Overview of Group Objects
Logic
Nr. |
Name |
Object function |
Length |
Properties |
Note |
Function description |
DPT |
---|---|---|---|---|---|---|---|
1 |
1th Logic |
Input a |
1 bit |
C,W,T,U |
visible if not disconnected |
AND, OR, XOR |
1.002 boolean |
2 |
1th Logic |
Input b |
1 bit |
C,W,T,U |
AND, OR, XOR |
||
3 |
1th Logic |
Input c |
1 bit |
C,W,T,U |
AND, OR, XOR |
||
4 |
1th Logic |
Input d |
1 bit |
C,W,T,U |
AND, OR, XOR |
||
5 |
1th Logic |
Input e |
1 bit |
C,W,T,U |
AND, OR, XOR |
||
6 |
1th Logic |
Input f |
1 bit |
C,W,T,U |
AND, OR, XOR |
||
7 |
1th Logic |
Input g |
1 bit |
C,W,T,U |
AND, OR, XOR |
||
8 |
1th Logic |
Input h |
1 bit |
C,W,T,U |
AND, OR, XOR |
||
9 |
1th Logic |
Logic result |
1 bit |
C,T |
AND, OR, XOR |
||
1 |
1th Logic |
Threshold value input |
4 bit 1 byte 2 byte 4 byte |
C,W,U |
Length according to parameter select |
Threshold comparator |
3.007 dimming 5.010 counter pulses 7.001 pulses 12.001 counter pulses |
9 |
1th Logic |
Logic result |
1 bit |
C,T |
Threshold comparator |
1.002 boolean |
|
1 |
1th Logic |
Input 1bit-bit0 |
1 bit |
C,W,U |
2 x 1bit → 1 x 2bit |
Format convert |
1.002 boolean |
2 |
1th Logic |
Input 1bit-bit1 |
1 bit |
C,W,U |
Format convert |
1.002 boolean |
|
9 |
1th Logic |
Output 2bit |
2 bit |
C,T |
Format convert |
2.001 switch control |
|
1 |
1th Logic |
Input 1bit-bit0 |
1 bit |
C,W,U |
8 x 1bit → 1 x 1byte |
Format convert |
1.002 boolean |
2 |
1th Logic |
Input 1bit-bit1 |
1 bit |
C,W,U |
Format convert |
||
3 |
1th Logic |
Input 1bit-bit2 |
1 bit |
C,W,U |
Format convert |
||
4 |
1th Logic |
Input 1bit-bit3 |
1 bit |
C,W,U |
Format convert |
||
5 |
1th Logic |
Input 1bit-bit4 |
1 bit |
C,W,U |
Format convert |
||
6 |
1th Logic |
Input 1bit-bit5 |
1 bit |
C,W,U |
Format convert |
||
7 |
1th Logic |
Input 1bit-bit6 |
1 bit |
C,W,U |
Format convert |
||
8 |
1th Logic |
Input 1bit-bit7 |
1 bit |
C,W,U |
Format convert |
||
9 |
1th Logic |
Output 1byte |
1 byte |
C,T |
Format convert |
5.010 counter pulses |
|
1 |
1th Logic |
Input 1byte |
1 byte |
C,W,U |
1 x 1byte → 1 x 2byte |
Format convert |
5.010 counter pulses |
9 |
1th Logic |
Output 2byte |
2 byte |
C,T |
Format convert |
7.001 pulses |
|
1 |
1th Logic |
Input 1byte-low |
1 byte |
C,W,U |
2 x1byte → 1 x 2byte |
Format convert |
5.010 counter pulses |
2 |
1th Logic |
Input 1byte-high |
1 byte |
C,W,U |
Format convert |
5.010 counter pulses |
|
9 |
1th Logic |
Output 2byte |
2 byte |
C,T |
Format convert |
7.001 pulses |
|
1 |
1th Logic |
Input 2byte-low |
2 byte |
C,W,U |
2 x 2byte → 1 x 4byte |
Format convert |
7.001 pulses |
2 |
1th Logic |
Input 2byte-high |
2 byte |
C,W,U |
Format convert |
||
9 |
1th Logic |
Output 4byte |
4 byte |
C,T |
Format convert |
12.001 counter pulses |
|
1 |
1th Logic |
Input 1byte |
1 byte |
C,W,U |
1 x 1byte → 8 x 1bit |
Format convert |
5.010 counter pulses |
2 |
1th Logic |
Output 1bit-bit0 |
1 bit |
C,T |
Format convert |
1.002 boolean |
|
3 |
1th Logic |
Output 1bit-bit1 |
1 bit |
C,T |
Format convert |
||
4 |
1th Logic |
Output 1bit-bit2 |
1 bit |
C,T |
Format convert |
||
5 |
1th Logic |
Output 1bit-bit3 |
1 bit |
C,T |
Format convert |
||
6 |
1th Logic |
Output 1bit-bit4 |
1 bit |
C,T |
Format convert |
||
7 |
1th Logic |
Output 1bit-bit5 |
1 bit |
C,T |
Format convert |
||
8 |
1th Logic |
Output 1bit-bit6 |
1 bit |
C,T |
Format convert |
||
9 |
1th Logic |
Output 1bit-bit7 |
1 bit |
C,T |
Format convert |
||
1 |
1th Logic |
Input 2byte |
