List of Registers
The quantities are listed in alphabetical order according to the SMS topic name.
To access available registers, the following address scheme applies
| Module | Module Name | Equation | Address Range |
|---|---|---|---|
| BCM | Circuit Breaker Communication Module | — | 1–47 |
| CCM | Cradle Communication Module | BCM + 50 | 51–97 |
| PM | Protection Module (Internal to trip unit) | BCM + 100 | 101–147 |
| MM | Meter Module (Internal to trip unit) | BCM + 200 | 201–247 |
List of Registers
| SMS Topic Name | User Description | Number of Registers* | Register* | Module* | Units* | Scale* |
|---|---|---|---|---|---|---|
| 810D_LDPU | Breaker LDPU in Progress | 1 | 8862 | PM | Scaling N/A | |
| 810DBrkrStatus | Breaker Status | 1 | 661 | BCM | Bit 0; ON = closed; OFF = open | |
| 810DBrkrTripStat | Breaker Trip Unit Status | 1 | 661 | BCM | Bit 2; ON = tripped; OFF = not tripped | |
| BCM_SN | BCM Serial Number | 4 | 516 | BCM | ASCII text | |
| BkrPos | Breaker Position | 1 | 661 | CCM | Bit 8 = disconnected Bit 9 = connected Bit 10 = test position |
|
| CFVAB | Crest Factor Voltage A-B | 1 | 1119 | MM | No Units | Hundredths |
| CFVAN | Crest Factor Voltage A-N | 1 | 1122 | MM | No Units | Hundredths |
| CFVBC | Crest Factor Voltage B-C | 1 | 1120 | MM | No Units | Hundredths |
| CFVBN | Crest Factor Voltage B-N | 1 | 1123 | MM | No Units | Hundredths |
| CFVCA | Crest Factor Voltage C-A | 1 | 1121 | MM | No Units | Hundredths |
| CFVCN | Crest Factor Voltage C-N | 1 | 1124 | MM | No Units | Hundredths |
| DT_3Regs | Device Clock Date/Time | 4 | 679 | BCM | 3-register date/time format* | |
| DTLastTrip | D/T of Last Trip | 3 | 693 | BCM | 3-register date/time format* | |
| DTPkIAD | D/T Peak Demand Current A | 3 | 3005 | MM | 3-register date/time format* | |
| DTPkIBD | D/T Peak Demand Current B | 3 | 3008 | MM | 3-register date/time format* | |
| DTPkICD | D/T Peak Demand Current C | 3 | 3011 | MM | 3-register date/time format* | |
| DTPkIND | D/T Peak Demand Current N | 3 | 3014 | MM | 3-register date/time format* | |
| DTPkKFDA | D/T K-Factor Dmd Peak A | 3 | 3041 | MM | No Units | 3-register date/time format* |
| DTPkKFDB | D/T K-Factor Dmd Peak B | 3 | 3044 | MM | No Units | 3-register date/time format* |
| DTPkKFDC | D/T K-Factor Dmd Peak C | 3 | 3047 | MM | No Units | 3-register date/time format* |
| DTPkKFDN | D/T K-Factor Dmd Peak N | 3 | 3050 | MM | No Units | 3-register date/time format* |
| DTPkkVAD | D/T Peak Demand Apparent Power | 3 | 3023 | MM | 3-register date/time format* | |
| DTPkkVARD | D/T Peak Demand Reactive Power | 3 | 3020 | MM | 3-register date/time format* | |
| DTPkkWD | D/T Peak Demand Active Power | 3 | 3017 | MM | 3-register date/time format* | |
| DTResetEnergy | D/T Last Reset Accum. Energies | 3 | 3038 | MM | 3-register date/time format* | |
| DTResetMinMax | D/T Last Reset Min/Max | 3 | 3032 | MM | 3-register date/time format* | |
| DTResetPkID | D/T Last Reset Peak Dmd Currents | 3 | 3026 | MM | 3-register date/time format* | |
| DTResetPkkWD | D/T Last Reset Peak Dmd Power | 3 | 3029 | MM | 3-register date/time format* | |
| EnableCloseBkr | Remote Closing Enabled | 1 | 669 | BCM | Bit 2; ON = enabled, OFF = not enabled | |
