Firmware upgrades
-
Improve meter performance (e.g., optimize processing speed)
-
Enhance existing meter features and functions
-
Add new functionality to the meter
-
Achieve compliance to new industry standards
-
Enhance meter Cybersecurity
Meter models, firmware versions and firmware upgrade methods
Meter models |
Source firmware version |
Target firmware version |
Firmware upgrade method via |
---|---|---|---|
PM5560 / PM5562 / PM5563 / PM5580 |
2.X.Y |
2.9.9 and earlier |
FTP server (Refer Firmware upgrade using FTP server) |
2.5.X to 2.9.9 |
4.0.X and above |
Firmware upgrade tool (Refer Firmware upgrade using firmware upgrade tool) NOTE:
If the meters are upgraded to their target firmware version, you
cannot go back (downgrade) to their source firmware version.
|
|
4.0.X and above |
4.X.Y and above |
Webpages (Refer Firmware upgrade using webpages) |
|
PM5570 / PM5660 / PM5760 |
3.1.X |
3.2.9 and earlier |
FTP server (Refer Firmware upgrade using FTP server) |
3.2.9 and earlier |
6.0.X and above |
Firmware upgrade not supported. Contact Schneider Electric Technical Support for help. |
|
6.0.X and above |
6.X.Y and above |
Webpages (Refer Firmware upgrade using webpages) |
|
PM5650 |
2.11.X |
2.12.9 and earlier |
FTP server (Refer Firmware upgrade using FTP server) |
2.12.9 and earlier |
4.10.X and above |
Firmware upgrade tool (Refer Firmware upgrade using firmware upgrade tool) NOTE:
If the meters are upgraded to their target firmware version, you
cannot go back (downgrade) to their source firmware version.
|
|
4.10.X and above |
4.10.Y and above |
Webpages (Refer Firmware upgrade using webpages) |
|
PM5561 |
10.6.X |
10.9.9 and earlier |
FTP server (Refer Firmware upgrade using FTP server) |
10.9.9 and earlier |
12.0.X and above |
Firmware upgrade tool (Refer Firmware upgrade using firmware upgrade tool) NOTE:
If the meters are upgraded to their target firmware version, you
cannot go back (downgrade) to their source firmware version.
|
|
12.0.X and above |
12.X.Y and above |
Webpages (Refer Firmware upgrade using webpages) |
|
PM5661 / PM5761 |
11.0.X |
11.2.9 and earlier |
FTP server (Refer Firmware upgrade using FTP server) |
11.2.9 and earlier |
14.0.X and above |
Firmware upgrade not supported. Contact Schneider Electric Technical Support for help. |
|
14.0.X and above |
14.X.Y and above |
Webpages (Refer Firmware upgrade using webpages) |
|
PM5570L / PM5660L / PM5760L |
6.0.X and above |
6.X.Y and above |