Overview of Group Objects
This list provides the numbers for uniquely identifying a group object. The data point types (DPT) in this application are preset.
General
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
1 |
General |
Live signal |
1 bit |
C, T |
Visible when Cyclic sending live signal parameter > 0. Sends value 1 to the bus cyclically to indicate that the application layer of the device operates normally. The sending cycle is set by parameters. |
1.001 switch |
2 |
Date |
3 byte |
C, W |
Date and time are modified by the bus. |
11.001 date |
|
3 |
Time |
3 byte |
C, W |
10.001 time of day |
Temperature sensor
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
4 |
Internal sensor |
Temperature value |
2 byte |
C, R, T |
Sends a temperature detection value. |
9.001 temperature |
5 |
Low temperature alarm |
1 bit |
C, R, T |
Low/high temperature alarm = 1. No alarm = 0. Sends read-only information or sends on a change. |
1.005 alarm |
|
6 |
High temperature alarm |
1 bit |
C, R, T |
1.005 alarm |
Logic function
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
|
---|---|---|---|---|---|---|---|
7 |
1th Logic |
Input a |
1 bit |
C, W, T, U |
AND OR or XOR displayed |
1.002 boolean |
|
8 |
1th Logic |
Input b |
1 bit |
C, W, T, U |
|||
9 |
1th Logic |
Input c |
1 bit |
C, W, T, U |
|||
10 |
1th Logic |
Input d |
1 bit |
C, W, T, U |
|||
11 |
1th Logic |
Input e |
1 bit |
C, W, T, U |
|||
12 |
1th Logic |
Input f |
1 bit |
C, W, T, U |
|||
13 |
1th Logic |
Input g |
1 bit |
C, W, T, U |
|||
14 |
1th Logic |
Input h |
1 bit |
C, W, T, U |
|||
15 |
1th Logic |
Logic result |
1 bit |
C, T |
|||
7 |
1th Logic |
Threshold value input |
4 bit 1 byte 2 byte 4 byte |
C, W, U |
Displayed according to parameters |
Threshold comparator |
3.007 dimming 5.010 counter pulses 7.001 pulses 12.001 counter pulses |
15 |
1th Logic |
Logic result |
1 bit |
C, T |
1.002 boolean |
||
7 |
1th Logic |
Input 1 bit – bit 0 |
1 bit |
C, W, U |
2 x 1 Bit→1 x 2 Bit |
Format convert |
1.002 boolean |
8 |
1th Logic |
Input 1 bit – bit 1 |
1 bit |
C, W, U |
1.002 boolean |
||
15 |
1th Logic |
Output 2 bit |
2 bit |
C, T |
2.001 switch control |
||
7 |
1th Logic |
Input 1 bit – bit 0 |
1 bit |
C, W, U |
8 x 1 Bit→1 x 1 Byte |
Format convert |
1.002 boolean |
8 |
1th Logic |
Input 1 bit – bit 1 |
1 bit |
C, W, U |
|||
9 |
1th Logic |
Input 1 bit – bit 2 |
1 bit |
C, W, U |
|||
10 |
1th Logic |
Input 1 bit – bit 3 |
1 bit |
C, W, U |
|||
11 |
1th Logic |
Input 1 bit – bit 4 |
1 bit |
C, W, U |
|||
12 |
1th Logic |
Input 1 bit – bit 5 |
1 bit |
C, W, U |
|||
13 |
1th Logic |
Input 1 bit – bit 6 |
1 bit |
C, W, U |
|||
14 |
1th Logic |
Input 1 bit – bit 7 |
1 bit |
C, W, U |
|||
15 |
1th Logic |
Output 1 byte |
1 byte |
C, T |
5.010 counter pulses |
||
7 |
1th Logic |
Input 1 byte |
1 byte |
C, W, U |
1 x 1 Byte→1 x 2 Byte |
5.010 counter pulses |
|
15 |
1th Logic |
Output 2 byte |
2 byte |
C, T |
7.001 pulses |
||
7 |
1th Logic |
Input 1 byte – low |
1 byte |
C, W, U |
2 x 1 Byte→1 x 2 Byte |
5.010 counter pulses |
|
8 |
1th Logic |
Input 1 byte – high |
1 byte |
C, W, U |
5.010 counter pulses |