| EnableOpenBkr | Remote Opening Enabled | 1 | 669 | BCM | Bit 1; ON = enabled; OFF = not enabled | |
| EnableRemCtrl | Remote Control Enabled | 1 | 669 | BCM | Bit 3; ON = auto (enabled); OFF = manual (not enabled) | |
| fkVAA | Fundamental Apparent Power A | 1 | 1084 | MM | kVA | Scale E |
| fkVAB | Fundamental Apparent Power B | 1 | 1085 | MM | kVA | Scale E |
| fkVAC | Fundamental Apparent Power C | 1 | 1086 | MM | kVA | Scale E |
| fkVATtl | Fundamental Apparent Power Total | 1 | 1087 | MM | kVA | Scale E |
| fVAngA | Fundamental Voltage Ang A-B/A-N | 1 | 1133 | MM | Deg | Tenths |
| fVAngB | Fundamental Voltage Ang B-C/B-N | 1 | 1134 | MM | Deg | Tenths |
| fVAngC | Fundamental Voltage Ang C-A/C-N | 1 | 1135 | MM | Deg | Tenths |
| GFAlarmStatus | GF Alarm Status | 1 | 8860 | PM | Bit 0; ON = active; OFF = inactive | |
| GFPreAlarmStatus | GF Alarm Pre-Alarm Status | 1 | 8864 | PM | Bit 0; ON = active; OFF = inactive | |
| Hz | Frequency | 1 | 1054 | MM | Hz | Scale F |
| IA | Current A | 1 | 1016 | MM | A | Scale A - Phase Current |
| IA_PCT | Current A % Load | 1 | 8837 | PM | % | Unity |
| IAD | Demand Current A | 1 | 2200 | MM | A | Scale A |
| IAppA | Current Apparent A | 1 | 1023 | MM | A | Scale A |
| IAppB | Current Apparent B | 1 | 1024 | MM | A | Scale A |
| IAppC | Current Apparent C | 1 | 1025 | MM | A | Scale A |
| IAppN | Current Apparent N | 1 | 1026 | MM | A | Scale B |
| IAvg | Current Avg | 1 | 1027 | MM | A | Scale A - Phase Current |
| IB | Current B | 1 | 1017 | MM | A | Scale A - Phase Current |
| IB_PCT | Current B % Load | 1 | 8838 | PM | % | Unity |
| IBD | Demand Current B | 1 | 2201 | MM | A | Scale A |
| IC | Current C | 1 | 1018 | MM | A | Scale A - Phase Current |
| IC_PCT | Current C % Load | 1 | 8839 | PM | % | Unity |
| ICD | Demand Current C | 1 | 2202 | MM | A | Scale A |
| IDatPkKFD_A | Current Demand at Peak K-Factor Demand A | 1 | 2270 | MM | A | Scale A |
| IDatPkKFD_B | Current Demand at Peak K-Factor Demand B | 1 | 2271 | MM | A | Scale A |
| IDatPkKFD_C | Current Demand at Peak K-Factor Demand C | 1 | 2272 | MM | A | Scale A |
| IDatPkKFD_N | Current Demand at Peak K-Factor Demand N | 1 | 2273 | MM | A | Scale B |
| IG | Current G | 1 | 1021 | MM | A | Scale C |
| IG_PCT | Current G % Load | 1 | 8841 | PM | % | Unity |
| IG_PCT_VIGI | Current G (VIGI) % Load | 1 | 8842 | PM | % | Hundredths |
| IG_VIGI | Current G (VIGI) | 1 | 8826 | PM | A | Thousandths |
| IMax | Current Max Present | 1 | 1020 | MM | A | Scale A - Phase Current |
| IN | Current N | 1 | 1019 | MM | A | Scale B - Neutral Current |
| IN_PCT | Current N % Load | 1 | 8840 | PM | % | Unity |
| IND | Demand Current N | 1 | 2203 | MM | A | Scale B |
| IUnbalA | Current Unbalance A | 1 | 1028 | MM | % | Tenths |
| IUnbalAlrm | Current Unbalance Alarm Status | 1 | 8859 | PM | Bit 0; ON = active; OFF = inactive | |
| IUnbalB | Current Unbalance B | 1 | 1029 | MM | % | Tenths |
| IUnbalC | Current Unbalance C | 1 | 1030 | MM | % | Tenths |
| IUnbalPreAlrm | Current Unbalance Pre-Alarm Status | 1 | 8863 | PM | Bit 0; ON = active, OFF = inactive | |
| IUnbalW | Current Unbalance Worst | 1 | 1032 | MM | % | Tenths |
