9065CT9701R03/21

Table 14

For additional information and instructions for thermal units, see the previous sections Introduction through Mounting the Thermal Units in this chapter.

Thermal Unit — Table 14

Motor FLC (A)

Thermal Unit Number

1.T.U.

2 T.U.

3 T.U.

0.43–0.47

0.41–0.45

0.40–0.41

A.49

0.48–0.51

0.46–0.50

0.42–0.46

A.54

0.52–0.56

0.51–0.55

0.47–0.51

A.59

0.57–0.64

0.56–0.62

0.52–0.57

A.65

0.65–0.69

0.63–0.67

0.58–0.62

A.71

0.70–0.76

0.68–0.72

0.63–0.67

A.78

0.77–0.84

0.73–0.81

0.68–0.75

A.86

0.85–0.91

0.82–0.88

0.76–0.80

A.95

0.92–1.01

0.89–0.97

0.81–0.89

A1.02

1.02–1.15

0.98–1.08

0.90–1.02

A1.16

1.16–1.23

1.09–1.18

1.03–1.09

A1.25

1.24–1.37

1.19–1.32

1.10–1.21

A1.39

1.38–1.45

1.33–1.40

1.22–1.29

A1.54

1.46–1.56

1.41–1.48

1.30–1.37

A1.63

1.57–1.67

1.49–1.60

1.38–1.48

A1.75

1.68–1.77

1.61–1.72

1.49–1.58

A1.86

1.78–1.92

1.73–1.84

1.59–1.72

A1.99

1.93–2.09

1.85–2.00

1.73–1.85

A2.15

2.10–2.31

2.01–2.22

1.86–2.05

A2.31

2.32–2.56

2.23–2.45

2.06–2.29

A2.57

2.57–2.92

2.46–2.82

2.30–2.62

A2.81

2.93–3.16

2.83–3.08

2.63–2.84

A3.61

3.17–3.48

3.09–3.39

2.85–3.10

A3.95

3.49–3.83

3.40–3.75

3.11–3.46

A4.32

3.84–4.24

3.76–4.16

3.47–3.85

A4.79

4.25–4.62

4.17–4.51

3.86–4.16

A5.30

4.63–4.92

4.52–4.83

4.17–4.46

A5.78

4.93–5.61

4.84–5.49

4.47–5.08

A6.20

5.62–5.85

5.50–5.67

5.09–5.35

A6.99

5.86–6.36

5.68–6.16

5.36–5.82

A7.65

6.37–6.99

6.17–6.75

5.83–6.34

A8.38

7.00–7.67

6.76–7.00

6.35–6.95

A9.25

7.68–8.15

6.96–7.00

A9.85

8.16–9.00

A11.0

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.