1st telegram information
|
Byte No |
Size |
Value |
Description |
|---|---|---|---|
|
1 |
1 |
68 |
Start character |
|
2 |
1 |
F4 |
L-field, calculated from C field to last user data |
|
3 |
1 |
F4 |
L-field, repeated |
|
4 |
1 |
68 |
Start character |
|
5 |
1 |
08 |
C-field, RSP_UD |
|
6 |
1 |
XX |
A-field, address |
|
7 |
1 |
72 |
CI-field, variable data respond, LSB first |
|
8 – 11 |
4 |
XXXX |
Identification number, 8 BCD digits |
|
12 – 13 |
2 |
4CA3 |
Manufacturer: SCH |
|
14 |
1 |
00 |
Version |
|
15 |
1 |
02 |
Medium, 02 = Electricity |
|
16 |
1 |
X |
Number of accesses |
|
17 |
1 |
X |
Status |
|
18 – 19 |
2 |
0000 |
Signature (0000 = no encryption) |
|
20 |
1 |
0D |
DIF size, special function |
|
21 |
1 |
FD |
VIF extension of VIF-codes |
|
22 |
1 |
0A |
Manufacturer name |
|
23 |
1 |
12 |
String length |
|
24 – 41 |
18 |
XXXXXXXXXXXXXXXXXX |
Schneider Electric |
|
42 |
1 |
0D |
DIF size, special function |
|
43 |
1 |
0D |
VIF extension of VIF-codes |
|
44 |
1 |
FD |
Model |
|
45 – 53 |
9 |
0C |
Meter model |
|
54 |
1 |
XXXXXXXXX |
DIF size, special function |
|
55 |
1 |
0D |
VIF extension of VIF-codes |
|
56 |
1 |
FD |
Firmware version |
|
57 – 64 |
8 |
0E |
Meter Firmware version |
|
65 |
1 |
XXXXXXXX |
DIF size, 24 Bit Integer |
|
66 |
1 |
03 |
VIF extension of VIF-codes |
|
67 |
1 |
FD |
Error flags |
|
68 – 70 |
3 |
17 |
Error flags (Diagnostics active bitmaps(1)) |
|
71 |
1 |
XXX |
DIF size, 32 Bit Real |
|
72 |
1 |
05 |
VIF extension of VIF-codes |
|
73 |
1 |
FD |
Current |
|
74 |
1 |
DC |
VIF next byte is manufacturer specific |
|
75 |
1 |
FF |
L1 |
|
76 – 79 |
4 |
01 |
Current per phase,I1 |
|
80 |
1 |
XXXX |
DIF size, 32 Bit Real |
|
81 |
1 |
05 |
VIF extension of VIF-codes |
|
82 |
1 |
FD |
Current |
|
83 |
1 |
DC |
VIF next byte is manufacturer specific |
|
84 |
1 |
FF |
L2 |
|
85 – 88 |
4 |
02 |
Current per phase,I2 |
|
89 |
1 |
XXXX |
DIF size, 32 Bit Real |
|
90 |
1 |
05 |
VIF extension of VIF-codes |
|
91 |
1 |
FD |
Current |
|
92 |
1 |
DC |
VIF next byte is manufacturer specific |
|
93 |
1 |
FF |
L3 |
|
94 – 97 |
4 |
03 |
Current per phase,I3 |
|
98 |
1 |
XXXX |
DIF size, 32 Bit Real |
|
99 |
1 |
05 |
VIF extension of VIF-codes |
|
100 |
1 |
FD |
Current |
|
101 |
1 |
DC |
VIF next byte is manufacturer specific |
|
102 |
1 |
FF |
Average |
|
103 – 106 |
4 |
00 |
Average current |
|
107 |
1 |
XXXX |
DIF size, 32 Bit Real |
|
108 |
1 |
05 |
VIF extension of VIF-codes |
|
109 |
1 |
FD |
Voltage |
|
110 |
1 |
C9 |
VIF next byte is manufacturer specific |
|
111 |
1 |
FF |
L1-L2 |
|
112 – 115 |
4 |
05 |
Voltage,L1-L2 |
|
116 |
1 |
XXXX |
DIF size, 32 Bit Real |
|
117 |
1 |
05 |
VIF extension of VIF-codes |
|
118 |
1 |
C9 |
Voltage |
|
119 |
1 |
FF |
VIF next byte is manufacturer specific |
|
120 |
1 |
06 |
L2-L3 |
|
121 – 124 |
4 |
XXXX |
Voltage,L2-L3 |
|
125 |
1 |
05 |
DIF size, 32 Bit Real |
|
126 |
1 |
FD |
VIF extension of VIF-codes |
|
127 |
1 |
C9 |
Voltage |
|
128 |
1 |
FF |
VIF next byte is manufacturer specific |
|
129 |
1 |
07 |
L3-L1 |
