Configuring input metering using the display
- Navigate to .
- Enter the setup passcode (default is “0”), then press OK.
- Navigate to .
- Move the cursor to point to the input metering channel you want to set up, then press Edit.
-
Move the cursor to the parameter you want to modify, then
press Edit.
NOTE: If Edit is not displayed, it means the parameter is either read-only or can only be modified through software.
- Modify the parameter as required, then press OK.
-
Press the up arrow to exit. Press Yes to save your changes.
Parameter Values Description Label — Use this field to change the default label and assign a descriptive name to this input metering channel.
Pulse Weight 0 to 99.99999 Use this field to specify the quantity or value each pulse represents.
Unit Code None, Wh, kWh, MWh, VARh, kVARh, MVARh, VAh, kVAh, MVAh, gal, BTU, L, m3, MCF, lbs, kg, klbs, Therm Select the unit of measurement associated with the monitored value.
Demand Code Varies (based on the units selected) For time-based values (such as kWh), this provides the associated demand units (kW) for demand calculations. For other values (such as kg), this can be configured to provide rate information (kg/h).
Mode Pulse, Transition Set Mode to Pulse to count only complete pulses. Set Mode to Transition to count each ON-to-OFF or OFF-to-ON status change.
Digital Inputs None, Digital input Select the digital input from the Available inputs box and use the right arrow button to assign the input metering channel to that digital input.