Access Management Per Access Path
General Description
Data on MicroLogic Active control units can be accessed:
-
From the MicroLogic Active HMI (PIN code protected)
-
On a device connected to the MicroLogic Active USB-C port (password protected):
-
An Android smartphone running EcoStruxure Power Device app through USB OTG connection
-
A PC running EcoStruxure Power Commission software
-
-
On remote controllers through the ULP modules of the IMU system (only if the MicroLogic Active control unit is in Auto Remote control mode)
-
On a smartphone running EcoStruxure Power Device app through NFC connection
-
On Panel Server webpages and on servers or remote controllers connected to Panel Server, through Zigbee wireless communication (MicroLogic Active AP/EP control unit only)
The following table describes the functions which can be accessed via each access path, and the required protection mechanisms (if any).
Function |
Description |
Access path |
||||
---|---|---|---|---|---|---|
HMI |
USB port |
IMU |
Zigbee |
NFC |
||
Monitoring |
Read settings, measurements, and data |
✔ |
- |
✔ |
✔ |
✔ |
Settings |
Set MicroLogic Active control unit settings |
✔ (1) |
✔ (2) |
- |
- |
- |
Reset counters |
Reset minimum and maximum values |
✔ |
- |
- |
- |
- |
Test |
Send test commands |
✔ (1) |
- |
- |
- |
- |
Firmware update |
Update firmware to the latest version |
- |
✔ (2) |
- |
- |
- |
Operation |
Send commands to open and close the circuit breaker |
- |
- |
✔ (3) |
- |
- |
MicroLogic Active replacement |
Set the settings of a replacement MicroLogic Active control unit |
✔ (1) |
- |
- |
- |
- |
✔ Access allowed without restriction ✔ (1) Access protected by PIN code ✔ (2) Access protected by USB password ✔ (3) Access only allowed in Auto Remote control mode |