MicroLogic Active 测量可用性和显示
简介
可用的测量取决于 MicroLogic Active 控制单元的类型:
-
MicroLogic Active A/AP 控制单元仅测量电流。
-
MicroLogic Active E/EP/Ei 控制单元可测量电流和电压。
测量值可以显示:
-
在 MicroLogic Active 显示屏上
-
在 FDM121 显示器上
-
通过 Panel Server Zigbee 连接:在 Panel Server 网页上以及连接 Panel Server 的远程控制器上,通过 Zigbee 无线通讯(仅限 MicroLogic Active AP/EP 控制单元)
-
使用有线通讯网络在服务器或远程控制器上
-
IFE/EIFE 网页
下表列出了每种显示选项可适用的测量。
电流
|
测量 |
MicroLogic Active HMI |
FDM121 |
Panel Server Zigbee 连接 |
有线通讯网络 |
IFE/EIFE 网页 |
|---|---|---|---|---|---|
|
实时相电流值 I1、I2、I3 |
✔ |
✔ |
✔ |
✔ |
– |
|
最大相电流值 I1 Max、I2 Max、I3 Max |
✔ |
✔ |
– |
✔ |
– |
|
最小相电流值 I1 Min、I2 Min、I3 Min |
– |
– |
– |
✔ |
– |
|
实时中性线电流值 IN(1) |
✔ |
– |
✔ |
✔ |
– |
|
最大中性线电流值 IN MAX(1) |
✔ |
– |
– |
✔ |
– |
|
最小中性线电流值 IN Min(1) |
– |
– |
– |
✔ |
– |
|
实时平均电流值 I Avg(2) |
✔ |
✔ |
✔ |
✔ |
– |
|
最小平均电流值 Iavg MIN |
– |
– |
– |
✔ |
– |
|
实时接地故障电流值 Ig |
✔ |
✔ |
✔ |
✔ |
✔ |
|
接地故障电流最大值 Ig Max |
✔ |
✔ |
– |
✔ |
✔ |
|
接地故障电流最小值 Ig Min |
– |
– |
– |
✔ |
– |
|
(1) 适用于连接并配置有 ENCT 的 4 极断路器或 3 极断路器。 (2) 仅适用于 MicroLogic Active E/EP/Ei 控制单元。 |
|||||
电流不平衡 (MicroLogic Active E/EP/Ei)
|
测量 |
MicroLogic Active HMI |
FDM121 |
Panel Server Zigbee 连接 |
有线通讯网络 |
IFE/EIFE 网页 |
|---|---|---|---|---|---|
|
3 个相电流不平衡的实时最大值 I Unb |
✔ |
✔ |
✔ |
✔ |
– |
|
3 个最大相电流不平衡 I Unb Max 中的最大值 |
✔ |
✔ |
✔ |
✔ |
– |
电流需量 (MicroLogic Active E/EP/Ei)
|
测量 |
MicroLogic Active HMI |
FDM121 |
Panel Server Zigbee 连接 |
有线通讯网络 |
IFE/EIFE 网页 |
|---|---|---|---|---|---|
|
相(I1、I2、I3)电流需用值 |
– |
✔ |
✔ |
✔ |
– |
|
相 (Iavg) 电流需量值 |
– |
– |
✔ |
– |
– |
|
相(I1、I2、I3)高峰电流需用值 |
– |
✔ |
✔ |
✔ |
✔ |
|
相 (Iavg) 峰值电流需量值 |
– |
– |
✔ |
– |
✔ |
|
中性线 (IN) 电流需用值(1) |
– |
– |
✔ |
✔ |
– |
|
中性线 (IN) 高峰电流需用值(1) |
– |
– |
✔ |
✔ |
✔ |
|
(1) 适用于连接并配置有 ENVT 的 4 极断路器或 3 极断路器。 |
|||||
运行指示灯 (MicroLogic Active E/EP/Ei)
|
测量 |
MicroLogic Active HMI |