| KFDatPkID_A | K-Factor Demand at Peak Demand Current A | 1 | 2254 | MM | No Units | Tenths |
| KFDatPkID_B | K-Factor Demand at Peak Demand Current B | 1 | 2255 | MM | No Units | Tenths |
| KFDatPkID_C | K-Factor Demand at Peak Demand Current C | 1 | 2256 | MM | No Units | Tenths |
| KFDatPkID_N | K-Factor Demand at Peak Demand Current N | 1 | 2257 | MM | No Units | Tenths |
| KFDN | K-Factor Demand N | 1 | 2215 | MM | No Units | Tenths |
| KFN | K-Factor N | 1 | 1118 | MM | No Units | Tenths |
| kVAA | Apparent Power A | 1 | 1042 | MM | kVA | Scale E |
| kVAB | Apparent Power B | 1 | 1043 | MM | kVA | Scale E |
| kVAC | Apparent Power C | 1 | 1044 | MM | kVA | Scale E |
| kVAD | Demand Apparent Power | 1 | 2236 | MM | kVA | Scale D |
| kVAD_PkkVARD | KVA Dmd Coincident w/Peak KVAR Dmd | 1 | 2235 | MM | kVA | Scale D |
| kVAD_PkkWD | KVA Dmd Coincident w/Peak KW Dmd | 1 | 2229 | MM | kVA | Scale D |
| kVAHr | Apparent Energy | 4 | 2024 | MM | kVAH | Unity |
| kVARA | Reactive Power A | 1 | 1038 | MM | kVAR | Scale E |
| kVARB | Reactive Power B | 1 | 1039 | MM | kVAR | Scale E |
| kVARC | Reactive Power C | 1 | 1040 | MM | kVAR | Scale E |
| kVARD | Demand Reactive Power | 1 | 2230 | MM | kVAR | Scale D |
| kVARD_PkkVAD | KVAR Dmd Coincident w/Peak KVA Dmd | 1 | 2241 | MM | kVAR | Scale D |
| kVARD_PkkWD | KVAR Dmd Coincident w/Peak KW Dmd | 1 | 2228 | MM | kVAR | Scale D |
| kVARHr | Reactive Energy | 4 | 2004 | MM | kVARH | Unity |
| kVARHr_I | Reactive Energy Into the Load | 4 | 2016 | MM | kVARH | Unity |
| kVARHr_O | Reactive Energy Out of the Load | 4 | 2020 | MM | kVARH | Unity |
| kVARTtl | Reactive Power Total | 1 | 1041 | MM | kVAR | Scale E |
| kVATtl | Apparent Power Total | 1 | 1045 | MM | kVA | Scale E |
| kWA | Active Power A | 1 | 1034 | MM | kW | Scale E |
| kWB | Active Power B | 1 | 1035 | MM | kW | Scale E |
| kWC | Active Power C | 1 | 1036 | MM | kW | Scale E |
| kWD | Demand Active Power | 1 | 2224 | MM | kW | Scale D |
| kWD_PkkVAD | KW Dmd Coincident w/Peak KVA Dmd | 1 | 2240 | MM | kW | Scale D |
| kWD_PkkVARD | KW Dmd Coincident w/Peak KVAR Dmd | 1 | 2234 | MM | kW | Scale D |
| kWHr | Real Energy | 4 | 2000 | MM | kWH | Unity |
| kWHr_I | Real Energy Into the Load | 4 | 2008 | MM | kWH | Unity |
| kWHr_O | Real Energy Out of the Load | 4 | 2012 | MM | kWH | Unity |
| kWTtl | Active Power Total | 1 | 1037 | MM | kW | Scale E |
| LDPUValue | Long Delay Pickup Value | 2 | 8756 | PM | A | Unity |
| LSCurrAlrm | Load Shed Current Alarm Status | 1 | 8859 | PM | Bit 13; ON = active; OFF = inactive | |
| LSCurrPreAlrm | Load Shed Current Pre-Alarm Status | 1 | 8863 | PM | Bit 13; ON = active; OFF = inactive | |
| LSPwrAlrm | Load Shed Power Alarm Status | 1 | 8859 | PM | Bit 14; ON = active; OFF = inactive | |
| LSPwrPreAlrm | Load Shed Power Pre-Alarm Status | 1 | 8863 | PM | Bit 14; ON = active; OFF = inactive | |
| M2C_M6CR1Status | Relay Module R1 Status | 1 | 8857 | PM | Bit 0; ON = on; OFF = off | |
| M2C_M6CR2Status | Relay Module R2 Status | 1 | 8857 | PM | Bit 1; ON = on; OFF = off | |
| M2C_M6CR3Status | Relay Module R3 Status | 1 | 8857 | PM | Bit 2; ON = on; OFF = off | |
| M2C_M6CR4Status | Relay Module R4 Status | 1 | 8857 | PM | Bit 3; ON = on; OFF = off | |
