DOCA0157EN-08

PowerTag Energy Sensors Modbus Registers

Applicable Devices

The code in the Applicable Devices column indicates the types of PowerTag Energy sensors for which the register is available:

  • A: the register is available for PowerTag Energy ●63 (A9MEM152●, A9MEM154●, A9MEM156●, and A9MEM157●)

  • M: the register is available for PowerTag Energy M250/M630 (LV43402●)

  • R: the register is available for PowerTag Energy F160 (A9MEM1580) and Rope (A9MEM159●)

Current Metering Data

Address

Register

No.

RW

X

Unit

Type

Range

Invalid Value

Svd

Function Code

Applicable Devices

Description

0x0BB7

3000

2

R

A

Float32

0xFFC00000

N

03,

100–4

A/M/R

RMS current on phase A

0x0BB9

3002

2

R

A

Float32

0xFFC00000

N

03,

100–4

A/M/R

RMS current on phase B

0x0BBB

3004

2

R

A

Float32

0xFFC00000

N

03,

100–4

A/M/R

RMS current on phase C

0x0BBD

3006

2

R

A

Float32

0xFFC00000

N

03,

100–4

R

RMS current on Neutral

Voltage Metering Data

Address

Register

No.

RW

X

Unit

Type

Range

Invalid Value

Svd

Function Code

Applicable Devices

Description

0x0BCB

3020

2

R

V

Float32

0xFFC00000

N

03,

100–4

A/M/R

RMS phase-to-phase voltage A-B

0x0BCD

3022

2

R

V

Float32

0xFFC00000

N

03,

100–4

A/M/R

RMS phase-to-phase voltage B-C

0x0BCF

3024

2

R

V

Float32

0xFFC00000

N

03,

100–4

A/M/R

RMS phase-to-phase voltage C-A

0x0BD1

3026

2

Reserved

0x0BD3

3028

2

R

V

Float32

0xFFC00000

N

03,

100–4

A/M/R

RMS phase-to-neutral voltage A-N

0x0BD5

3030

2

R

V

Float32

0xFFC00000

N

03,

100–4

A/M/R

RMS phase-to-neutral voltage B-N

0x0BD7

3032

2

R

V

Float32

0xFFC00000

N

03,

100–4

A/M/R

RMS phase-to-neutral voltage C-N

Power Metering Data

Address

Register

No.

RW

X

Unit

Type

Range

Invalid Value

Svd

Function Code

Applicable Devices

Description

0x0BED

3054

2

R

W

Float32

0xFFC00000

N

03,

100–4

A/M/R

Active power on phase A

0x0BEF

3056

2

R

W

Float32

0xFFC00000

N

03,

100–4

A/M/R

Active power on phase B

0x0BF1

3058

2

R

W

Float32

0xFFC00000

N

03,

100–4

A/M/R

Active power on phase C

0x0BF3

3060

2

R

W

Float32

0xFFC00000

N

03,

100–4

A/M/R

total active power

0x0BF5

3062

2

R

VAR

Float32

0xFFC00000

N

03,

100–4

R

Reactive power on phase A

0x0BF7

3064

2

R

VAR

Float32

0xFFC00000

N

03,

100–4

R

Reactive power on phase B

0x0BF9

3066

2

R

VAR

Float32

0xFFC00000

N

03,

100–4

R

Reactive power on phase C

0x0BFB

3068

2

R

-

Var

Float32

-

0xFFC00000

N

03,

100–4

M/R

Total reactive power

0x0BFD

3070

2

R

VA

Float32

0xFFC00000

N

03,

100–4

R

Apparent power on phase A

0x0BFF

3072

2

R

VA

Float32

0xFFC00000

N

03,

100–4

R

Apparent power on phase B

0x0C01

3074

2

R

VA

Float32

0xFFC00000

N

03,

100–4

R

Apparent power on phase C

0x0C03

3076

2

R

-

VA

Float32

-

0xFFC00000

N

03,

100–4

A/M/R

Total apparent power (arithmetric)

Power Factor Metering Data

Address

Register

No.

