Table 128
For additional information and instructions for thermal units, see the previous sections Introduction through Mounting the Thermal Units in this chapter.
Thermal Unit — Table 128 | |
---|---|
Motor FLC (A) |
Thermal Unit Number |
7.88–8.91 |
B6.90 |
8.92–9.95 |
B7.70 |
9.96–10.57 |
B8.20 |
10.58–11.95 |
B9.10 |
11.96–13.79 |
B10.2 |
13.80–15.85 |
B11.5 |
15.86–17.43 |
B12.8 |
17.44–18.55 |
B14.0 |
18.56–20.5 |
B15.5 |
20.6–22.9 |
B17.5 |
23.0–24.7 |
B19.5 |
24.8–27.9 |
B22.0 |
28.0–31.7 |
B25.0 |
31.8–35.9 |
B28.0 |
36.0–39.9 |
B32.0 |
40.0–45.7 |
B36.0 |
45.8–50.9 |
B40.0 |
51.0–61.7 |
B45.0 |
61.8–65.1 |
B50.0 |
65.2–69.9 |
B56.0 |
70.0–79.5 |
B62.0 |
79.6–89.4 |
B70.0 |