |
Unbalance motor protection |
||||||
|
E |
– |
– |
– |
11 |
Jam motor protection |
||||||
|
E |
– |
– |
– |
12 |
Underload motor protection |
||||||
|
E |
– |
– |
– |
13 |
Long-start motor protection |
||||||
|
A/E |
– |
– |
– |
14 |
Reflex tripping protection |
||||||
|
A/E |
A/E/P/H |
A/E |
– |
15 |
If this bit is at 1, bits 0 to 14 are not valid. |
||||||
|
0x7D07 |
32008 |
R |
– |
INT16U |
– |
– |
P/H |
E |
– |
Quality of each bit of register 32009:
|
|
|
0x7D08 |
32009 |
R |
– |
INT16U |
– |
– |
P/H |
E |
– |
– |
Tripping causes for the advanced protection functions |
|
– |
P/H |
– |
– |
0 |
Current unbalance |
||||||
|
– |
P/H |
– |
– |
1 |
Overcurrent on phase 1 |
||||||
|
– |
P/H |
– |
– |
2 |
Overcurrent on phase 2 |
||||||
|
– |
P/H |
– |
– |
3 |
Overcurrent on phase 3 |
||||||
|
– |
P/H |
– |
– |
4 |
Overcurrent on Neutral |
||||||
|
– |
P/H |
E |
X |
5 |
Undervoltage |
||||||
|
– |
P/H |
E |
X |
6 |
Overvoltage |
||||||
|
– |
P/H |
– |
– |
7 |
Voltage unbalance |
||||||
|
– |
P/H |
– |
– |
8 |
Overpower |
||||||
|
– |
P/H |
– |
X |
9 |
Reverse power |
||||||
|
– |
P/H |
– |
X |
10 |
Underfrequency |
||||||
|
– |
P/H |
– |
X |
11 |
Overfrequency |
||||||
|
– |
P/H |
– |
– |
12 |
Phase rotation |
||||||
|
– |
P/H |
– |
– |
13 |
Load shedding based on current |
||||||
|
– |
P/H |
– |
– |
14 |
Load shedding based on power |
||||||
|
– |
P/H |
E |
– |
15 |
If this bit is at 1, bits 0 to 14 are not valid. |
||||||
|
0x7D09–0x7D0C |
32010–32013 |
– |
– |
– |
– |
– |
– |
– |
– |
– |
Reserved |
Overrun of the Protection Setpoints
The alarm setpoint registers provide information about overrun of the standard and advanced protection setpoints. A bit is at 1 once a setpoint overrun has occurred, even if the time delay has not expired.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Bit |
Description |
|---|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D0D |
32014 |
R |
– |
INT16U |
– |
A/E |
P/H |
E |
– |
– |
Quality of each bit of register 32015:
|
|
0x7D0E |
32015 |
R |
– |
INT16U |
– |
A/E |
P/H |
E |
– |
– |
Overrun of the standard protection setpoints |
|
A/E |
P/H |
E |
– |
0 |
Long-time protection pick-up |
||||||
|
– |
– |
– |
– |
1–14 |
Reserved |
||||||
|
A/E |
P/H |
E |
– |
15 |
If this bit is at 1, bits 0 to 14 are not valid. |
||||||
|
0x7D0F |
32016 |
R |
– |
INT16U |
– |
A/E |
P/H |
E |
– |
– |
Quality of each bit of register 32017:
|
|
0x7D10 |
32017 |
R |
– |
INT16U |
– |
A/E |
P/H |
E |
– |
– |
Overrun of the advanced protection setpoints |
|
– |
P/H |
E |
– |
0 |
Current unbalance |
||||||
|
– |
P/H |
E |
– |
1 |
Maximum current on phase 1 |
||||||
|
– |
P/H |
E |
– |
2 |
Maximum current on phase 2 |
||||||
|
– |
P/H |
E |
– |
3 |
Maximum current on phase 3 |
||||||
|
– |
P/H |
E |
– |
4 |
Maximum current on the neutral |
