Thermal Unit — Table 59 | ||
---|---|---|
Motor FLC (A) |
Thermal Unit Number |
|
1 or 2 T.U. |
3 T.U. |
|
0.34–0.38 |
0.29–0.31 |
B0.44 |
0.39–0.43 |
0.32–0.35 |
B0.51 |
0.44–0.47 |
0.36–0.38 |
B0.57 |
0.48–0.53 |
0.39–0.46 |
B0.63 |
0.54–0.60 |
0.47–0.55 |
B0.71 |
0.61–0.68 |
0.56–0.62 |
B0.81 |
0.69–0.76 |
0.63–0.67 |
B0.92 |
0.77–0.86 |
0.68–0.75 |
B1.03 |
0.87–0.97 |
0.76–0.84 |
B1.16 |
0.98–1.07 |
0.85–0.95 |
B1.30 |
1.08–1.23 |
0.96–1.09 |
B1.45 |
1.24–1.39 |
1.10–1.21 |
B1.67 |
1.40–1.55 |
1.22–1.35 |
B1.88 |
1.56–1.77 |
1.36–1.53 |
B2.10 |
1.78–1.96 |
1.54–1.73 |
B2.40 |
1.97–2.15 |
1.74–1.90 |
B2.65 |
2.16–2.41 |
1.91–2.14 |
B3.00 |
2.42–2.71 |
2.15–2.34 |
B3.30 |
2.72–3.03 |
2.35–2.67 |
B3.70 |
3.04–3.53 |
2.68–3.22 |
B4.15 |
3.54–4.01 |
3.23–3.48 |
B4.85 |
4.02–4.56 |
3.49–3.87 |
B5.50 |
4.57–5.03 |
3.88–4.14 |
B6.25 |
5.04–5.59 |
4.15–4.73 |
B6.90 |
5.60–5.95 |
4.74–5.28 |
B7.70 |
5.96–6.58 |
5.29–5.64 |
B8.20 |
6.59–7.31 |
5.65–6.39 |
B9.10 |
7.32–8.15 |
6.40–7.43 |
B10.2 |
8.16–9.13 |
7.44–8.55 |
B11.5 |
9.14–9.91 |
8.56–9.40 |
B12.8 |
9.92–10.7 |
9.41–10.0 |
B14.0 |
10.8–12.1 |
10.1–11.2 |
B15.5 |
12.2–13.5 |
11.3–12.5 |
B17.5 |
13.6–15.1 |
12.6–13.5 |
B19.5 |
15.2–17.0 |
13.6–15.4 |
B22.0 |
17.1–18.9 |
15.5–17.5 |
B25.0 |
19.0–21.5 |
17.6–19.9 |
B28.0 |
21.6–24.0 |
20.0–22.2 |
B32.0 |
24.1–26.0 |
22.3–25.5 |
B36.0 |
— |
25.6–26.0 |
B40.0 |