Digital outputs
You can configure the digital outputs for use in the following applications:
-
switching applications, for example, to provide on/off control signals for switching capacitor banks, generators, and other external devices and equipment
-
demand synchronization applications, where the meter provides pulse signals to the input of another meter to control its demand period
-
energy pulsing applications, where a receiving device determines energy usage by counting the kWh pulses coming from the meter’s digital outputs
Refer to Device specifications for the voltage limits of the digital outputs. For higher voltage applications, use an external relay as the switching circuit.