Supported BACnet features
The meter’s BACnet/IP protocol support is certified by BACnet International. Go to www.bacnetinternational.org or www.se.com and search for your meter model to access the PICS (Protocol Implementation Conformance Statement) for your meter.
Supported BACnet components
BACnet component | Description |
---|---|
Protocol version |
1 |
Protocol revision |
14 |
Standardized device profile (Annex L) |
BACnet Application Specific Controller (B-ASC) |
BACNet Interoperability Building Blocks (Annex K) |
|
BACnet/IP (Annex J) |
BACnet communication internet protocol |
Data link layer options |
UDP |
Character set ANSI |
X3.4/UTF-8 |
Supported services |
|
Segmentation |
The meter does not support segmentation |
Static device address binding |
The meter does not support static device address binding |
Networking options |
The meter supports registration as a foreign device |
Supported standard object types
Object type | Optional properties supported | Writeable properties supported | Conditional writeable properties supported |
---|---|---|---|
Device Object |
|
|
— |
Analog Input Object |
|
|
Present_Value |
Binary Input Object |
|
Out_Of_Service |
Present_Value |
Multi-state Input Object |
|
Out_Of_Service |
Present_Value |