||
15 |
1th Logic |
Output 2 byte |
2 byte |
C, T |
7.001 pulses |
||
7 |
1th Logic |
Input 2 byte – low |
2 byte |
C, W, U |
2 x 2 Byte→1 x 4 Byte |
7.001 pulses |
|
8 |
1th Logic |
Input 2 byte – high |
2 byte |
C, W, U |
|||
15 |
1th Logic |
Output 4 byte |
4 byte |
C, T |
12.001 counter pulses |
||
7 |
1th Logic |
Input 1 byte |
1 byte |
C, W, U |
1 x 1 Byte→8 x 1 Bit |
5.010 counter pulses |
|
8 |
1th Logic |
Output 1 bit – bit 0 |
1 bit |
C, T |
1.002 boolean |
||
9 |
1th Logic |
Output 1 bit – bit 1 |
1 bit |
C, T |
|||
10 |
1th Logic |
Output 1 bit – bit 2 |
1 bit |
C, T |
|||
11 |
1th Logic |
Output 1 bit – bit 3 |
1 bit |
C, T |
|||
12 |
1th Logic |
Output 1 bit – bit 4 |
1 bit |
C, T |
|||
13 |
1th Logic |
Output 1 bit – bit 5 |
1 bit |
C, T |
|||
14 |
1th Logic |
Output 1 bit – bit 6 |
1 bit |
C, T |
|||
15 |
1th Logic |
Output 1 bit – bit 7 |
1 bit |
C, T |
|||
7 |
1th Logic |
Input 2 byte |
2 byte |
C, W, U |
1 x 2 Byte→2 x 1 Byte |
7.001 pulses |
|
14 |
1th Logic |
Output 1 byte-low |
1 byte |
C, T |
5.010 counter pulses |
||
15 |
1th Logic |
Output 1 byte-high |
1 byte |
C, T |
|||
7 |
1th Logic |
Input 4 byte |
4 byte |
C, W, U |
1 x 4 Byte→2 x 2 Byte |
12.001 counter pulses |
|
14 |
1th Logic |
Output 2 byte-low |
2 byte |
C, T |
7.001 pulses |
||
15 |
1th Logic |
Output 2 byte-high |
2 byte |
C, T |
|||
7 |
1th Logic |
Input 3 byte |
3 byte |
C, W, U |
1 x 3 Byte→3 x 1 Byte |
232.600 RGB value 3 x (0..255) |
|
13 |
1th Logic |
Output 1 byte-low |
1 byte |
C, T |
5.010 counter pulses |
||
14 |
1th Logic |
Output 1 byte-middle |
1 byte |
C, T |
|||
15 |
1th Logic |
Output 1 byte-high |
1 byte |
C, T |
|||
7 |
1th Logic |
Input 1 byte-low |
1 byte |
C, W, U |
3 x 1 Byte→1 x 3 Byte |
5.010 counter pulses |
|
8 |
1th Logic |
Input 1 byte-middle |
1 byte |
C, W, U |
|||
9 |
1th Logic |
Input 1 byte-high |
1 byte |
C, W, U |
|||
15 |
1th Logic |
Output 3 byte |
3 byte |
C, T |
232.600 RGB value 3 x (0..255) |
||
16 – 78 |
2nd – 8th Logic |
Scene group
Nr. |
Name |
Object function |
Length |
Properties |
Note |
DPT |
---|---|---|---|---|---|---|
79 |
Scene group |
Main scene trigger |
1 byte |
C, W |
Scene group feature visible when enabled |
17.001 scene number |
80 |
1st Scene group |
Sub scene output 1 |
1 bit 1 byte 2 byte |
C, T |
Displayed according to parameter options |
1.001 switch 5.010 counter pulses 7.001 pulses |
81 |
Sub scene output 2 |
|||||
82 |
Sub scene output 3 |
|||||
83 |
Sub scene output 4 |
|||||
84 |
Sub scene output 5 |
|||||
85 |
Sub scene output 6 |
|||||
86 |
Sub scene output 7 |
|||||
87 |
Sub scene output 8 |
|||||
88 – 143 |
2nd – 8th Scene group |
FCU controller
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
Note |
DPT |
---|---|---|---|---|---|---|---|
144 |
FCU controller |
Power on/off, status |
1 bit |
C, W |
Controller switch. |
Switch status is displayed on the screen. |
1.001 switch |
145 |
External temperature sensor |
2 byte |
C, W, T, U |
Receives the external sensor temperature value. Periodically sends read requests. |
The temperature option is visible when an external sensor is available. |