||||||
|
– |
P/H |
E |
– |
5 |
Minimum voltage |
||||||
|
– |
P/H |
E |
– |
6 |
Maximum voltage |
||||||
|
– |
P/H |
– |
– |
7 |
Voltage unbalance |
||||||
|
– |
P/H |
– |
– |
8 |
Maximum power |
||||||
|
– |
P/H |
– |
– |
9 |
Reverse power |
||||||
|
– |
P/H |
– |
– |
10 |
Minimum frequency |
||||||
|
– |
P/H |
– |
– |
11 |
Maximum frequency |
||||||
|
– |
P/H |
– |
– |
12 |
Phase rotation |
||||||
|
– |
P/H |
– |
– |
13 |
Load shedding based on the current |
||||||
|
– |
P/H |
– |
– |
14 |
Load shedding based on the power |
||||||
|
– |
P/H |
E |
– |
15 |
If this bit is at 1, bits 0 to 14 are not valid. |
||||||
|
0x7D11 |
32018 |
R |
– |
INT16U |
– |
– |
P/H |
– |
– |
– |
Quality of each bit of register 32019:
|
|
0x7D12 |
32019 |
R |
– |
INT16U |
– |
– |
P/H |
– |
– |
– |
Advanced protection settings extended |
|
– |
P/H |
– |
– |
0 |
Ground-fault alarm |
||||||
|
E |
P/H |
– |
– |
1 |
Earth-leakage alarm |
||||||
|
– |
– |
– |
– |
2–14 |
Reserved |
||||||
|
– |
P/H |
E |
– |
15 |
If this bit is at 1, bits 0 to 14 are not valid. |
Alarms
The alarm register provides information about the pre-alarms and the user-defined alarms. A bit is set to 1 once an alarm is active.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Bit |
Description |
|---|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D13 |
32020 |
R |
– |
INT16U |
– |
A/E |
– |
– |
– |
– |
Quality of each bit of register 32021:
|
|
0x7D14 |
32021 |
R |
– |
INT16U |
– |
A/E |
– |
– |
– |
– |
Pre-alarm extended register |
|
A/E |
– |
– |
X |
0 |
Long-time protection time pre-alarm (PAL Ir) |
||||||
|
E |
– |
– |
– |
1 |
Earth-leakage protection pre-alarm (PAL IΔn) |
||||||
|
– |
– |
– |
X |
Earth-leakage alarm(1) |
|||||||
|
A/E |
– |
– |
– |
2 |
Ground-fault protection pre-alarm (PAL Ig) |
||||||
|
– |
– |
– |
X |
Ground-fault alarm(2) |
|||||||
|
– |
– |
– |
– |
3–14 |
Reserved |
||||||
|
A/E |
– |
– |
– |
15 |
If this bit is at 1, bits 0 to 14 are not valid. |
||||||
|
0x7D15 |
32022 |
R |
– |
INT16U |
– |
A/E |
– |
– |
– |
– |
Quality of each bit of register 32023:
|
|
0x7D16 |
32023 |
R |
– |
INT16U |
– |
A/E |
– |
– |
– |
– |
Register of user-defined alarms |
|
A/E |
– |
– |
– |
0 |
User-defined alarm 201 |
||||||
|
A/E |
– |
– |
– |
1 |
User-defined alarm 202 |
||||||
|
A/E |
– |
– |
– |
2 |
User-defined alarm 203 |
||||||
|
A/E |
– |
– |
– |
3 |
User-defined alarm 204 |
||||||
|
A/E |
– |
– |
– |
4 |
User-defined alarm 205 |
||||||
|
A/E |
– |
– |
– |
5 |
User-defined alarm 206 |
||||||
|
A/E |
– |
– |
– |
6 |
User-defined alarm 207 |
||||||
|
A/E |
– |
– |
– |
7 |
User-defined alarm 208 |
||||||
|
A/E |
– |
– |
– |
8 |
User-defined alarm 209 |
||||||
|
A/E |
– |
– |
– |
9 |
User-defined alarm 210 |
||||||
|
– |
– |
– |
– |
10–14 |
Reserved |
||||||
|
A/E |
– |
– |
– |
15 |
