2nd telegram information
|
Byte No |
Size |
Value |
Description |
|---|---|---|---|
|
1 |
1 |
68 |
Start character |
|
2 |
1 |
F6 |
L-field, calculated from C field to last user data |
|
3 |
1 |
F6 |
L-field, repeated |
|
4 |
1 |
68 |
Start character |
|
5 |
1 |
08 |
C-field, RSP_UD |
|
6 |
1 |
X |
A-field, address |
|
7 |
1 |
72 |
CI-field, variable data respond, LSB first |
|
8 – 11 |
4 |
XXXX |
Identification number, 8 BCD digits |
|
12 – 13 |
2 |
4CA3 |
Manufacturer: SCH |
|
14 |
1 |
00 |
Version |
|
15 |
1 |
02 |
Medium, 02 = Electricity |
|
16 |
1 |
X |
Number of accesses |
|
17 |
1 |
00 |
Status |
|
18 – 19 |
2 |
0000 |
Signature (0000 = no encryption) |
|
20 |
1 |
07 |
DIF size, 64 Bit Integer |
|
21 |
1 |
83 |
Energy |
|
22 |
1 |
FF |
VIF next byte is manufacturer specific |
|
23 |
1 |
09 |
Export energy |
|
24 – 31 |
8 |
XXXXXXXX |
Total Active Energy Export |
|
32 |
1 |
87 |
DIF size, 64 Bit Integer |
|
33 |
1 |
87 |
DIFE: Unit1 |
|
34 |
1 |
40 |
Energy |
|
35 – 42 |
8 |
03 |
Total Reactive Energy Import |
|
43 |
1 |
XXXXXXXX |
DIF size, 64 Bit Integer |
|
44 |
1 |
87 |
DIFE:Unit 1 |
|
45 |
1 |
40 |
Energy |
|
46 |
1 |
83 |
VIF next byte is manufacturer specific |
|
47 |
1 |
FF |
Export energy |
|
48 – 55 |
8 |
09 |
Total Reactive Energy Export |
|
56 |
1 |
XXXXXXXX |
DIF size, 32 Bit Integer |
|
57 |
1 |
04 |
Date/Time |
|
58 |
1 |
ED |
VIF next byte is manufacturer specific |
|
59 |
1 |
FF |
Energy Reset |
|
60 – 63 |
4 |
0C |
Energy Reset Date/Time |
|
64 |
1 |
XXXX |
DIF size, 64 Bit Integer |
|
65 |
1 |
07 |
Energy |
|
66 |
1 |
83 |
VIF next byte is manufacturer specific |
|
67 |
1 |
FF |
Partial energy |
|
68 – 75 |
8 |
0D |
Partial Active Energy Import |
|
76 |
1 |
XXXXXXXX |
DIF size, 64 Bit Integer |
|
77 |
1 |
87 |
DIFE: Unit 1 |
|
78 |
1 |
40 |
Energy |
|
79 |
1 |
83 |
VIF next byte is manufacturer specific |
|
80 |
1 |
FF |
Partial Energy |
|
81 – 88 |
8 |
0D |
Partial Reactive Energy Import |
|
89 |
1 |
XXXXXXXX |
DIF size, 64 Bit Integer |
|
90 |
1 |
07 |
Energy |
|
91 |
1 |
83 |
VIF next byte is manufacturer specific |
|
92 |
1 |
FF |
L1 |
|
93 – 100 |
8 |
01 |
Active Energy Delivered, L1 |
|
101 |
1 |
XXXXXXXX |
DIF size, 64 Bit Integer |
|
102 |
1 |
07 |
Energy |
|
103 |
1 |
83 |
VIF next byte is manufacturer specific |
|
104 |
1 |
FF |
L2 |
|
105 – 112 |
8 |
02 |
Active Energy Delivered, L2 |
|
113 |
1 |
XXXXXXXX |
DIF size, 64 Bit Integer |
|
114 |
1 |
07 |
Energy |
|
115 |
1 |
83 |
VIF next byte is manufacturer specific |
|
116 |
1 |
FF |
L3 |
|
117 – 124 |
8 |
03 |
Active Energy Delivered, L3 |
|
125 |
1 |
XXXXXXXX |
DIF size, 32 Bit Integer |
|
126 |
1 |
04 |
Date/Time |
|
127 |
1 |
ED |
VIF next byte is manufacturer specific |
|
128 |
1 |
0E |
Input metering reset |
|
129 – 132 |
4 |
XXXX |
Input Metering Accumulation Reset D/T |
|
133 |
1 |
07 |
DIF size, 64 Bit Integer |
|
134 |