RW

X

Unit

Type

Range

Invalid Value

Svd

Function Code

Applicable Devices

Description

0x0C05

3078

2

R

Float32

0xFFC00000

N

03,

100–4

R

Power factor on phase A

0x0C07

3080

2

R

Float32

0xFFC00000

N

03,

100–4

R

Power factor on phase B

0x0C09

3082

2

R

Float32

0xFFC00000

N

03,

100–4

R

Power factor on phase C

0x0C0B

3084

2

R

Float32

0xFFC00000

N

03,

100–4

A/M/R

Total power factor

0x0C0D

3086

1

R

UINT16

0xFFFF

N

03,

100–4

R

Power factor sign convention

0 = IEC

1 = IEEE

Frequency Metering Data

Address

Register

No.

RW

X

Unit

Type

Range

Invalid Value

Svd

Function Code

Applicable Devices

Description

0x0C25

3110

2

R

Hz

Float32

0xFFC00000

N

03,

100–4

M/R

AC frequency

Device Temperature Metering Data

Address

Register

No.

RW

X

Unit

Type

Range

Invalid Value

Svd

Function Code

Applicable Devices

Description

0x0C3B

3132

2

R

°C

Float32

0xFFC00000

N

03,

100–4

M/R

Device internal temperature

Energy Data

Address

Register

No.

RW

X

Unit

Type

Range

Invalid Value

Svd

Function Code

Applicable Devices

Description

0x0C83

3204

4

R

-

Wh

INT64

-

0x8000000000000000

Y

03

A/M/R

Total active energy delivered + received (not resettable)

0x0C87

3208

4

R

Wh

INT64

0x8000000000000000

Y

03

A/M/R

Total active energy delivered count positively (not resettable)

0x0C8B

3212

4

R

Wh

INT64

0x8000000000000000

Y

03

A/M/R

Total active energy received (not resettable)

Address

Register

No.

RW

X

Unit

Type

Range

Invalid Value

Svd

Function Code

Applicable Devices

Description

0x0C8F

3216

4

R

Wh

INT64

0x8000000000000000

Y

03

M

Active energy on phase A delivered - received (not resettable)

0x0C93

3220

4

R

Wh

INT64

0x8000000000000000

Y

03

M

Active energy on phase B delivered - received (not resettable)

0x0C97

3224

4

R

Wh

INT64

0x8000000000000000

Y

03

M

Active energy on phase C delivered - received (not resettable)

0x09CB

3228

28

Reserved

0x0CB7

3256

4

R

-

Wh

INT64

-

0x8000000000000000

Y

03

A/M/R

Partial active energy delivered + received (resettable)

0x0CBB

3260

4

RW

-

Wh

INT64

-

0x8000000000000000

N

03, 16

A/M/R

Set partial active energy counter. The value returns to zero by PowerTag Link gateway.

0x0CBF

3264

4

R

Wh

INT64

0x8000000000000000

Y

03

A/M/R

Partial active energy delivered (resettable)

0x0CC3

3268

4

RW

Wh

INT64

0x8000000000000000

N

03, 16

A/M/R

Set partial active energy delivered counter. The value returns to zero by PowerTag Link gateway.

0x0CC7

3272

4

R

Wh

INT64

0x8000000000000000

Y

03

A/M/R

Partial active energy received (resettable)

0x0CCB

3276

4

RW

Wh

INT64

0x8000000000000000

N

03, 16

A/M/R

Set partial active energy received counter. The value returns to zero by PowerTag Link gateway.

0x0CCF

3280

4

R

VARh

INT64

0x8000000000000000

Y

03

M/R

Partial reactive energy delivered (resettable)

0x0CD3

3284

4

RW

VARh

INT64

0x8000000000000000

N

03, 16

M/R

Set partial reactive energy delivered counter. The value returns to zero by PowerTag Link gateway.

