Configuring waveform capture using the display
- Navigate to .
- Enter the setup passcode (default is “0”), then press OK.
- Navigate to WFC.
- Move the cursor to point to the parameter you want to modify, then press Edit.
- Modify the parameters as required, then press OK.
-
Press the up arrow to exit. Press Yes to save your changes.
Waveform capture setup parameters available using the display
Parameter
Values
Description
Enable
Yes, No
Enables or disables the waveform capture on your meter
Samples Per Cycle
128
64
32
16
Select the samples per cycle based on the requirement
Pre Cycles
The pre cycles can be configured based on the samples per cycle
-
Maximum 1 – 8 pre cycles for 128 samples per cycle
-
Maximum 1 – 16 pre cycles for 64 samples per cycle
-
Maximum 1 – 32 pre cycles for 32 samples per cycle
-
Maximum 1 – 64 pre cycles for 16 samples per cycle
Select the pre cycles based on the requirement
The Post-cycles will be automatically configured based on the Pre-cycles
NOTE: It is recommended for the end user to configure equal number of pre and post cycles to visualize sag/swell events in waveform.-
Pre-cycles: Number of cycles that will be captured in waveforms prior to waveform trigger
-
Post-cycles : Number of cycles that will be captured in waveforms post waveform trigger
-