If this bit is at 1, bits 0 to 14 are not valid. |
||||||
|
0x7D17–0x7D1A |
32024–32027 |
– |
– |
– |
– |
– |
– |
– |
– |
– |
Reserved |
|
(1) Value available on MicroLogic 7.0 X control unit only when the Digital Module ANSI 51N/51G Ground-fault alarm is installed. (2) Value available on MicroLogic 2.0 X, 3.0 X, 5.0 X, and 6.0 X control units only when the Digital Module ANSI 51N/51G Ground-fault alarm is installed. |
|||||||||||
Current
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D1B–0x7D1C |
32028–32029 |
R |
A |
FLOAT32 |
– |
A/E |
A/E/P/H |
A/E |
X |
RMS current on phase 1 |
|
0x7D1D–0x7D1E |
32030–32031 |
R |
A |
FLOAT32 |
– |
A/E |
A/E/P/H |
A/E |
X |
RMS current on phase 2 |
|
0x7D1F–0x7D20 |
32032–32033 |
R |
A |
FLOAT32 |
– |
A/E |
A/E/P/H |
A/E |
X |
RMS current on phase 3 |
|
0x7D21–0x7D22 |
32034–32035 |
R |
A |
FLOAT32 |
– |
A/E |
A/E/P/H |
A/E |
X |
RMS current on the neutral(1) |
|
0x7D23–0x7D24 |
32036–32037 |
R |
A |
FLOAT32 |
– |
A/E |
A/E/P/H |
A/E |
X |
Maximum of RMS current of phases 1, 2, 3 and N (most loaded phase) (3) |
|
0x7D25–0x7D26 |
32038–32039 |
R |
– |
FLOAT32 |
– |
A/E |
A/E/P/H |
A/E |
X |
Current ratio on ground (Ig setting ratio) |
|
0x7D27–0x7D28 |
32040–32041 |
R |
– |
FLOAT32 |
– |
E |
A/P/H |
– |
X |
Current ratio on earth-leakage (IΔn setting ratio) (2) |
|
(1) Value available when system type register returns 30 or 41. (2) Value available with MicroLogic 7.0. (3) Value reset with the reset minimum/maximum command. |
||||||||||
Maximum Current Values
Maximum current values can be reset with the reset minimum/maximum command.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D29–0x7D2A |
32042–32043 |
R |
A |
FLOAT32 |
– |
A/E |
A/E/P/H |
A/E |
X |
Maximum RMS current on phase 1 |
|
0x7D2B–0x7D2C |
32044–32045 |
R |
A |
FLOAT32 |
– |
A/E |
A/E/P/H |
A/E |
X |
Maximum RMS current on phase 2 |
|
0x7D2D–0x7D2E |
32046–32047 |
R |
A |
FLOAT32 |
– |
A/E |
A/E/P/H |
A/E |
X |
Maximum RMS current on phase 3 |
|
0x7D2F–0x7D30 |
32048–32049 |
R |
A |
FLOAT32 |
– |
A/E |
A/E/P/H |
A/E |
X |
Maximum RMS current on the neutral(1) |
|
0x7D31–0x7D32 |
32050–32051 |
R |
A |
FLOAT32 |
– |
A/E |
A/E/P/H |
A/E |
X |
This is the highest (i.e. maximum) maximum current value since this measurement was last reset. The measurement looks at all 3 currents, MaxI1, MaxI2, MaxI3 and MaxIN and keeps track of the highest value of any of them over time. |
|
0x7D33–0x7D36 |
32052–32055 |
– |
– |
– |
– |
– |
– |
– |
– |
Reserved |
|
(1) Value available when system type register returns 30 or 41. |
||||||||||
Voltage
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D37–0x7D38 |
32056–32057 |
R |
V |
FLOAT32 |
41.6–2250 |
E |
E/P/H |
E |
X |
RMS phase-to-phase voltage V12 |
|
0x7D39–0x7D3A |
32058–32059 |
R |
V |
FLOAT32 |
41.6–2250 |