Address

Register

No.

RW

X

Unit

Type

Range

Invalid Value

Svd

Function Code

Applicable Devices

Description

0x0CD7

3288

4

R

VARh

INT64

0x8000000000000000

Y

03

M/R

Partial reactive energy received (resettable)

0x0CDB

3292

4

RW

VARh

INT64

0x8000000000000000

N

03, 16

M/R

Set partial reactive energy received counter. The value returns to zero by PowerTag Link gateway.

0x1390

5009

4

RW

Wh

INT64

0x8000000000000000 

Y

03, 16

A/R

Active energy delivered (resettable)

0x1394

5013

4

R

Wh

INT64

0x8000000000000000 

Y

03

A/R

Active energy delivered count positively (not resettable)

0x1398

5017

4

RW

Wh

INT64

0x8000000000000000 

Y

03, 16

A/R

Active energy received (resettable)

0x139C

5021

4

R

Wh

INT64

0x8000000000000000 

Y

03

A/R

Active energy received count negatively (not resettable)

0x13A0

5025

24

Reserved

0x13B8

5049

4

RW

Wh

INT64

0x8000000000000000 

Y

03, 16

R

Active energy on phase A delivered (resettable)

0x13BC

5053

4

R

Wh

INT64

0x8000000000000000 

Y

03

R

Active energy on phase A delivered (not resettable)

0x13C0

5057

4

RW

Wh

INT64

0x8000000000000000 

Y

03, 16

R

Active energy on phase A received (resettable)

0x13C4

5061

4

R

Wh

INT64

0x8000000000000000 

Y

03

R

Active energy on phase A received (not resettable)

0x13C8

5065

12

Reserved

0x13D4

5077

4

R

Wh

INT64

0x8000000000000000 

Y

03

R

Active energy on phase A delivered + received (not resettable)

0x13D8

5081

8

Reserved

Address

Register

No.

RW

X

Unit

Type

Range

Invalid Value

Svd

Function Code

Applicable Devices

Description

0x13E0

5089

4

RW

Wh

INT64

0x8000000000000000 

Y

03, 16

R

Active energy on phase B delivered (resettable)

0x13E4

5093

4

R

Wh

INT64

0x8000000000000000 

Y

03

R

Active energy on phase B delivered (not resettable)

0x13E8

5097

4

RW

Wh

INT64

0x8000000000000000 

Y

03, 16

R

Active energy on phase B received (resettable)

0x13EC

5101

4

R

Wh

INT64

0x8000000000000000 

Y

03

R

Active energy on phase B received (not resettable)

0x13F0

5105

24

Reserved

0x1408

5129

4

RW

Wh

INT64

0x8000000000000000 

Y

03, 16

R

Active energy on phase C delivered (resettable)

0x140C

5133

4

R

Wh

INT64

0x8000000000000000 

Y

03

R

Active energy on phase C delivered (not resettable)

0x1410

5137

4

RW

Wh

INT64

0x8000000000000000 

Y

03, 16

R

Active energy on phase C received (resettable)

0x1414

5141

4

R

Wh

INT64

0x8000000000000000 

Y

03

R

Active energy on phase C received (not resettable)

0x1418

5145

32

Reserved

0x1438

5177

4

RW

VARh

INT64

0x8000000000000000 

Y

03, 16

R

Reactive energy delivered (resettable)

0x143C

5181

4

R

VARh

INT64

0x8000000000000000 

Y

03

R

Reactive energy delivered count positively (not resettable)

0x1440

5185

8

Reserved

0x1488

5193

4

RW

VARh

INT64

0x8000000000000000 

Y

03, 16

R

Reactive energy received (resettable)

0x144C

5197

4

R

VARh

INT64

0x8000000000000000 

Y

03

R

Reactive energy received count negatively (not resettable)

