Modbus TCP/IP Client (Universal and Advanced Models)
Presentation
The Panel Server acts as both a Modbus TCP/IP gateway and a Modbus device by using the internal Modbus TCP server.
To correctly configure your Modbus TCP/IP client to access data from Panel Server and from devices under Panel Server, see Modbus Gateway Function.
The Panel Server acts as a Modbus gateway for wired or wireless Ethernet communications from an upstream PC to Ethernet devices and field devices on the downstream network. By using a local monitoring software you can access information from devices for data collection and other functions.
The Panel Server manages Modbus communication on all interfaces including Wi-Fi.
For more information, see Modbus TCP/IP functions and Modbus TCP/IP exception codes in appendix.
Availability
This function is available on Panel Server Universal and Advanced.
Setting the Parameters
NOTICE |
---|
IMPAIRED NETWORK PERFORMANCE
Only qualified personnel should modify the Modbus TCP/IP
settings. Perform such modifications only after you have read about
and understood the Modbus TCP/IP settings.
Failure to follow these instructions can result in loss
of network connectivity.
|
-
With EcoStruxure Power Commission software
-
On the Panel Server webpages, at .
For information about the Modbus registers, see the guide of each Modbus-SL device and DOCA0241EN EcoStruxure Panel Server - Modbus File for wireless devices.
Modbus TCP/IP Client Settings
The following table describes the settings and where they are available.
Parameter | Description | EPC software | Webpages |
---|---|---|---|
Connection timeout (s) |
Used to set the length of time the Panel Server will wait for a remote Modbus TCP/IP device to establish the connection with the Panel Server. Values from 0.1 to 10 seconds (default setting: 2 seconds) |
✔ | ✔ |
Message timeout (s) |
Used to set the length of time the Panel Server will wait for a remote Modbus TCP/IP device to respond and send a message following a Modbus TCP/IP request initiated by the Panel Server. Values from 1 to 20 seconds (default setting: 3 seconds) |
– | ✔ |
For recommendations and more information about setting the message timeout parameter, refer to Setting Message Timeout for Modbus Client and Server.