1 |
FD |
VIF extension |
|
135 |
1 |
61 |
Input Metering Accumulation Channel 1 |
|
136 – 143 |
8 |
XXXXXXXX |
Input Metering Channel 1 Value |
|
144 |
1 |
03 |
DIF size, 24 Bit Integer |
|
145 |
1 |
FF |
VIF next byte is manufacturer specific |
|
146 |
1 |
10 |
Energy Active Rate |
|
147 – 149 |
3 |
XXX |
Energy Active Rate, Number |
|
150 |
1 |
87 |
DIF size, 64 Bit Integer |
|
151 |
1 |
10 |
DIFE: Tariff 1 |
|
152 |
1 |
03 |
Energy |
|
153 – 160 |
8 |
XXXXXXXX |
Active Energy Delivered Rate 1 |
|
161 |
1 |
87 |
DIF size, 64 Bit Integer |
|
162 |
1 |
20 |
DIFE: Tariff 2 |
|
163 |
1 |
03 |
Energy |
|
164 – 171 |
8 |
XXXXXXXX |
Active Energy Delivered Rate 2 |
|
172 |
1 |
87 |
DIF size, 64 Bit Integer |
|
173 |
1 |
30 |
DIFE: Tariff 3 |
|
174 |
1 |
03 |
Energy |
|
175 – 182 |
8 |
XXXXXXXX |
Active Energy Delivered Rate 3 |
|
183 |
1 |
87 |
DIF size, 64 Bit Integer |
|
184 |
1 |
80 |
DIFE: Tariff 4 |
|
185 |
1 |
10 |
DIFE: Tariff 4 |
|
186 |
1 |
03 |
Energy |
|
187 – 194 |
8 |
XXXXXXXX |
Active Energy Delivered Rate 4 |
|
195 |
1 |
04 |
DIF size, 32 Bit Integer |
|
196 |
1 |
6D |
Date/Time |
|
197 – 200 |
4 |
XXXX |
System date/time |
|
201 |
1 |
03 |
DIF size, 24 Bit Integer |
|
202 |
1 |
FF |
VIF next byte is manufacturer specific |
|
203 |
1 |
2C |
Energy pulse duration |
|
204 – 206 |
3 |
XXX |
Value, Energy pulse duration |
|
207 |
1 |
03 |
DIF size, 24 Bit Integer |
|
208 |
1 |
FF |
VIF next byte is manufacturer specific |
|
209 |
1 |
2D |
Digital output association |
|
210 – 212 |
3 |
XXX |
Value, Digital output association |
|
213 |
1 |
05 |
DIF size, 32 Bit Real |
|
214 |
1 |
FF |
VIF next byte is manufacturer specific |
|
215 |
1 |
2E |
Pulse weight |
|
216 – 219 |
4 |
XXXX |
Value, Pulse weight |
|
220 |
1 |
05 |
DIF size, 32 Bit Real |
|
221 |
1 |
FF |
VIF next byte is manufacturer specific |
|
222 |
1 |
2F |
Pulse constant |
|
223 – 226 |
4 |
XXXX |
Value, Pulse constant |
|
227 |
1 |
03 |
DIF size, 24 Bit Integer |
|
228 |
1 |
FF |
VIF next byte is manufacturer specific |
|
229 |
1 |
30 |
Digital input association |
|
230 – 232 |
3 |
XXX |
Value, Digital input association |
|
233 |
1 |
03 |
DIF size, 24 Bit Integer |
|
234 |
1 |
FD |
VIF extension |
|
235 |
1 |
1B |
Digital input control mode |
|
236 – 238 |
3 |
XXX |
Value, Digital input control mode |
|
239 |
1 |
02 |
DIF size, 16 Bit Integer |
|
240 |
1 |
FF |
VIF next byte is manufacturer specific |
|
241 |
1 |
32 |
Digital input status |
|
242 – 243 |
2 |
XX |
Value, Digital input status |
|
244 |
1 |
03 |
DIF size, 24 Bit Integer |
|
245 |
1 |
FD |
VIF extension |
|
246 |
1 |
1A |
Digital output control mode status |
|
247 – 249 |
3 |
XXX |
Value, Digital output control mode status |
|
250 |
1 |
1F |
DIF, more records will follow in next telegram |
|
251 |
1 |
X |
CS checksum, calculated from C field to last data |
|
252 |
1 |
16 |
Stop character |