E |
E/P/H |
E |
X |
RMS phase-to-phase voltage V23 |
|
0x7D3B–0x7D3C |
32060–32061 |
R |
V |
FLOAT32 |
41.6–2250 |
E |
E/P/H |
E |
X |
RMS phase-to-phase voltage V31 |
|
0x7D3D–0x7D3E |
32062–32063 |
R |
V |
FLOAT32 |
24-1500 |
E |
E/P/H |
E |
X |
RMS phase-to-neutral voltage V1N(1) |
|
0x7D3F–0x7D40 |
32064–32065 |
R |
V |
FLOAT32 |
24-1500 |
E |
E/P/H |
E |
X |
RMS phase-to-neutral voltage V2N(1) |
|
0x7D41–0x7D42 |
32066–32067 |
R |
V |
FLOAT32 |
24-1500 |
E |
E/P/H |
E |
X |
RMS phase-to-neutral voltage V3N(1) |
|
(1) Value available when system type register returns 40 or 41. |
||||||||||
Frequency
When the MicroLogic trip unit cannot calculate the frequency, it returns Not applicable = 0xFFC00000.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D43–0x7D44 |
32068–32069 |
R |
Hz |
FLOAT32 |
40.0–70.0 |
E |
P/H |
E |
X |
Frequency |
|
0x7D45–0x7D46 |
32070–32071 |
R |
Hz |
FLOAT32 |
40.0–70.0 |
E |
P/H |
E |
X |
Maximum frequency (1) |
|
(1) This value can be reset with the reset minimum/maximum command. |
||||||||||
Power
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D47–0x7D48 |
32072–32073 |
R |
W |
FLOAT32 |
-16000000–16000000 |
E |
E/P/H |
E |
X |
Active power on phase 1(1) (2) |
|
0x7D49–0x7D4A |
32074–32075 |
R |
W |
FLOAT32 |
-16000000–16000000 |
E |
E/P/H |
E |
X |
Active power on phase 2(1) (2) |
|
0x7D4B–0x7D4C |
32076–32077 |
R |
W |
FLOAT32 |
-16000000–16000000 |
E |
E/P/H |
E |
X |
Active power on phase 3 (1) (2) |
|
0x7D4D–0x7D4E |
32078–32079 |
R |
W |
FLOAT32 |
-16000000–16000000 |
E |
E/P/H |
E |
X |
Total active power(2) |
|
0x7D4F–0x7D50 |
32080–32081 |
R |
var |
FLOAT32 |
-16000000–16000000 |
E |
E/P/H |
E |
X |
Reactive power on phase 1(1) (2) |
|
0x7D51–0x7D52 |
32082–32083 |
R |
var |
FLOAT32 |
-16000000–16000000 |
E |
E/P/H |
E |
X |
Reactive power on phase 2(1) (2) |
|
0x7D53–0x7D54 |
32084–32085 |
R |
var |
FLOAT32 |
-16000000–16000000 |
E |
E/P/H |
E |
X |
Reactive power on phase 3(1) (2) |
|
0x7D55–0x7D56 |
32086–32087 |
R |
var |
FLOAT32 |
-16000000–16000000 |
E |
E/P/H |
E |
X |
Total reactive power(2) |
|
0x7D57–0x7D58 |
32088–32089 |
R |
VA |
FLOAT32 |
0–16000000 |
E |
E/P/H |
E |
X |
Apparent power on phase 1(1) |
|
0x7D59–0x7D5A |
32090–32091 |
R |
VA |
FLOAT32 |
0–16000000 |
E |
E/P/H |
E |
X |
Apparent power on phase 2(1) |
|
0x7D5B–0x7D5C |
32092–32093 |
R |
VA |
FLOAT32 |
0–16000000 |
E |
E/P/H |
E |
X |
Apparent power on phase 3(1) |
|
0x7D5D–0x7D5E |
32094–32095 |
R |
VA |
FLOAT32 |
0–16000000 |
E |
E/P/H |
E |
X |
Total apparent power |
|
(1) Value available when system type register returns 40 or 41. (2) The sign for the active and reactive power depends on the configuration of:
|
||||||||||
Energy
Energy is stored in big-endian format: the most significant register is transmitted first.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D5F–0x7D62 |