| M2C_M6CR5Status | Relay Module R5 Status | 1 | 8857 | PM | Bit 4; ON = on; OFF = off | |
| M2C_M6CR6Status | Relay Module R6 Status | 1 | 8857 | PM | Bit 5; ON = on; OFF = off | |
| MaxCFVAB | Maximum Crest Factor Voltage A-B | 1 | 1719 | MM | No Units | Hundredths |
| MaxCFVAN | Maximum Crest Factor Voltage A-N | 1 | 1722 | MM | No Units | Hundredths |
| MaxCFVBC | Maximum Crest Factor Voltage B-C | 1 | 1720 | MM | No Units | Hundredths |
| MaxCFVBN | Maximum Crest Factor Voltage B-N | 1 | 1723 | MM | No Units | Hundredths |
| MaxCFVCA | Maximum Crest Factor Voltage C-A | 1 | 1721 | MM | No Units | Hundredths |
| MaxCFVCN | Maximum Crest Factor Voltage C-N | 1 | 1724 | MM | No Units | Hundredths |
| MaxfkVAA | Maximum Fundamental Apparent Power A | 1 | 1684 | MM | kVA | Scale E |
| MaxfkVAB | Maximum Fundamental Apparent Power B | 1 | 1685 | MM | kVA | Scale E |
| MaxfkVAC | Maximum Fundamental Apparent Power C | 1 | 1686 | MM | kVA | Scale E |
| MaxfkVATtl | Maximum Fundamental Apparent Power Total | 1 | 1687 | MM | kVA | Scale E |
| MaxfVMagAB | Maximum Fundamental Voltage Mag A-B | 1 | 1656 | MM | V | Scale D |
| MaxfVMagAN | Maximum Fundamental Voltage Mag A-N | 1 | 1659 | MM | V | Scale D |
| MaxfVMagBC | Maximum Fundamental Voltage Mag B-C | 1 | 1657 | MM | V | Scale D |
| MaxfVMagBN | Maximum Fundamental Voltage Mag B-N | 1 | 1660 | MM | V | Scale D |
| MaxfVMagCA | Maximum Fundamental Voltage Mag C-A | 1 | 1658 | MM | V | Scale D |
| MaxfVMagCN | Maximum Fundamental Voltage Mag C-N | 1 | 1661 | MM | V | Scale D |
| MaxHz | Max Frequency | 1 | 1654 | MM | Hz | Scale F |
| MaxIA | Max Current A | 1 | 1616 | MM | A | Scale A - Phase Current |
| MaxIAppA | Maximum Current Apparent A | 1 | 1623 | MM | A | Scale A |
| MaxIAppB | Maximum Current Apparent B | 1 | 1624 | MM | A | Scale A |
| MaxIAppC | Maximum Current Apparent C | 1 | 1625 | MM | A | Scale A |
| MaxIAppN | Maximum Current Apparent N | 1 | 1626 | MM | A | Scale B |
| MaxIAvg | Max Current Avg | 1 | 1627 | MM | A | Scale A - Phase Current |
| MaxIB | Max Current B | 1 | 1617 | MM | A | Scale A - Phase Current |
| MaxIC | Max Current C | 1 | 1618 | MM | A | Scale A - Phase Current |
| MaxIG | Max Current G | 1 | 1621 | MM | A | Scale C |
| MaxIG_VIGI | Max Current G (VIGI) | 1 | 8832 | PM | A | Thousandths |
| MaxIN | Max Current N | 1 | 1619 | MM | A | Scale B - Neutral Current |
| MaxIUnbalA | Max Current Unbalance A | 1 | 1628 | MM | % | Tenths |
| MaxIUnbalB | Max Current Unbalance B | 1 | 1629 | MM | % | Tenths |
| MaxIUnbalC | Max Current Unbalance C | 1 | 1630 | MM | % | Tenths |
| MaxIUnbalW | Max Current Unbalance Worst | 1 | 1632 | MM | % | Tenths |
| MaxKFN | Maximum K-Factor N | 1 | 1718 | MM | No Units | Tenths |
| MaxkVAA | Max Apparent Power A | 1 | 1642 | MM | kVA | Scale E |
| MaxkVAB | Max Apparent Power B | 1 | 1643 | MM | kVA | Scale E |
| MaxkVAC | Max Apparent Power C | 1 | 1644 | MM | kVA | Scale E |
| MaxkVARA | Max Reactive Power A | 1 | 1638 | MM | kVAR | Scale E |
| MaxkVARB | Max Reactive Power B | 1 | 1639 | MM | kVAR | Scale E |
| MaxkVARC | Max Reactive Power C | 1 | 1640 | MM | kVAR | Scale E |
