Table 89
For additional information and instructions for thermal units, see the previous sections Introduction through Mounting the Thermal Units in this chapter.
| Thermal Unit — Table 89 | |
|---|---|
|
Motor FLC (A) |
Thermal Unit Number |
|
10.0–11.1 |
B17.5 |
|
11.2–12.0 |
B19.5 |
|
12.1–13.3 |
B22.0 |
|
13.4–15.1 |
B25.0 |
|
15.2–17.1 |
B28.0 |
|
17.2–18.6 |
B32.0 |
|
18.7–21.4 |
B36.0 |
|
21.5–25.7 |
B40.0 |
|
25.8–28.2 |
B45.0 |
|
28.3–29.7 |
B50.0 |
|
29.8–31.2 |
B56.0 |
|
31.3–32.1 |
B62.0 |
|
32.2–35.7 |
B70.0 |
|
35.8–40.7 |
B79.0 |
|
40.8–48.0 |
B88.0 |