FDM121 |
Panel Server Zigbee 连接 |
有线通讯网络 |
IFE/EIFE 网页 |
|---|---|---|---|---|---|
|
相位旋转 |
✔ |
– |
– |
– |
– |
|
负载类型 |
✔ |
– |
– |
– |
– |
电压 (MicroLogic Active E/EP/Ei)
|
测量 |
MicroLogic Active HMI |
FDM121 |
Panel Server Zigbee 连接 |
有线通讯网络 |
IFE/EIFE 网页 |
|---|---|---|---|---|---|
|
实时线电压值 V12、V23、V31 |
✔ |
✔ |
✔ |
✔ |
– |
|
线电压最大值 V12 MAX、V23 MAX、V31 MAX |
✔ |
✔ |
– |
✔ |
– |
|
线电压最小值 V12 MIN、V23 MIN、V31 MIN |
✔ |
✔ |
– |
✔ |
– |
|
实时相电压 V1N、V2N、V3N(1) |
✔ |
✔ |
✔ |
✔ |
– |
|
相电压最大值 V1N MAX、V2N MAX、V3N MAX(1) |
✔ |
✔ |
– |
✔ |
– |
|
相电压最小值 V1N MIN、V2N MIN、V3N MIN(1) |
✔ |
✔ |
– |
✔ |
– |
|
实时平均线电压 Vavg LL |
✔ |
✔ |
– |
✔ |
– |
|
实时平均相电压 Vavg LN(1) |
✔ |
✔ |
– |
✔ |
– |
|
(1) 适用于连接并配置有 ENVT 的 4 极断路器或 3 极断路器。 |
|||||
电压不平衡 (MicroLogic Active E/EP/Ei)
|
测量 |
MicroLogic Active HMI |
FDM121 |
Panel Server Zigbee 连接 |
有线通讯网络 |
IFE/EIFE 网页 |
|---|---|---|---|---|---|
|
3 个线电压不平衡的实时最大值 VLL Unb |
✔ |
✔ |
✔ |
✔ |
– |
|
3 个相电压不平衡的实时最大值 VLN Unb(1) |
✔ |
✔ |
✔ |
✔ |
– |
|
3 个最大线电压不平衡 VLL Unb Max 中的最大值 |
✔ |
✔ |
✔ |
✔ |
– |
|
3 个最大相电压不平衡 VLN Unb Max 中的最大值(1) |
✔ |
✔ |
✔ |
✔ |
– |
|
实时线电压不平衡 V12unbal、V23unbal、V31unbal |
– |
– |
✔ |
✔ |
– |
|
实时相电压不平衡 V1Nunbal、V2Nunbal、V3Nunbal(1) |
– |
– |
✔ |
✔ |
– |
|
(1) 适用于连接并配置有 ENVT 的 4 极断路器或 3 极断路器。 |
|||||
功率 (MicroLogic Active E/EP/Ei)
|
测量 |
MicroLogic Active HMI |
FDM121 |
Panel Server Zigbee 连接 |
有线通讯网络 |
IFE/EIFE 网页 |
|---|---|---|---|---|---|
|
各相实时有功功率 P1、P2、P3(1) |
✔ |
✔ |
✔ |
✔ |
– |
|
各相有功功率最大值 P1 MAX、P2 MAX、P3 MAX(1) |
✔ |
✔ |
– |
✔ |
– |
|
实时总有功功率 Ptot |
✔ |
✔ |
✔ |
✔ |
– |
|
总有功功率最大值 Ptot MAX |
✔ |
✔ |
– |
✔ |
– |
|
各相实时无功功率 Q1、Q2、Q3(1) |
✔ |
✔ |
✔ |
✔ |
– |
|
各相无功功率最大值 Q1 MAX、Q2 MAX、Q3 MAX(1) |
– |
✔ |
– |
✔ |
– |
|
实时总无功功率 Qtot |
✔ |
✔ |
✔ |
✔ |
– |
|
总无功功率最大值 Qtot MAX |
✔ |
✔ |
– |
✔ |
– |
|
各相实时视在功率 S1、S2、S3(1) |
✔ |
✔ |
✔ |