| MaxkVARTtl | Max Reactive Power Total | 1 | 1641 | MM | kVAR | Scale E |
| MaxkVATtl | Max Apparent Power Total | 1 | 1645 | MM | kVA | Scale E |
| MaxkWA | Max Active Power A | 1 | 1634 | MM | kW | Scale E |
| MaxkWB | Max Active Power B | 1 | 1635 | MM | kW | Scale E |
| MaxkWC | Max Active Power C | 1 | 1636 | MM | kW | Scale E |
| MaxkWTtl | Max Active Power Total | 1 | 1637 | MM | kW | Scale E |
| MaxPFA | Max Power Factor A | 3 | 1646 | MM | PF format* | |
| MaxPFB | Max Power Factor B | 3 | 1647 | MM | PF format* | |
| MaxPFC | Max Power Factor C | 3 | 1648 | MM | PF format* | |
| MaxPFTtl | Max Power Factor Total | 3 | 1649 | MM | PF format* | |
| MaxVAB | Max Voltage A-B | 1 | 1600 | MM | V | Scale D - Voltage |
| MaxVAN | Max Voltage A-N | 1 | 1603 | MM | V | Scale D - Voltage |
| MaxVBC | Max Voltage B-C | 1 | 1601 | MM | V | Scale D - Voltage |
| MaxVBN | Max Voltage B-N | 1 | 1604 | MM | V | Scale D - Voltage |
| MaxVCA | Max Voltage C-A | 1 | 1602 | MM | V | Scale D - Voltage |
| MaxVCN | Max Voltage C-N | 1 | 1605 | MM | V | Scale D - Voltage |
| MaxVLLAvg | Max Voltage L-L Avg | 1 | 1606 | MM | V | Scale D - Voltage |
| MaxVLNAvg | Max Voltage L-N Avg | 1 | 1607 | MM | V | Scale D - Voltage |
| MaxVUnbalAB | Max Voltage Unbalance A-B | 1 | 1608 | MM | % | Tenths |
| MaxVUnbalAN | Max Voltage Unbalance A-N | 1 | 1611 | MM | % | Tenths |
| MaxVUnbalBC | Max Voltage Unbalance B-C | 1 | 1609 | MM | % | Tenths |
| MaxVUnbalBN | Max Voltage Unbalance B-N | 1 | 1612 | MM | % | Tenths |
| MaxVUnbalCA | Max Voltage Unbalance C-A | 1 | 1610 | MM | % | Tenths |
| MaxVUnbalCN | Max Voltage Unbalance C-N | 1 | 1613 | MM | % | Tenths |
| MaxVUnbalLLW | Max Voltage Unbalance L-L Worst | 1 | 1614 | MM | % | Tenths |
| MaxVUnbalLNW | Max Voltage Unbalance L-N Worst | 1 | 1615 | MM | % | Tenths |
| MinCFVAB | Minimum Crest Factor Voltage A-B | 1 | 1419 | MM | No Units | Hundredths |
| MinCFVAN | Minimum Crest Factor Voltage A-N | 1 | 1422 | MM | No Units | Hundredths |
| MinCFVBC | Minimum Crest Factor Voltage B-C | 1 | 1420 | MM | No Units | Hundredths |
| MinCFVBN | Minimum Crest Factor Voltage B-N | 1 | 1423 | MM | No Units | Hundredths |
| MinCFVCA | Minimum Crest Factor Voltage C-A | 1 | 1421 | MM | No Units | Hundredths |
| MinCFVCN | Minimum Crest Factor Voltage C-N | 1 | 1424 | MM | No Units | Hundredths |
| MinfkVAA | Minimum Fundamental Apparent Power A | 1 | 1384 | MM | kVA | Scale E |
| MinfkVAB | Minimum Fundamental Apparent Power B | 1 | 1385 | MM | kVA | Scale E |
| MinfkVAC | Minimum Fundamental Apparent Power C | 1 | 1386 | MM | kVA | Scale E |
| MinfkVATtl | Minimum Fundamental Apparent Power Total | 1 | 1387 | MM | kVA | Scale E |
| MinfVMagAB | Minimum Fundamental Voltage Mag A-B | 1 | 1356 | MM | V | Scale D |
| MinfVMagAN | Minimum Fundamental Voltage Mag A-N | 1 | 1359 | MM | V | Scale D |
| MinfVMagBC | Minimum Fundamental Voltage Mag B-C | 1 | 1357 | MM | V | Scale D |
| MinfVMagBN | Minimum Fundamental Voltage Mag B-N | 1 | 1360 | MM | V | Scale D |
| MinfVMagCA | Minimum Fundamental Voltage Mag C-A | 1 | 1358 | MM | V | Scale D |
| MinfVMagCN | Minimum Fundamental Voltage Mag C-N | 1 | 1361 | MM | V | Scale D |
| MinHz | Min Frequency | 1 | 1354 | MM | Hz | Scale F |