32096–32099 |
R |
Wh |
INT64 |
– |
E |
E/P/H |
E |
X |
Total active energy(2) |
|
0x7D63–0x7D66 |
32100–32103 |
R |
varh |
INT64 |
– |
E |
E/P/H(1) |
E(1) |
X |
Total reactive energy(2) |
|
0x7D67–0x7D6A |
32104–32107 |
R |
Wh |
INT64U |
– |
E |
P/H |
E |
X |
Total active energy delivered (into the load, counted positively)(2) |
|
0x7D6B–0x7D6E |
32108–32111 |
R |
Wh |
INT64U |
– |
E |
P/H |
E |
X |
Total active energy received (out of the load, counted negatively)(2) |
|
0x7D6F–0x7D72 |
32112–32115 |
R |
varh |
INT64U |
– |
E |
P/H |
E |
X |
Total reactive energy delivered (into the load, counted positively)(2) |
|
0x7D73–0x7D76 |
32116–32119 |
R |
varh |
INT64U |
– |
E |
P/H |
E |
X |
Total reactive energy received (out of the load, counted negatively)(2) |
|
0x7D77–0x7D7A |
32120–32123 |
R |
VAh |
INT64U |
– |
E |
– |
– |
X |
Total apparent energy(2) |
|
0x7D7B–0x7D7E |
32124–32127 |
R |
Wh |
INT64U |
– |
E |
– |
– |
X |
Total cumulative active energy delivered (into the load, counted positively, not resettable) |
|
0x7D7F–0x7D82 |
32128–32131 |
R |
Wh |
INT64U |
– |
E |
– |
– |
X |
Total cumulative active energy received (out of the load, counted negatively, not resettable) |
|
(1) This value is always positive with MasterPacT MicroLogic E trip unit. (2) Value reset with the reset energies command. |
||||||||||
Average Values
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D83–0x7D84 |
32132–32133 |
R |
A |
FLOAT32 |
– |
– |
– |
– |
X |
Average of 3-phase RMS currents |
|
0x7D85–0x7D86 |
32134–32135 |
R |
V |
FLOAT32 |
– |
– |
– |
– |
X |
Average of 3 RMS phase-to-phase voltages: (V12+V23+V31)/3 |
|
0x7D87–0x7D88 |
32136–32137 |
R |
V |
FLOAT32 |
– |
– |
– |
– |
X |
Average of 3 RMS phase-to-neutral voltages: (V1N+V2N+V3N)/3(1) |
|
(1) Value available when system type register returns 40 or 41. |
||||||||||
Maximum Power Values
Maximum power values can be reset with the reset minimum/maximum command.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D89–0x7D8A |
32138–32139 |
R |
W |
FLOAT32 |
– |
– |
– |
– |
X |
Maximum total active power |
|
0x7D8B–0x7D8C |
32140–32141 |
R |
var |
FLOAT32 |
– |
– |
– |
– |
X |
Maximum total reactive power |
|
0x7D8D–0x7D8E |
32142–32143 |
R |
VA |
FLOAT32 |
– |
– |
– |
– |
X |
Maximum total apparent power |
Maximum Average Values
Maximum average values can be reset with the reset minimum/maximum command.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D8F–0x7D90 |
32144–32145 |
R |
A |
FLOAT32 |
– |
– |
– |
– |
X |
Maximum of average of 3-phase RMS currents |
|
0x7D91–0x7D92 |
32146–32147 |
R |
V |
FLOAT32 |
– |
– |
– |
– |
X |
Maximum of average of 3 RMS phase-to-phase voltages |
|
0x7D93–0x7D94 |
32148–32149 |
R |
V |
FLOAT32 |
– |
