100 Millisecond, Arc-Rated MCC, Upstream Over-Current Protection Device (OCPD) Requirements
The OCPD external to and upstream of the MCC must meet the following criteria:
-
The current rating of the upstream OCPD must be equal to or less than the main device and main bus rating of the MCC.
-
The voltage rating of the upstream OCPD must be equal to or greater than the voltage rating of the MCC. The maximum voltage is 600 V.
-
The interrupting rating of the upstream OCPD must be equal to or greater than the available short circuit current. The maximum available short circuit current is 65,000 A.
-
The instantaneous trip setting (if available) of the upstream OCPD must NOT be turned off and must be set to trip at or below 35,000 A.
-
The short time delay trip setting (if available) of the upstream OCPD MUST be set to the OFF position; no intentional delay is allowed.
-
Approved circuit breakers that can be used as the upstream OCPD:
-
15–125 A, PowerPacT™ B-frame circuit breakers manufactured by Schneider Electric
-
15–150 A, PowerPacT H-frame circuit breakers manufactured by Schneider Electric
-
175–250 A, PowerPacT J-frame circuit breakers manufactured by Schneider Electric
-
300–600 A, PowerPacT L-frame circuit breakers equipped with MicroLogic™ trip units, manufactured by Schneider Electric
-
700–1200 A, PowerPacT PJ- or PL-frame circuit breakers equipped with MicroLogic trip units, manufactured by Schneider Electric
-
1200–2500 A, PowerPacT R-frame circuit breakers equipped with MicroLogic trip units, manufactured by Schneider Electric
-
800–1200 A, MasterPacT™ NT and MTZ1 circuit breakers equipped with MicroLogic trip units, manufactured by Schneider Electric
-
1600–2500 A, MasterPacT NW and MTZ2 circuit breakers equipped with MicroLogic trip units, manufactured by Schneider Electric
-
-
Approved fuses that can be used as the upstream OCPD:
-
15–600 A, UL Listed, Class RK1 from any manufacturer
-
15–600 A, UL Listed, Class RK5 from any manufacturer
-
15–600 A, UL Listed, Class J from any manufacturer
-
700–2500 A, UL Listed, Class L from any manufacturer
-