2 byte |
C,W,U |
1 x 2byte → 2 x 1byte |
Format convert |
7.001 pulses |
8 |
1th Logic |
Output 1byte-low |
1 byte |
C,T |
Format convert |
5.010 counter pulses |
|
9 |
1th Logic |
Output 1byte-high |
1 byte |
C,T |
Format convert |
||
1 |
1th Logic |
Input 4byte |
4 byte |
C,W,U |
1 x 4byte → 2 x 2byte |
Format convert |
12.001 counter pulses |
8 |
1th Logic |
Output 2byte-low |
2 byte |
C,T |
Format convert |
7.001 pulses |
|
9 |
1th Logic |
Output 2byte-high |
2 byte |
C,T |
Format convert |
||
1 |
1th Logic |
Input 3byte |
3 byte |
C,W,U |
1 x 3byte → 3 x 1byte |
Format convert |
232.600 RGB value 3 x (0..255) |
7 |
1th Logic |
Output 1byte-low |
1 byte |
C,T |
Format convert |
5.010 counter pulses |
|
8 |
1th Logic |
Output 1byte-middle |
1 byte |
C,T |
Format convert |
||
9 |
1th Logic |
Output 1byte-high |
1 byte |
C,T |
Format convert |
||
1 |
1th Logic |
Input 1byte-low |
1 byte |
C,W,U |
3 x 1byte → 1 x 3byte |
Format convert |
5.010 counter pulses |
2 |
1th Logic |
Input 1byte-middle |
1 byte |
C,W,U |
Format convert |
||
3 |
1th Logic |
Input 1byte-high |
1 byte |
C,W,U |
Format convert |
||
9 |
1th Logic |
Output 3byte |
3 byte |
C,T |
Format convert |
232.600 RGB value 3 x (0..255) |
|
10 – 18 |
2nd Logic |
||||||
19 – 27 |
3rd Logic |
||||||
28 – 36 |
4th Logic |
||||||
37 – 45 |
5th Logic |
||||||
46 – 54 |
6th Logic |
||||||
55 – 63 |
7th Logic |
||||||
64 – 72 |
8th Logic |
Functions
Nr. |
Name |
Object function |
Length |
Properties |
Note |
Function description |
DPT |
---|---|---|---|---|---|---|---|
73 |
Function 1 The name of the object refers to the parameter Name of the channel of the function. The name of the function changes with the parameter description. If the parameter description is empty, Function 1 displays by default. |
Switch object A |
1 bit |
C,T |
Switch values are sent alternately during operation. |
Toggle: Extended settings disable |
1.001 switch |
75 |
Switch status object A |
1 bit |
C,W |
||||
73 |
Switch object A, Value object A |
1 bit/1 byte |
C,T |
visible according to object type |
Toggle: Extended settings |
1.001 switch, 5.001 percentage (0..100%), 5.010 counter pulses |
|
74 |
Switch object B, Value object B |
1 bit/1 byte |
C,T |
visible according to object type&2 objects |
|||
75 |
Switch status object A, Value status object A |
1 bit/1 byte |
C,W |
visible according to object type |
|||
76 |
Switch status object B, Value status object B |
1 bit/1 byte |
C,W |
visible according to object type&2 objects |
|||
73 |
Function 1 The name of the object refers to the parameter Name of the channel of the function. The name of the function changes with the parameter description. If the parameter description is empty, Function 1 displays by default. |
Switch object A |
1 bit |
C,T |
Switching: Extended settings disable |
1.001 switch |
|
73 |
Switch object A, Value object A |
1 bit, 1 byte |
C,T |
Visible according to object type |
Switching: Extended settings |
1.001 switch, 5.001 percentage(0..100%), 5.010 counter pulses |
|
74 |
Switch object B, Value object B |
1 bit, 1 byte |
C,T |
Visible according to object type and objects |
|||
73 |
Switch object |
1 bit |
C,T |
Dimming |
1.001 switch |
||
74 |
Dimming object |
4 bit |
C,T |
3.007 dimming |
|||
75 |
Switch status object |
1 bit |
C,W |
Only visible if you select Dimming brighter/darker |
1.001 switch |
||
73 |
Movement object |
1 bit |
C,T |
Moving blind up, Moving blind down, Moving blind up/down |
