Group Objects
Power on/off group object controls switching the Ventilation system on and off. Power on/off, status object displays on/off status on the screen.
No. |
Name |
Object function |
Length |
Behavior |
Data Type |
---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Power on/off |
1 bit |
Sends |
1.001 switch |
245 |
Screen 1 Function 1 |
Filter timer counter |
2 byte |
Sends |
7.007 time (h) |
246 |
Screen 1 Function 1 |
Filter alarm |
1 bit |
Sends |
1.005 alarm |
247 |
Screen 1 Function 1 |
Fan speed |
1 byte |
Sends |
5.001 percentage 5.100 fan stage |
248 |
Screen 1 Function 1 |
Fan automatic operation |
1 bit |
Sends |
1.003 enable |
249 |
Screen 1 Function 1 |
Heat recovery |
1 bit |
Sends |
1.003 enable |
251 |
Screen 1 Function 1 |
Power on/off, status |
1 bit |
Receives |
1.001 switch |
252 |
Screen 1 Function 1 |
Filter timer counter change |
2 byte |
Receives |
7.007 time (h) |
253 |
Screen 1 Function 1 |
Filter timer reset |
1 bit |
Receives |
1.015 reset |
254 |
Screen 1 Function 1 |
Fan speed, status |
1 byte |
Receives |
5.001 percentage 5.100 fan stage |
255 |
Screen 1 Function 1 |
Fan automatic operation, status |
1 bit |
Receives |
1.003 enable |
256 |
Screen 1 Function 1 |
Heat recovery, status |
1 bit |
Receives |
1.003 enable |
257 |
Screen 1 Function 1 |
Scene |
1 byte |
Receives |
18.001 scene control |