Setting up the data log using ION Setup
| NOTICE | 
|---|
| Data Loss Save the contents of the data log
                           before configuring it. Failure to follow these instructions can result
                           in data loss. | 
To set up the data log using ION Setup:
- Start ION Setup and open your meter in setup screens mode (). See the ION Setup Help for instructions.
- Double-click Data Log #1.
- Set up the logging frequency and measurements or data to
                  log.Parameter Values Description Status Enable Disable Set this parameter to enable or disable data logging in the meter. Interval 1 minute 5 minutes 10 minutes 15 minutes (Default) 30 minutes 1 hour 24 hours Select a time value to set the logging frequency. Channels Parameters available for logging can vary based on the meter type. Select a parameter to record from the “Available” column, then click the double-right arrow button to move the parameter to the “Selected” column. To remove parameter, select it from the “Selected” column then click the double-left arrow button. 
- Click Send to save the changes to the meter.