Blind |
1.008 up/down |
|
74 |
Stop/step |
1 bit |
C,T |
1.007 step |
|||
75 |
Last direction |
1 bit |
C,W |
Only visible if you select Moving blind up/down |
Blind Extended settings |
1.008 up/down |
|
73 |
Blind position |
1 byte |
C,T |
Moving blind with positioning values |
5.001 percentage (0..100%), 5.010 counter pulses |
||
74 |
Slat position |
1 byte |
C,T |
||||
73 |
Switch object A, Priority control object A, Dimming object A, Value object A |
1 bit 2 bit 4 bit 1 byte |
C,T |
Visible according to object type |
Edges 1bit, 2bit (Priority), 4bit, 1byte values |
1.001 switch, 2.001 switch control, 3.007 dimming, 5.010 counter pulses, 5.001 percentage (0..100%) |
|
74 |
Switch object B, Priority control object B, Dimming object B, Value object B |
C,T |
visible according to object type and objects |
||||
75 |
Switch status object A, Priority control status object A, Dimming status object A, Value status object A |
1 bit 2 bit 4 bit 1 byte |
C,W |
visible according to object type |
1.001 switch, 2.001 switch control, 3.007 dimming, 5.010 counter pulses, 5.001 percentage (0..100%) |
||
76 |
Switch status object B, Priority control status object B, Dimming status object B, Value status object B |
C,W |
visible according to object type&2 objects |
||||
73 |
Value object A |
2 byte |
C,T |
visible according to object type |
Edges with 2byte values |
9.004 lux(Lux), 7.001 pulses, 8.001 pulses difference |
|
75 |
Value status object A |
C,W |
|||||
73 |
Value object A |
1 byte |
C,T |
8 bit slider |
5.004 percentage (0..255%) |
||
75 |
Set value object A |
C,W |
|||||
73 |
Scene object A |
1 byte |
C,T |
Scene |
18.001 scene control |
||
74 |
Function 1 The name of the object refers to the parameter Name of the channel of the function. The name of the function changes with the parameter description. If the parameter description is empty, Function 1 displays by default. |
Scene object B |
1 byte |
C,T |
Scene Extended settings |
18.001 scene control |
|
73 |
RGB dimming value |
3 byte |
C,T |
RGB: 3byte option |
RGB lighting |
232.600 RGB value 3 x (0..255) |
|
73 |
RGBW dimming value |
6 byte |
C,T |
RGBW: 6byte option |
251.600 DPT_Colour_RGBW |
||
73 |
Red dimming value |
1 byte |
C,T |
1byte option |
5.001 percentage( 0..100%) |
||
74 |
Green dimming value |
1 byte |
C,T |
||||
75 |
Blue dimming value |
1 byte |
C,T |
||||
76 |
White dimming value |
1 byte |
C,T |
||||
73 |
Brightness value |
1 byte |
C,T |
Colour temperature control |
5.001 percentage(0..100%) |
||
74 |
Colour temperature value |
2 byte |
C,T |
7.600 absolute colour temperature |
|||
73 |
Setpoint output |
2 byte |
C,T |
When operating the button, the temperature setpoint is lowered. |
Temperature decrease |
9.001 temperature (°C) |
|
74 |
Setpoint input |
2 byte |
C,W,T,U |
The temperature setpoint is received from the bus and a read request is sent at power-up. |
|||
73 |
Setpoint output |
2 byte |
C,T |
When operating the button, the reference temperature difference is lowered. |
9.002 temperature difference (K) |
||
74 |
Setpoint input |
2 byte |
C,W,T,U |
The reference temperature difference value is received from the bus and a read request is sent at power-up |
|||
73 |
Setpoint output |
1 byte |
C,T |
When the button is operated, the reference temperature difference is lowered. |
6.010 counter pulse (-128..127) |
||
74 |
Setpoint input |
1 byte |
C,W,T,U |
The reference temperature value is received from the bus, and a read request is sent on power-up. |