|
130 – 133 |
4 |
XXXX |
Voltage,L3-L1 |
|
134 |
1 |
05 |
DIF size, 32 Bit Real |
|
135 |
1 |
FD |
VIF extension of VIF-codes |
|
136 |
1 |
C9 |
Voltage |
|
137 |
1 |
FF |
VIF next byte is manufacturer specific |
|
138 |
1 |
08 |
L-L Average |
|
139 – 142 |
4 |
XXXX |
Average voltage, L -L |
|
143 |
1 |
05 |
DIF size, 32 Bit Real |
|
144 |
1 |
FD |
VIF extension of VIF-codes |
|
145 |
1 |
C9 |
Voltage |
|
146 |
1 |
FF |
VIF next byte is manufacturer specific |
|
147 |
1 |
01 |
L1 |
|
148 – 151 |
4 |
XXXX |
Voltage, L1 |
|
152 |
1 |
05 |
DIF size, 32 Bit Real |
|
153 |
1 |
FD |
VIF extension of VIF-codes |
|
154 |
1 |
C9 |
Voltage |
|
155 |
1 |
FF |
VIF next byte is manufacturer specific |
|
156 |
1 |
02 |
L2 |
|
157 – 160 |
4 |
XXXX |
Voltage, L2 |
|
161 |
1 |
05 |
DIF size, 32 Bit Real |
|
162 |
1 |
FD |
VIF extension of VIF-codes |
|
163 |
1 |
C9 |
Voltage |
|
164 |
1 |
FF |
VIF next byte is manufacturer specific |
|
165 |
1 |
03 |
L3 |
|
166 – 169 |
4 |
XXXX |
Voltage, L3 |
|
170 |
1 |
05 |
DIF size, 32 Bit Real |
|
171 |
1 |
FD |
VIF extension of VIF-codes |
|
172 |
1 |
C9 |
Voltage |
|
173 |
1 |
FF |
VIF next byte is manufacturer specific |
|
174 |
1 |
04 |
L-N, average |
|
175 – 178 |
4 |
XXXX |
Average, L-N |
|
179 |
1 |
05 |
DIF size, 32 Bit Real |
|
180 |
1 |
AE |
Power |
|
181 |
1 |
FF |
VIF next byte is manufacturer specific |
|
182 |
1 |
01 |
L1 |
|
183 – 186 |
4 |
XXXX |
Power,L1 |
|
187 |
1 |
05 |
DIF size, 32 Bit Real |
|
188 |
1 |
AE |
Power |
|
189 |
1 |
FF |
VIF next byte is manufacturer specific |
|
190 |
1 |
02 |
L2 |
|
191 – 194 |
4 |
XXXX |
Power,L2 |
|
195 |
1 |
05 |
DIF size, 32 Bit Real |
|
196 |
1 |
AE |
Power |
|
197 |
1 |
FF |
VIF next byte is manufacturer specific |
|
198 |
1 |
03 |
L3 |
|
199 – 202 |
4 |
XXXX |
Power,L3 |
|
203 |
1 |
05 |
DIF size, 32 Bit Real |
|
204 |
1 |
2E |
Power |
|
205 – 208 |
4 |
XXXX |
Total power |
|
209 |
1 |
85 |
DIF size, 32 Bit Real |
|
210 |
1 |
40 |
DIFE: Unit 1 |
|
211 |
1 |
2E |
Power |
|
212 – 215 |
4 |
XXXX |
Reactive power |
|
216 |
1 |
85 |
DIF size, 32 Bit Real |
|
217 |
1 |
80 |
DIFE |
|
218 |
1 |
40 |
DIFE: Unit 2 |
|
219 |
1 |
2E |
Power |
|
220 – 223 |
4 |
XXXX |
Apparent power |
|
224 |
1 |
05 |
DIF size, 32 Bit Real |
|
225 |
1 |
FF |
VIF next byte is manufacturer specific |
|
226 |
1 |
0A |
Power factor |
|
227 – 230 |
4 |
XXXX |
Power factor value |
|
231 |
1 |
05 |
DIF size, 32 Bit Real |
|
232 |
1 |
FF |
VIF next byte is manufacturer specific |
|
233 |
1 |
0B |
Frequency |
|
234 – 237 |
4 |
XXXX |
Frequency value |
|
238 |
1 |
07 |
DIF size, 64 Bit Integer |
|
239 |
1 |
03 |
Energy |
|
240 – 247 |
8 |
XXXXXXXX |
Total Active Energy Import |
|
248 |
1 |
1F |
DIF, more records will follow in next telegram |
|
249 |
1 |
X |
CS checksum, calculated from C field to last data |
|
250 |
1 |
16 |
Stop character |
- 0 = Inactive
- 1 = Active
- Bit0 = Code 101
- Bit1 = Code 102
- Bit2 = Code 201
- Bit3 = Code 202
- Bit4 = Code 203
- Bit5 = Code 204
- Bit6 = Code 205
- Bit7 = Code 206
- Bit8 = Code 207