– |
– |
– |
X |
Maximum of average of 3 RMS phase-to-neutral voltages |
Ground and Earth-Leakage Current
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D95–0x7D96 |
32150–32151 |
R |
A |
FLOAT32 |
– |
– |
– |
– |
X |
Ground-fault current |
|
0x7D97–0x7D98 |
32152–32153 |
R |
A |
FLOAT32 |
– |
– |
– |
– |
X |
Earth-leakage current(1) |
|
0x7D99–0x7D9A |
32154–32155 |
– |
– |
– |
– |
– |
– |
– |
– |
Reserved |
|
(1) Value available with MicroLogic 7 |
||||||||||
Current Demand Values
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7D9B–0x7D9C |
32156–32157 |
R |
A |
FLOAT32 |
– |
E |
E/P/H |
E |
X |
Current demand value on phase 1: I1 Dmd |
|
0x7D9D–0x7D9E |
32158–32159 |
R |
A |
FLOAT32 |
– |
E |
E/P/H |
E |
X |
Current demand value on phase 2: I2 Dmd |
|
0x7D9F–0x7DA0 |
32160–32161 |
R |
A |
FLOAT32 |
– |
E |
E/P/H |
E |
X |
Current demand value on phase 3: I3 Dmd |
|
0x7DA1–0x7DA2 |
32162–32163 |
R |
A |
FLOAT32 |
– |
E |
E/P/H |
E |
X |
Current demand value on the neutral: IN Dmd(1) |
|
(1) Value available when system type register returns 30 or 41. |
||||||||||
Power Demand Values
-
For the block window, the demand value is updated at the end of the window.
-
For the sliding window,
-
If window duration is configured for less or equal to 15 minutes, the demand value is updated every 15 seconds
-
If window duration is configured for more than 15 minutes, the demand value is updated every 1 minute.
-
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7DA3–0x7DA4 |
32164–32165 |
R |
W |
FLOAT32 |
– |
E |
E/P/H |
E |
X |
Total active power demand: P Dmd |
|
0x7DA5–0x7DA6 |
32166–32167 |
R |
var |
FLOAT32 |
– |
E |
P/H |
E |
X |
Total reactive power demand: Q Dmd |
|
0x7DA7–0x7DA8 |
32168–32169 |
R |
VA |
FLOAT32 |
– |
E |
P/H |
E |
X |
Total apparent power demand: S Dmd |
Current Peak Demand Values
Current peak demand values can be reset with the reset minimum/maximum command.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7DA9–0x7DAA |
32170–32171 |
R |
A |
FLOAT32 |
– |
– |
– |
– |
X |
Current peak demand value on phase 1: I1 dmd max |
|
0x7DAB–0x7DAC |
32172–32173 |
R |
A |
FLOAT32 |
– |
– |
– |
– |
X |
Current peak demand value on phase 2: I2 dmd max |
|
0x7DAD–0x7DAE |
32174–32175 |
R |
A |
FLOAT32 |
– |
– |
– |
– |
X |
Current peak demand value on phase 3: I3 dmd max |
|
0x7DAF–0x7DB0 |
32176–32177 |
R |
A |
FLOAT32 |
– |
– |
– |
– |
X |
Current peak demand value on the neutral: IN dmd max(1) |
|
(1) Value available when system type register returns 30 or 41. |
||||||||||
Power Peak Demand Values
Power peak demand values are updated every 15 seconds. Power peak demand values can be reset with the reset minimum/maximum command.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7DB1–0x7DB2 |
32178–32179 |
R |
W |
FLOAT32 |
– |