|||
73 |
Function 1 The name of the object refers to the parameter Name of the channel of the function. The name of the function changes with the parameter description. If the parameter description is empty, Function 1 displays by default. |
Setpoint output |
2 byte |
C,T |
When operating the button, the temperature setpoint is raised. |
Temperature increase |
9.001 temperature (°C) |
74 |
Setpoint input |
2 byte |
C,W,T,U |
The temperature setpoint is received from the bus and a read request is sent at power-up. |
|||
73 |
Setpoint output |
2 byte |
C,T |
When operating the button, the reference temperature difference is adjusted upwards. |
9.002 temperature difference (K) |
||
74 |
Setpoint input |
2 byte |
C,W,T,U |
The reference temperature difference value is received from the bus and a read request is sent at power-up. |
|||
Setpoint output |
1 byte |
C,T |
When the button is operated, the reference temperature difference is adjusted upward. |
6.010 counter pulse (-128..127) |
|||
Setpoint input |
1 byte |
C,W,T,U |
The reference temperature difference value is received from the bus, and a read request is sent on power-up. |
||||
77 |
Button Locking object |
1 bit |
C,W |
Visible when the locking function is enabled. When locked, the buttons are not operational and the specific value of the object is defined by the parameter |
Locking |
1.003 enable |
|
78 |
Status feedback object, Status feedback object value |
1 bit, 1 byte |
C,W,T,U |
1bit object type visible if the option is Status feedback object = On/Off. 1byte object type visible if the option is Status feedback object value = On/Off. |
1.001 switch 5.004 percentage (0..255%) |
||
79 – 84 |
Function 2 |
The same as function 1 |
|||||
85 – 90 |
Function 3 |
||||||
91 – 96 |
Function 4 |
||||||
97 – 102 |
Function 5 |
||||||
109 – 108 |
Function 6 |
||||||
109 – 114 |
Function 7 |
||||||
115 – 120 |
Function 8 |
Other Objects
Nr. |
Name |
Object function |
Length |
Properties |
Note |
Function description |
DPT |
---|---|---|---|---|---|---|---|
121 |
Middle field display line 1 |
Brightness level status feedback object |
1 byte |
C,W |
Visible if dimming level is enabled |
5.001 percentage (0..100%) |
|
122 |
Middle field display line 2 |
1 byte |
C,W |
||||
123 |
Middle field display line 3 |
1 byte |
C,W |
||||
124 |
Middle field display line 4 |
1 byte |
C,W |
||||
125 |
Night mode |
Night mode input |
1 bit |
C,W,T,U |
Visible when parameter Night mode is enabled |
1.024 day/night |
|
126 |
Proximity function |
Proximity input |
1 bit |
C,W |
Visible when parameter option How the Proximity function is triggered including Proximity object |
1.001 switch |
|
127 |
Proximity output |
1 bit, 1 byte |
C,T |
Visible according to the parameter option |
1.001 switch, 5.010 counter pulses |
||
128 |
Temperature measurement |
Actual temperature 2Byte |
2 byte |
C,R,T |
Displays according to parameter option. |
9.001 temperature (°C), 9.027 temperature (°F) |
|
129 |
Temperature measurement |
Actual temperature 4Byte |
4 byte |
C,R,T |
|||
130 |
General |
Live signal |
1 bit |
C,T |
1.001 switch |
||
131 |
Date |
3 byte |
C,W |
11.001 date |
|||
132 |
Time |
3 byte |
C,W |
10.001 time of day |
|||
138 |
External temperature sensor |
2 byte |
C,W,T,U |
Receives external temperature sensor measurements, sends periodic read requests, and sends power-ups. |
9.001 temperature |
||
139 |
Middle field display line 1 |