| MinIA | Min Current A | 1 | 1316 | MM | A | Scale A - Phase Current |
| MinIAppA | Minimum Current Apparent A | 1 | 1323 | MM | A | Scale A |
| MinIAppB | Minimum Current Apparent B | 1 | 1324 | MM | A | Scale A |
| MinIAppC | Minimum Current Apparent C | 1 | 1325 | MM | A | Scale A |
| MinIAppN | Minimum Current Apparent N | 1 | 1326 | MM | A | Scale B |
| MinIAvg | Min Current Avg | 1 | 1327 | MM | A | Scale A - Phase Current |
| MinIB | Min Current B | 1 | 1317 | MM | A | Scale A - Phase Current |
| MinIC | Min Current C | 1 | 1318 | MM | A | Scale A - Phase Current |
| MinIN | Min Current N | 1 | 1319 | MM | A | Scale B - Neutral Current |
| MinIUnbalA | Min Current Unbalance A | 1 | 1328 | MM | % | Tenths |
| MinIUnbalB | Min Current Unbalance B | 1 | 1329 | MM | % | Tenths |
| MinIUnbalC | Min Current Unbalance C | 1 | 1330 | MM | % | Tenths |
| MinIUnbalW | Min Current Unbalance Worst | 1 | 1332 | MM | % | Tenths |
| MinKFN | Minimum K-Factor N | 1 | 1418 | MM | No Units | Tenths |
| MinkVAA | Min Apparent Power A | 1 | 1342 | MM | kVA | Scale E |
| MinkVAB | Min Apparent Power B | 1 | 1343 | MM | kVA | Scale E |
| MinkVAC | Min Apparent Power C | 1 | 1344 | MM | kVA | Scale E |
| MinkVARA | Min Reactive Power A | 1 | 1338 | MM | kVAR | Scale E |
| MinkVARB | Min Reactive Power B | 1 | 1339 | MM | kVAR | Scale E |
| MinkVARC | Min Reactive Power C | 1 | 1340 | MM | kVAR | Scale E |
| MinkVARTtl | Min Reactive Power Total | 1 | 1341 | MM | kVAR | Scale E |
| MinkVATtl | Min Apparent Power Total | 1 | 1345 | MM | kVA | Scale E |
| MinkWA | Min Active Power A | 1 | 1334 | MM | kW | Scale E |
| MinkWB | Min Active Power B | 1 | 1335 | MM | kW | Scale E |
| MinkWC | Min Active Power C | 1 | 1336 | MM | kW | Scale E |
| MinkWTtl | Min Active Power Total | 1 | 1337 | MM | kW | Scale E |
| MinPFA | Min Power Factor A | 3 | 1346 | MM | PF format* | |
| MinPFB | Min Power Factor B | 3 | 1347 | MM | PF format* | |
| MinPFC | Min Power Factor C | 3 | 1348 | MM | PF format* | |
| MinPFTtl | Min Power Factor Total | 3 | 1349 | MM | PF format* | |
| MinVAB | Min Voltage A-B | 1 | 1300 | MM | V | Scale D - Voltage |
| MinVAN | Min Voltage A-N | 1 | 1303 | MM | V | Scale D - Voltage |
| MinVBC | Min Voltage B-C | 1 | 1301 | MM | V | Scale D - Voltage |
| MinVBN | Min Voltage B-N | 1 | 1304 | MM | V | Scale D - Voltage |
| MinVCA | Min Voltage C-A | 1 | 1302 | MM | V | Scale D - Voltage |
| MinVCN | Min Voltage C-N | 1 | 1305 | MM | V | Scale D - Voltage |
| MinVLLAvg | Min Voltage L-L Avg | 1 | 1306 | MM | V | Scale D - Voltage |
| MinVLNAvg | Min Voltage L-N Avg | 1 | 1307 | MM | V | Scale D - Voltage |
| MinVUnbalAB | Min Voltage Unbalance A-B | 1 | 1308 | MM | % | Tenths |
| MinVUnbalAN | Min Voltage Unbalance A-N | 1 | 1311 | MM | % | Tenths |
| MinVUnbalBC | Min Voltage Unbalance B-C | 1 | 1309 | MM | % | Tenths |
| MinVUnbalBN | Min Voltage Unbalance B-N | 1 | 1312 | MM | % | Tenths |
| MinVUnbalCA | Min Voltage Unbalance C-A | 1 | 1310 | MM | % | Tenths |
| MinVUnbalCN | Min Voltage Unbalance C-N | 1 | 1313 | MM | % | Tenths |
| MinVUnbalLLW | Min Voltage Unbalance L-L Worst | 1 | 1314 | MM | % | Tenths |