– |
– |
– |
X |
Total active power peak demand: P dmd max |
|
0x7DB3–0x7DB4 |
32180–32181 |
R |
var |
FLOAT32 |
– |
– |
– |
– |
X |
Total reactive power peak demand: Q dmd max |
|
0x7DB5–0x7DB6 |
32182–32183 |
R |
VA |
FLOAT32 |
– |
– |
– |
– |
X |
Total apparent power peak demand: S dmd max |
Maximum Ground and Earth-Leakage Current Values
Maximum ground and earth-leakage current values can be reset with the reset minimum/maximum command.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7DB7–0x7DB8 |
32184–32185 |
R |
A |
FLOAT32 |
– |
– |
– |
– |
X |
Maximum ground-fault current |
|
0x7DB9–0x7DBA |
32186–32187 |
R |
V |
FLOAT32 |
– |
E |
– |
– |
X |
Maximum earth-leakage current(1) |
|
0x7DBB–0x7DC0 |
32188–32193 |
– |
– |
– |
– |
– |
– |
– |
– |
Reserved |
|
(1) Value available with MicroLogic 7. |
||||||||||
Maximum Voltage Values
Maximum voltage values can be reset with the reset minimum/maximum command.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7DC1–0x7DC2 |
32194–32195 |
R |
V |
FLOAT32 |
41.6–2250 |
E |
E/P/H |
E |
X |
Maximum RMS phase-to-phase voltage V12 |
|
0x7DC3–0x7DC4 |
32196–32197 |
R |
V |
FLOAT32 |
41.6–2250 |
E |
E/P/H |
E |
X |
Maximum RMS phase-to-phase voltage V23 |
|
0x7DC5–0x7DC6 |
32198–32199 |
R |
V |
FLOAT32 |
41.6–2250 |
E |
E/P/H |
E |
X |
Maximum RMS phase-to-phase voltage V31 |
|
0x7DC7–0x7DC8 |
32200–32201 |
R |
V |
FLOAT32 |
24–1500 |
E |
E/P/H |
E |
X |
Maximum RMS phase-to-neutral voltage V1N(1) |
|
0x7DC9–0x7DCA |
32202–32203 |
R |
V |
FLOAT32 |
24–1500 |
E |
E/P/H |
E |
X |
Maximum RMS phase-to-neutral voltage V2N(1) |
|
0x7DCB–0x7DCC |
32204–32205 |
R |
V |
FLOAT32 |
24–1500 |
E |
E/P/H |
E |
X |
Maximum RMS phase-to-neutral voltage V3N(1) |
|
(1) Value available when system type register returns 40 or 41. |
||||||||||
Power Factor
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7DCD–0x7DCE |
32206–32207 |
R |
– |
FLOAT32 |
– |
E |
E/P/H |
E |
X |
Power factor on phase 1(1) |
|
0x7DCF–0x7DD0 |
32208–32209 |
R |
– |
FLOAT32 |
– |
E |
E/P/H |
E |
X |
Power factor on phase 2(1) |
|
0x7DD1–0x7DD2 |
32210–32211 |
R |
– |
FLOAT32 |
– |
E |
E/P/H |
E |
X |
Power factor on phase 3(1) |
|
0x7DD3–0x7DD4 |
32212–32213 |
R |
– |
FLOAT32 |
– |
E |
E/P/H |
E |
X |
Total power factor |
|
0x7DD5–0x7DD6 |
32214–32215 |
R |
– |
FLOAT32 |
– |
E |
H |
– |
X |
Fundamental power factor on phase 1 (cosϕ1)(1)(2) |
|
0x7DD7–0x7DD8 |
32216–32217 |
R |
– |
FLOAT32 |
– |
E |
H |
– |
X |
Fundamental power factor on phase 2 (cosϕ2)(1)(2) |
|
0x7DD9–0x7DDA |
32218–32219 |
R |
– |
FLOAT32 |
– |
E |
H |
– |
X |
Fundamental power factor on phase 3 (cosϕ3)(1)(2) |
|
0x7DDB–0x7DDC |
32220–32221 |
R |
– |
FLOAT32 |
– |
E |
H |
– |
X |
Total fundamental power factor(2) |
|