External actual temperature |
2 byte |
C,W,T,U |
Receives external temperature sensor measurements, sends periodic read requests, and sends power-ups. |
9.001 temperature |
|
140 |
Heating and Cooling mode |
1 bit |
C,W,T,U |
The heating/cooling mode is received from the bus and a read request is sent at power-up. |
1.100 cooling/heating |
||
141 |
Setpoint input |
2 byte |
C,W |
Receives the bus temperature setpoint. When there is data reception, the screen immediately switches to display the set temperature. After the delay it switches to the ambient temperature. |
9.001 temperature |
||
142 |
Middle field display line 2 |
External actual temperature |
2 byte |
C,W,T,U |
The same as Middle field display line 1 |
9.001 temperature |
|
143 |
Heating and Cooling mode |
1 bit |
C,W,T,U |
1.100 cooling/heating |
|||
144 |
Setpoint input |
2 byte |
C,W |
9.001 temperature |
|||
145 |
Middle field display line 3 |
External actual temperature |
2 byte |
C,W,T,U |
9.001 temperature |
||
146 |
Heating and Cooling mode |
1 bit |
C,W,T,U |
1.100 cooling/heating |
|||
147 |
Setpoint input |
2 byte |
C,W |
9.001 temperature |
|||
148 |
Middle field display line 4 |
External actual temperature |
2 byte |
C,W,T,U |
9.001 temperature |
||
149 |
Heating and Cooling mode |
1 bit |
C,W,T,U |
1.100 cooling/heating |
|||
150 |
Setpoint input |
2 byte |
C,W |
9.001 temperature |
Auxiliary function
Nr. |
Name |
Object function |
Length |
Properties |
DPT |
---|---|---|---|---|---|
133 |
Auxiliary function |
Switch object |
1 bit |
C,T |
1.001 switch |
134 |
Auxiliary function |
Switch status object |
1 bit |
C,W |
1.001 switch |
133 |
Auxiliary function |
Switch object |
1 bit |
C,T |
1.001 switch |
133 |
Auxiliary function |
Dimming object |
4 bit |
C,T |
3.007 dimming |
133 |
Auxiliary function |
Movement object |
1 bit |
C,T |
1.008 up/down |
134 |
Auxiliary function |
Stop/step |
1 bit |
C,T |
1.007 step |
135 |
Auxiliary function |
Last direction |
1 bit |
C,W |
1.008 up/down |
133 |
Auxiliary function |
Blind position |
1 byte |
C,T |
5.001 percentage (0..100%) 5.005 ratio (0..255) |
134 |
Auxiliary function |
Slat position |
1 byte |
C,T |
|
133 |
Auxiliary function |
Switch object Priority control object Dimming object Value object |
1 bit 2 bit 4 bit 1 byte 2 byte |
C,T |
1.001 switch 2.001 switch control 3.007 dimming 5.010 counter pulses 5.001 percentage (0..100%) 9.xx float value 8.001 pulse difference 7.001 pulse |
134 |
Auxiliary function |
Switch status object Priority control status object Dimming status object Value status object |
1 bit 2 bit 4 bit 1 byte 2 byte |
C,W |
|
133 |
Auxiliary function |
Scene object |
1 byte |
C,T |
17.001 scene number |
133 |
Auxiliary function |
RGB dimming value |
3 byte |
C,T |
232.600 RGB value 3 x (0..255) |
133 |
Auxiliary function |
RGBW dimming value |
6 byte |
C,T |
251.600 DPT Color RGBW |
133 |
Auxiliary function |
Red dimming value |
1 byte |
C,T |
5.001 percentage (0..100%) |
134 |
Auxiliary function |
Green dimming value |
1 byte |
C,T |
|
135 |
Auxiliary function |
Blue dimming value |
1 byte |
C,T |
|
136 |
Auxiliary function |
White dimming value |
1 byte |
C,T |
5.001 percentage (0..100%) |
133 |
Auxiliary function |
Brightness value |
1 byte |
C,T |
5.001 percentage (0..100%) |
134 |
Auxiliary function |
Color temperature value |
2 byte |
C,T |
7.600 absolute color temperature |
137 |
Auxiliary function |
Locking object |
1 bit |
C,W |
1.003 enable |