0x1450

5201

32

Reserved

0x1470

5233

4

RW

VARh

INT64

0x8000000000000000 

Y

03, 16

R

Reactive energy on phase A delivered (resettable)

0x1474

5237

4

R

VARh

INT64

0x8000000000000000 

Y

03

R

Reactive energy on phase A delivered (not resettable)

0x1478

5241

4

RW

VARh

INT64

0x8000000000000000 

Y

03, 16

R

Reactive energy on phase A received (resettable)

0x147C

5245

4

R

VARh

INT64

0x8000000000000000 

Y

03

R

Reactive energy on phase A received (not resettable)

0x1480

5249

24

Reserved

0x1498

5273

4

RW

VARh

INT64

0x8000000000000000 

Y

03, 16

R

Reactive energy on phase B delivered (resettable)

0x149C

5277

4

R

VARh

INT64

0x8000000000000000 

Y

03

R

Reactive energy on phase B delivered (not resettable)

0x14A0

5281

4

RW

VARh

INT64

0x8000000000000000 

Y

03, 16

R

Reactive energy on phase B received (resettable)

0x14A4

5285

4

R

VARh

INT64

0x8000000000000000 

Y

03

R

Reactive energy on phase B received (not resettable)

0x14A8

5289

24

Reserved

0x14C0

5313

4

RW

VARh

INT64

0x8000000000000000 

Y

03, 16

R

Reactive energy on phase C delivered (resettable)

0x14C4

5317

4

R

VARh

INT64

0x8000000000000000 

Y

03

R

Reactive energy on phase C delivered (not resettable)

0x14C8

5321

4

RW

VARh

INT64

0x8000000000000000 

Y

03, 16

R

Reactive energy on phase C received (resettable)

0x14CC

5325

4

R

VARh

INT64

0x8000000000000000 

Y

03

R

Reactive energy on phase C received (not resettable)

0x14D0

5329

36

Reserved

Address

Register

No.

RW

X

Unit

Type

Range

Invalid Value

Svd

Function Code

Applicable Devices

Description

0x14F4

5365

4

RW

VAh

INT64

0x8000000000000000 

Y

03, 16

R

Apparent energy delivered + received (resettable)

0x14F8

5369

4

R

VAh

INT64

0x8000000000000000 

Y

03

R

Apparent energy delivered + received (not resettable)

0x14FC

5373

16

Reserved

0x150C

5389

4

RW

VAh

INT64

0x8000000000000000 

Y

03, 16

R

Apparent energy on phase A (resettable)

0x1510

5393

4

R

VAh

INT64

0x8000000000000000 

Y

03

R

Apparent energy on phase A (not resettable)

0x1514

5397

32

Reserved

0x1534

5429

4

RW

VAh

INT64

0x8000000000000000 

Y

03, 16

R

Apparent energy on phase B (resettable)

0x1538

5433

4

R

VAh

INT64

0x8000000000000000 

Y

03

R

Apparent energy on phase B (not resettable)

0x153C

5437

32

Reserved

0x155C

5469

4

RW

VAh

INT64

0x8000000000000000 

Y

03, 16

R

Apparent energy on phase C (resettable)

0x1560

5473

4

R

VAh

INT64

0x8000000000000000 

Y

03

R

Apparent energy on phase C (not resettable)

Power Demand Data

Address

Register

No.

RW

X

Unit

Type

Range

Invalid Value

Svd

Function Code

Applicable Devices

Description

0x0EB5

3766

2

R

W

Float32

0xFFC00000

N

03,

100–4

A/R

Demand total active power

0x0EB7

3768

2

Reserved

0x0EB9

3770

2

R

W

Float32

0xFFC00000

Y

03,

100–4

A/R

Maximum Demand total active power

0x0EBA

3771

1

Reserved

0x0EBB

3772

4

R

NA

DATETIME

0xFFFFFFFFFFFFFFFF

Y

03,

100–4

A/R

Maximum Demand total active power time stamp

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.