(1) Value available when system type register returns 40 or 41. (2) The sign for the fundamental power factor (cosϕ) depends on the configuration:
|
||||||||||
Total Harmonic Distortion (THD)
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7DDD–0x7DDE |
32222–32223 |
R |
– |
FLOAT32 |
0–2 |
E |
H |
– |
X |
Total harmonic distortion (THD) of phase-to phase voltage V12 compared to the fundamental |
|
0x7DDF–0x7DE0 |
32224–32225 |
R |
– |
FLOAT32 |
0–2 |
E |
H |
– |
X |
Total harmonic distortion (THD) of phase-to phase voltage V23 compared to the fundamental |
|
0x7DE1–0x7DE2 |
32226–32227 |
R |
– |
FLOAT32 |
0–2 |
E |
H |
– |
X |
Total harmonic distortion (THD) of phase-to phase voltage V31 compared to the fundamental |
|
0x7DE3–0x7DE4 |
32228–32229 |
R |
– |
FLOAT32 |
0–2 |
E |
H |
– |
X |
Total harmonic distortion (THD) of phase-to-neutral voltage V1N compared to the fundamental (1) |
|
0x7DE5–0x7DE6 |
32230–32231 |
R |
– |
FLOAT32 |
0–2 |
E |
H |
– |
X |
Total harmonic distortion (THD) of phase-to-neutral voltage V2N compared to the fundamental (1) |
|
0x7DE7–0x7DE8 |
32232–32233 |
R |
– |
FLOAT32 |
0–2 |
E |
H |
– |
X |
Total harmonic distortion (THD) of phase-to-neutral voltage V3N compared to the fundamental (1) |
|
0x7DE9– 0x7DEA |
32234–32235 |
R |
– |
FLOAT32 |
0–2 |
E |
H |
– |
X |
Total harmonic distortion (THD) of current on phase 1 compared to the fundamental |
|
0x7DEB–0x7DEC |
32236–32237 |
R |
– |
FLOAT32 |
0–2 |
E |
H |
– |
X |
Total harmonic distortion (THD) of current on phase 2 compared to the fundamental |
|
0x7DED–0x7DEE |
32238–32239 |
R |
– |
FLOAT32 |
0–2 |
E |
H |
– |
X |
Total harmonic distortion (THD) of current on phase 3 compared to the fundamental |
|
0x7DEF– 0x7DF0 |
32240–32241 |
R |
– |
FLOAT32 |
0–2 |
E |
H |
– |
X |
Average of 3-phase current Total harmonic distortions (THD) compared to the fundamental |
|
(1) Value available when system type register returns 40 or 41. |
||||||||||
Maximum Power Factor
Maximum power factor can be reset with the reset minimum/maximum command.
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Description |
|---|---|---|---|---|---|---|---|---|---|---|
|
0x7DF1–0x7DF2 |
32242–32243 |
R |
– |
FLOAT32 |
– |
– |
– |
– |
X |
Maximum total power factor |
|
0x7DF3–0x7E52 |
32244–32339 |
– |
– |
– |
– |
– |
– |
– |
– |
Reserved |
Inhibit Close Order
|
Address |
Register |
RW |
Unit |
Type |
Range |
A/E |
A/E/P/H |
Active |
X |
Bit |
Description |
|---|---|---|---|---|---|---|---|---|---|---|---|
|
0x7E53 |
32340 |
R |
– |
INT16U |
– |
A/E |
A/E/P/H |
– |
X |
– |
Quality of each bit of register 32341:
|
|
0x7E54 |
32341 |
R |
– |
INT16U |
– |
A/E |
A/E/P/H |
– |
X |
– |
Inhibit close order status |
|
0 |
Close breaker inhibited by IO module
|
||||||||||
|
1 |
Close breaker inhibited by communication
|
||||||||||
|
– |
– |
– |
– |
2–15 |
Reserved |