✔ |
– |
|
各相视在功率最大值 S1 MAX、S2 MAX、S3 MAX(1) |
✔ |
✔ |
– |
✔ |
– |
|
实时总视在功率 Stot |
✔ |
✔ |
✔ |
✔ |
– |
|
总视在功率最大值 Stot MAX |
✔ |
✔ |
– |
✔ |
– |
|
(1) 适用于连接并配置有 ENVT 的 4 极断路器或 3 极断路器。 |
|||||
功率需量 (MicroLogic Active E/EP/Ei)
|
测量 |
MicroLogic Active HMI |
FDM121 |
Panel Server Zigbee 连接 |
有线通讯网络 |
IFE/EIFE 网页 |
|---|---|---|---|---|---|
|
总有功功率需用值 |
– |
✔ |
✔ |
✔ |
– |
|
总峰值有功功率需用值 |
– |
✔ |
✔ |
✔ |
✔ |
|
总无功功率需用值 |
– |
✔ |
– |
✔ |
– |
|
总峰值无功功率需用值 |
– |
✔ |
– |
✔ |
✔ |
|
总视在功率需用值 |
– |
✔ |
– |
✔ |
– |
|
总峰值视在功率需用值 |
– |
✔ |
– |
✔ |
✔ |
功率因数 PF 和 cos φ (MicroLogic Active E/EP/Ei)
|
测量 |
MicroLogic Active HMI |
FDM121 |
Panel Server Zigbee 连接 |
有线通讯网络 |
IFE/EIFE 网页 |
|---|---|---|---|---|---|
|
实时总功率因数 PF |
✔ |
✔ |
✔ |
✔ |
– |
|
– |
✔ |
– |
✔ |
– |
|
实时总计 cos φ |
✔ |
✔ |
– |
– |
– |
|
– |
✔ |
– |
✔ |
– |
|
各相实时功率因数 PFA、PFB、PFC(1) |
– |
✔ |
✔ |
✔ |
– |
|
|
– |
✔ |
– |
✔ |
– |
|
(1) 适用于连接并配置有 ENVT 的 4 极断路器或 3 极断路器。 |
|||||
频率 (MicroLogic Active E/EP/Ei)
|
测量 |
MicroLogic Active HMI |
FDM121 |
Panel Server Zigbee 连接 |
有线通讯网络 |
IFE/EIFE 网页 |
|---|---|---|---|---|---|
|
频率 |
✔ |
✔ |
✔ |
✔ |
– |
|
最大频率 |
✔ |
– |
✔ |
✔ |
– |
|
最小频率 |
✔ |
– |
✔ |
✔ |
– |
可复位电能表 (MicroLogic Active E/EP/Ei)
|
测量 |
MicroLogic Active HMI |
FDM121 |
Panel Server Zigbee 连接 |
有线通讯网络 |
IFE/EIFE 网页 |
|---|---|---|---|---|---|
|
总有功电能值 Ep |
✔ |
✔ |
– |
✔ |
– |
|
总有功电能值:Ep delivered 和 Ep received |
✔ |
– |
✔ |
✔ |
– |
|
各相有功电能值:Ep1 delivered、Ep2 delivered、Ep3 delivered、Ep1 received、Ep2 received、Ep3 received |
– |
– |
✔ |
✔ |
✔ |
|
总无功电能值 Eq |
✔ |
✔ |
– |
✔ |
– |
|
总无功电能值:Eq delivered 和 Eq received |
✔ |
– |
✔ |
✔ |
– |
|
各相无功电能值:Eq1 delivered、Eq2 delivered、Eq3 delivered、Eq1 received、Eq2 received、Eq3 received |
– |
– |
✔ |
✔ |
✔ |
|
总视在电能值 Es |
✔ |
✔ |
✔ |
✔ |
– |
|
各相视在电能值 Es1、Es2、Es3 |
– |
– |
✔ |
✔ |
– |