PowerTag Data Availability
Presentation
The data transmitted by the PowerTag Energy sensors to the PowerTag Link gateway depends on the type of PowerTag Energy sensors. The following tables indicate which data are available in the PowerTag Link gateway according to the type of PowerTag Energy sensors.
Device Commercial References
The device commercial references used for each type of PowerTag Energy sensors are:
-
A1: A9MEM1520, A9MEM1521, A9MEM1522, A9MEM1541, A9MEM1542
-
A2: A9MEM1540, A9MEM1543
-
P1: A9MEM1561, A9MEM1562, A9MEM1563, A9MEM1571, A9MEM1572
-
F1: A9MEM1560, A9MEM1570
-
F2: A9MEM1573
-
F3: A9MEM1564, A9MEM1574
-
FL: A9MEM1580
-
M0: LV434020
-
M1: LV434021
-
M2: LV434022
-
M3: LV434023
-
R1: A9MEM1590, A9MEM1591, A9MEM1592, A9MEM1593
Power
Data |
PowerTag M63 |
PowerTag P63 |
PowerTag F63 |
PowerTag F160 |
PowerTag M250 |
PowerTag M630 |
PowerTag Rope |
|||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
A1 |
A2 |
P1 |
F1 |
F2 |
F3 |
FL |
M0 |
M1 |
M2 |
M3 |
R1 |
|
Total active power |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Per phase active power |
✔ |
NA(1) |
✔ |
✔ |
NA(1) |
✔ |
✔(2) |
✔(2) |
✔ |
✔(2) |
✔ |
✔(2) |
Total reactive power |
– |
– |
– |
– |
– |
– |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Per phase reactive power |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Total apparent power |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Per phase apparent power |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Total factor power |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Per phase factor power |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Actual demand power |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
– |
– |
– |
– |
✔ |
Peak demand power |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
– |
– |
– |
– |
✔ |
(1) Not applicable because there is no neutral voltage on the PowerTag Energy sensors. (2) The values are significant only if the neutral voltage picking is connected. |
Energy
Data |
PowerTag M63 |
PowerTag P63 |
PowerTag F63 |
PowerTag F160 |
PowerTag M250 |
PowerTag M630 |
PowerTag Rope |
|||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
A1 |
A2 |
P1 |
F1 |
F2 |
F3 |
FL |
M0 |
M1 |
M2 |
M3 |
R1 |
|
Total resettable active energy delivered |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Total non resettable active energy delivered |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Per phase resettable active energy delivered |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Per phase non resettable active energy delivered |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Total resettable active energy received |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Total non resettable active energy received |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Per phase resettable active energy received |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Per phase non resettable active energy received |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Total resettable active energy delivered and received |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Total non resettable active energy delivered and received |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Per phase resettable active energy delivered and received |
– |
– |
– |
– |
– |
– |
NA(1) |
– |
– |
– |
– |
NA(1) |
Per phase non resettable active energy delivered and received |
– |
– |
– |
– |
– |
– |
NA(1) |
✔(2) |
✔ |
✔(2) |
✔ |
NA(1) |
Total resettable reactive energy delivered |
– |
– |
– |
– |
– |
– |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Total non resettable reactive energy delivered |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Per phase resettable reactive energy delivered |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Per phase non resettable reactive energy delivered |
– |
– |
– |
– |
– |
– |
✔ |
– |
– |
– |
– |
✔ |
Total resettable reactive energy received |
– |
– |
– |
– |
– |
– |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Total non resettable reactive energy received |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Per phase resettable reactive energy received |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Per phase non resettable reactive energy received |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Total resettable apparent energy delivered and received |
– |
– |
– |
– |
– |
– |
✔ |
– |
– |
– |
– |
✔ |
Total non resettable apparent energy delivered and received |
– |
– |
– |
– |
– |
– |
✔ |
– |
– |
– |
– |
✔ |
Per phase resettable apparent energy delivered and received |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
Per phase non resettable apparent energy delivered and received |
– |
– |
– |
– |
– |
– |
✔(2) |
– |
– |
– |
– |
✔(2) |
(1) Not applicable because energy is individually cumulated in received and delivered counters. (2) The values are significant only if the neutral voltage picking is connected. |
Alarms
Data |
PowerTag M63 |
PowerTag P63 |
PowerTag F63 |
PowerTag F160 |
PowerTag M250 |
PowerTag M630 |
PowerTag Rope |
|||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
A1 |
A2 |
P1 |
F1 |
F2 |
F3 |
FL |
M0 |
M1 |
M2 |
M3 |
R1 |
|
Voltage loss |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Overcurrent at voltage loss |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Load current 45% |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Load current loss |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Over oltage 120% |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Undervoltage 80% |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
RMS current on phase A, B, C at voltage loss |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Other Measurements
Data |
PowerTag M63 |
PowerTag P63 |
PowerTag F63 |
PowerTag F160 |
PowerTag M250 |
PowerTag M630 |
PowerTag Rope |
|||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
A1 |
A2 |
P1 |
F1 |
F2 |
F3 |
FL |
M0 |
M1 |
M2 |
M3 |
R1 |
|
Phase current (measured) |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Neutral current (calculated) |
– |
– |
– |
– |
– |
– |
✔ |
– |
– |
– |
– |
✔ |
Phase-to-phase voltage |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Phase-to-neutral voltage |
✔ |
NA(1) |
✔ |
✔ |
NA(1) |
✔ |
✔(2) |
✔(2) |
✔ |
✔(2) |
✔ |
✔(2) |
Frequency |
– |
– |
– |
– |
– |
– |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Quadrant |
1 |
1 |
1 |
1 |
1 |
1 |
4 |
4 |
4 |
4 |
4 |
4 |
Internal temperature |
– |
– |
– |
– |
– |
– |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
Load operating time counter |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
(1) Not applicable because there is no neutral voltage on the PowerTag Energy sensors. (2) The values are significant only if the neutral voltage picking is connected. |