| MinVUnbalLNW | Min Voltage Unbalance L-N Worst | 1 | 1315 | MM | % | Tenths |
| NominalCurrent | Breaker Nominal Current | 1 | 8750 | PM | A | Unity |
| OverFreqAlrm | Over Frequency Alarm Status | 1 | 8859 | PM | Bit 11; ON = active, OFF = inactive | |
| OverFreqPreAlrm | Over Frequency Pre-Alarm Status | 1 | 8863 | PM | Bit 11; ON = active, OFF = inactive | |
| OverIAAlrm | Over IA Demand Alarm Status | 1 | 8859 | PM | Bit 1; ON = active, OFF = inactive | |
| OverIAPreAlrm | Over IA Demand Pre-Alarm Status | 1 | 8863 | PM | Bit 1; ON = active, OFF = inactive | |
| OverIBAlrm | Over IB Demand Alarm Status | 1 | 8859 | PM | Bit 2; ON = active, OFF = inactive | |
| OverIBPreAlrm | Over IB Demand Pre-Alarm Status | 1 | 8863 | PM | Bit 2; ON = active, OFF = inactive | |
| OverICAlrm | Over IC Demand Alarm Status | 1 | 8859 | PM | Bit 3; ON = active, OFF = inactive | |
| OverICPreAlrm | Over IC Demand Pre-Alarm Status | 1 | 8863 | PM | Bit 3; ON = active, OFF = inactive | |
| OverINAlrm | Over IN Demand Alarm Status | 1 | 8859 | PM | Bit 4; ON = active, OFF = inactive | |
| OverINPreAlrm | Over IN Demand Pre-Alarm Status | 1 | 8863 | PM | Bit 4; ON = active, OFF = inactive | |
| OverVoltAlrm | Over Voltage Alarm Status | 1 | 8859 | PM | Bit 6; ON = active, OFF = inactive | |
| OverVoltPreAlrm | Over Voltage Pre-Alarm Status | 1 | 8863 | PM | Bit 6; ON = active, OFF = inactive | |
| PF_PkkVAD | PF Coincident w/Peak KVA Demand | 3 | 2239 | MM | Thousandths | |
| PF_PkkVARD | PF Coincident w/Peak KVAR Demand | 3 | 2233 | MM | Thousandths | |
| PF_PkkWD | PF Coincident w/Peak KW Demand | 3 | 2227 | MM | Thousandths | |
| PFA | Power Factor A | 3 | 1046 | MM | PF format* | |
| PFB | Power Factor B | 3 | 1047 | MM | PF format* | |
| PFC | Power Factor C | 3 | 1048 | MM | PF format* | |
| PFTtl | Power Factor Total | 3 | 1049 | MM | PF format* | |
| PhaRotAlrm | Phase Rotation Alarm Status | 1 | 8859 | PM | Bit 12; ON = active, OFF = inactive | |
| PkIAD | Peak Demand Current A | 1 | 2204 | MM | A | Scale A |
| PkIBD | Peak Demand Current B | 1 | 2205 | MM | A | Scale A |
| PkICD | Peak Demand Current C | 1 | 2206 | MM | A | Scale A |
| PkIND | Peak Demand Current N | 1 | 2207 | MM | A | Scale A |
| PkKFDA | Peak K-Factor Demand A | 1 | 2216 | MM | No Units | Tenths |
| PkKFDB | Peak K-Factor Demand B | 1 | 2217 | MM | No Units | Tenths |
| PkKFDC | Peak K-Factor Demand C | 1 | 2218 | MM | No Units | Tenths |
| PkKFDN | Peak K-Factor Demand N | 1 | 2219 | MM | No Units | Tenths |
| PkkVAD | Peak Demand Apparent Power | 1 | 2237 | MM | kVA | Scale A |
| PkkVARD | Peak Demand Reactive Power | 1 | 2231 | MM | kVAR | Scale A |
| PkkWD | Peak Demand Active Power | 1 | 2225 | MM | kW | Scale A |
| PredIAD | Predicted Demand Current A | 1 | 2208 | MM | A | Scale A |
| PredIBD | Predicted Demand Current B | 1 | 2209 | MM | A | Scale A |
| PredICD | Predicted Demand Current C | 1 | 2210 | MM | A | Scale A |
| PredIND | Predicted Demand Current N | 1 | 2211 | MM | A | Scale A |
| PredKFDA | Predicted K-Factor Demand A | 1 | 2220 | MM | No Units | Tenths |
| PredKFDB | Predicted K-Factor Demand B | 1 | 2221 | MM | No Units | Tenths |
| PredKFDC | Predicted K-Factor Demand C | 1 | 2222 | MM | No Units | Tenths |
