DOCA0265EN-03

Event List

Event Characteristics

The events are listed according to the history in which they are logged.

Each event is defined by the following characteristics:

  • Code: event code

  • Event: user message

  • History

  • Type: not customizable

    • Entry/Exit: occurrence/completion event.

    • Pulse: instantaneous event.

  • Latched:

    • Yes: the event is latched and the user must reset the event status.

    • No: the event is unlatched.

  • Activity:

    • Enabled

    • Disabled

  • Severity:

    • High severity events.

    • Medium severity events.

    • Low severity events.

Trip Events

Code

Event

History

Type

Latched

Activity

Severity

0x6400

(25600)

Long Time (Ir) trip

Trip

Pulse

Yes

Enabled

High

0x6401

(25601)

Short Time (Isd) trip

Trip

Pulse

Yes

Enabled

High

0x6402

(25602)

Instantaneous (Ii) trip

Trip

Pulse

Yes

Enabled

High

0x6403

(25603)

Ground Fault (Ig) trip

Trip

Pulse

Yes

Enabled

High

0x6406

(25606)

Ultimate self-protection (SELLIM) trip

Trip

Pulse

Yes

Enabled

High

0x6407

(25607)

Self diagnostic trip. Replace control unit

Trip

Pulse

Yes

Enabled

High

0x641D

(25629)

Ultimate self-protection (DIN/DINF) trip

Trip

Pulse

Yes

Enabled

High

0x641E

(25630)

Ig test trip

Trip

Pulse

Yes

Enabled

High

0x6405

(25605)

Control unit over temperature trip

Trip

Pulse

Yes

Enabled

High

0x640A

(25610)

ENCT Disconnected trip

Trip

Pulse

Yes

Enabled

High

0x6433

(25651)

Current sensor loss. Replace Circuit Breaker

Trip

Pulse

Yes

Enabled

High

Protection Events

Code

Event

History

Type

Latch

Activity

Severity

0x0F11

(3857)

Thermal memory reset order

Protection

Pulse

No

Enabled

Low

0x03F5

(1013)

Ir pre-alarm (I > 90% Ir)

Protection

Entry/Exit

No

Enabled

Medium

0x6200

(25088)

Ir start (I > 105% Ir)

Protection

Entry/Exit

No

Enabled

High

0x6201

(25089)

Isd start

Protection

Entry/Exit

No

Enabled

Low

0x6203

25091

Ig start

Protection

Entry/Exit

No

Enabled

Low

0x0C03

(3075)

ERMS engaged

Protection

Entry/Exit

No

Enabled

Low

0x0C08

(3080)

Ii protection disabled

Protection

Pulse

No

Enabled

Low

0x0C09

(3081)

Ig protection disabled

Protection

Pulse

No

Enabled

Low

0x1100

(4352)

Protection changed by HMI

Protection

Pulse

No

Enabled

Low

0x1108

(4360)

Protection changed by communication

Protection

Pulse

No

Enabled

Low

Diagnostic Events

Code

Event

History

Type

Latch

Activity

Severity

0x1302

(4866)

Control Unit in test mode

Diagnostic

Entry/Exit

No

Enabled

Low

0x1303

(4867)

Injection test in progress

Diagnostic

Entry/Exit

No

Enabled

Low

0x1304

(4868)

Test aborted by user

Diagnostic

Pulse

No

Enabled

Low

0x1400

(5120)

Self test 1. Replace control unit

Diagnostic

Entry/Exit

No

Enabled

High

0x1404

(5124)

Control unit over temperature

Diagnostic

Entry/Exit

No

Enabled

High

0x1405

(5125)

Self test 3. Replace control unit

Diagnostic

Entry/Exit

No

Enabled

High

0x1406

(5126)

Self test 4. Replace control unit

Diagnostic

Entry/Exit

No

Enabled

High

0x1416

(5142)