| PredKFDN | Predicted K-Factor Demand N | 1 | 2223 | MM | No Units | Tenths |
| PredkVAD | Predicted KVA Demand | 1 | 2238 | MM | kVA | Scale A |
| PredkVARD | Predicted KVAR Demand | 1 | 2232 | MM | kVAR | Scale A |
| PredkWD | Predicted KW Demand | 1 | 2226 | MM | kW | Scale A |
| R1OpsCounter | Relay 1 Operations Counter | 1 | 9081 | PM | Unity | |
| R2OpsCounter | Relay 2 Operations Counter | 1 | 9082 | PM | Unity | |
| R3OpsCounter | Relay 3 Operations Counter | 1 | 9083 | PM | Unity | |
| R4OpsCounter | Relay 4 Operations Counter | 1 | 9084 | PM | Unity | |
| R5OpsCounter | Relay 5 Operations Counter | 1 | 9085 | PM | Unity | |
| R6OpsCounter | Relay 6 Operations Counter | 1 | 9086 | PM | Unity | |
| ReadyToClose | Breaker Ready to Close | 1 | 661 | BCM | Bit 5; ON = yes, OFF = no | |
| RevPwrAlrm | Reverse Power Alarm Status | 1 | 8859 | PM | Bit 9; ON = active; OFF = inactive | |
| RevPwrPreAlrm | Reverse Power Pre-Alarm Status | 1 | 8863 | PM | Bit 9; ON = active; OFF = inactive | |
| TimeToTrip | Time Remaining to LT Trip | 2 | 8865 | PM | Tenths | |
| TU_BATT_PCT | Trip Unit % Battery | 1 | 8843 | PM | % | Unity |
| TU_SN | Trip Unit Serial Number | 4 | 8700 | PM | ASCII text | |
| TUCommStatus | Trip Unit Internal Comms Status | 1 | 552 | BCM | Bit 11; ON = not responding; OFF = OK | |
| UnderFreqAlrm | Under Frequency Alarm Status | 1 | 8859 | PM | Bit 10; ON = active; OFF = inactive | |
| UnderFreqPreAlrm | Under Frequency Pre-Alarm Status | 1 | 8863 | PM | Bit 10; ON = active; OFF = inactive | |
| UnderVoltAlrm | Under Voltage Alarm Status | 1 | 8859 | PM | Bit 5; ON = active; OFF = inactive | |
| UnderVoltPreAlrm | Under Voltage Pre-Alarm Status | 1 | 8863 | PM | Bit 5; ON = active; OFF = inactive | |
| VAB | Voltage A-B | 1 | 1000 | MM | V | Scale D - Voltage |
| VAN | Voltage A-N | 1 | 1003 | MM | V | Scale D - Voltage |
| VBC | Voltage B-C | 1 | 1001 | MM | V | Scale D - Voltage |
| VBN | Voltage B-N | 1 | 1004 | MM | V | Scale D - Voltage |
| VCA | Voltage C-A | 1 | 1002 | MM | V | Scale D - Voltage |
| VCN | Voltage C-N | 1 | 1005 | MM | V | Scale D - Voltage |
| VigiAlarm | Vigi Alarm Status | 1 | 8860 | PM | Bit 1; ON = active; OFF = inactive | |
| VigiPreAlrm | Vigi Pre-Alarm Status | 1 | 8864 | PM | Bit 1; ON = active; OFF = inactive | |
| VLLAvg | Voltage L-L Avg | 1 | 1006 | MM | V | Scale D - Voltage |
| VLNAvg | Voltage L-N Avg | 1 | 1007 | MM | V | Scale D - Voltage |
| VUnbalAB | Voltage Unbalance A-B | 1 | 1008 | MM | % | Tenths |
| VUnbalAlrm | Voltage Unbalance Alarm Status | 1 | 8859 | PM | Bit 7; ON = active, OFF = inactive | |
| VUnbalAN | Voltage Unbalance A-N | 1 | 1011 | MM | % | Tenths |
| VUnbalBC | Voltage Unbalance B-C | 1 | 1009 | MM | % | Tenths |
| VUnbalBN | Voltage Unbalance B-N | 1 | 1012 | MM | % | Tenths |
| VUnbalCA | Voltage Unbalance C-A | 1 | 1010 | MM | % | Tenths |
| VUnbalCN | Voltage Unbalance C-N | 1 | 1013 | MM | % | Tenths |
| VUnbalLLW | Voltage Unbalance L-L Worst | 1 | 1014 | MM | % | Tenths |
| VUnbalLNW | Voltage Unbalance L-N Worst | 1 | 1015 | MM | % | Tenths |
| VUnbalPreAlrm | Voltage Unbalance Pre-Alarm Status | 1 | 8863 | PM | Bit 7; ON = active, OFF = inactive |