Mitop disconnected. Call Schneider Electric support

Diagnostic

Entry/Exit

No

Enabled

High

0x1518

(5400)

Self-test 6. Replace control unit

Diagnostic

Entry/Exit

No

Enabled

High

0x1402

(5122)

Current sensor loss. Replace circuit breaker

Diagnostic

Entry/Exit

No

Enabled

High

0x1403

(5123)

ENCT disconnected

Diagnostic

Entry/Exit

No

Enabled

High

0x1430

(5168)

Protection settings reset to factory values

Diagnostic

Entry/Exit

No

Enabled

High

0x142F

(5167)

Last protection settings have not been applied

Diagnostic

Entry/Exit

No

Enabled

Medium

0x140F

(5135)

Protection settings not accessible 1

Diagnostic

Entry/Exit

No

Enabled

Medium

0x1474

(5236)

Protection settings not accessible 2

Diagnostic

Entry/Exit

No

Enabled

Medium

0x1473

(5235)

Internal access loss. Reboot control unit

Diagnostic

Entry/Exit

No

Enabled

Medium

0x1433

(5171)

Replace internal battery

Diagnostic

Entry/Exit

No

Enabled

Low

0x1437

(5175)

Internal battery not detected

Diagnostic

Entry/Exit

No

Enabled

Low

0x1436

(5174)

Control unit memory degradation

Diagnostic

Pulse

No

Enabled

Low

0x1409

(5129)

Unable to read sensor plug

Diagnostic

Entry/Exit

No

Enabled

High

0x0D09

(3337)

Firmware discrepancy within control unit

Diagnostic

Entry/Exit

No

Enabled

Medium

0x0D0A

(3338)

Invalid CU factory config. 1

Diagnostic

Entry/Exit

No

Enabled

Low

0x1413

Ig test - no trip

Diagnostic

Pulse

No

Enabled

High

0x142A

(5162)

Ig test launched

Diagnostic

Pulse

No

Enabled

Low

0x1482

(5250)

Sched. Manufact. maintenance within 3 months

Diagnostic

Entry/Exit

No

Enabled

Medium

0x1440

(5184)

Contact wear > 60%. Check contacts

Diagnostic

Entry/Exit

No

Enabled

Medium

0x1441

(5185)

Contact wear > 95%. Plan circuit breaker replacement

Diagnostic

Entry/Exit

No

Enabled

Medium

0x1442

(5186)

Contact wear > 100%. Replace circuit breaker

Diagnostic

Entry/Exit

No

Enabled

High

0x1435

(5173)

Events in history log have been erased

Diagnostic

Pulse

No

Enabled

Low

0x150F

(5391)

Iron CT loss. Replace circuit breaker

Diagnostic

Entry/Exit

No

Enabled

High

0x1517

(5399)

Current unbalance > 50%. Check load balancing

Diagnostic

Entry/Exit

No

Enabled

Low

0x1421 (5153)

Invalid PowerTag communication

Diagnostic

Entry/Exit

No

Enabled

Medium

0x1423 (5155)

Loss of IEEE 802.15.4 communication with Gateway

Diagnostic

Entry/Exit

No

Enabled

Low

Operation Events

Code

Event

History

Type

Latch

Activity

Severity

0x1000

(4096)

Circuit breaker opened

Operation

Pulse

No

Enabled

Low

0x1001

(4097)

Circuit breaker closed

Operation

Pulse

No

Enabled

Low

0x1307

(4871)

Alarm reset

Operation

Pulse

No

Enabled

Low

0x112B

(4395)

Control unit firmware update mode

Operation

Entry/Exit

No

Enabled

Low

0x112C

(4396)

Control unit firmware update unsuccessful

Operation

Pulse

No

Enabled

Low

0x1107

(4359)

Date and time set

Operation

Pulse

No

Enabled

Low

0x1301

(4865)

Connection on USB port

Operation

Entry/Exit

No

Enabled

Low

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?