9.001 temperature |
|
146 |
Current setpoint adjustment, status Base setpoint adjustment, status |
2 byte |
C, W |
Modifies the current setpoint temperature value by bus. Modifies the base setpoint temperature by bus. |
Current setpoint adjustment visible when Operating mode is not enabled or when Absolute setpoint method is enabled. Base setpoint adjustment visible when Relative setpoint method is enabled. |
9.001 temperature |
|
150 |
Switch Heating/Cooling mode |
1 bit |
C, W |
Heating/cooling via object. |
1.100 cooling/heating |
||
150 |
Switch Control mode |
1 byte |
C, W |
Heating/cooling via both object and the button. |
20.107 DPT Changover Mode |
||
151 |
Operation mode, status |
1 byte |
C, W |
Control HVAC operation mode via bus. 1-bit object receives a value "1" → the corresponding mode activates. 1-bit standby object disables comfort, economy and protection mode. All three = 0. |
Sends HVAC operation mode messages to the bus. When a particular mode is activated, only the corresponding object sends 1. 1-bit object for standby mode not enabled: The other objects for comfort, energy-saving, and protection mode send 0 together when standby mode is activated. A 1-bit object for standby mode enabled: Only the standby object sends 1 when the standby mode is activated. When switching via the bus, there is no need to send the mode status to the bus. |
20.102 HVAC mode |
|
152 |
Comfort mode, status |
1 bit |
C, W |
1.003 enable |
|||
153 |
Economy mode, status |
1 bit |
C, W |
||||
154 |
Frost/Heat protection mode, status |
1 bit |
C, W |
||||
155 |
Standby mode, status |
1 bit |
C, W |
||||
156 |
Extended comfort mode |
1 bit |
C, W |
"1" triggers the extension of the comfort mode time. |
1.016 acknowledge |
||
157 |
Fan speed, status |
1 byte |
C, W, U, T |
The object datatype of 1 byte fan speed is displayed according to the parameters. |
Sends automatic control fan speed value to the bus. 1-bit object function for fan speed enabled: When a particular fan speed is activated, only the corresponding 1-bit fan speed status object sends 1. 1-bit object for fan speed off not enabled: When the fan speed is off, all the other fan speed status objects send 0. 1-bit object for fan speed off enabled: When the wind speed is switched to off, only the Fan speed off, status object sends the message 1. |
5.001 percentage 5.100 fan stage |
|
158 |
Fan On/Off, status |
1 bit |
C, W, U, T |
Visible when the fan is enabled. 1 speed level/ 1 bit status. |
1.001 switch |
||
158 |
Fan speed 1, status |
1 bit |
C, W, U, T |
"1" switches the corresponding fan speed. Fan multilevel/ 1 bit status. Displays when 1-bit object function for fan speed is enabled |
|||
159 |
Fan speed 2, status |
1 bit |
C, W, U, T |
||||
160 |
Fan speed 3, status |
1 bit |
C, W, U, T |
||||
161 |
Fan speed off, status |
1 bit |
C, W, U, T |
Fan multilevel/ 1 bit status off Displays when 1-bit object for fan speed off is enabled. |
|||
162 |
Fan automatic operation, status |
1 bit |
C, W, U, T |
The fan speed is displayed when it is automatically controlled and enabled. |
Receives status feedback for automatic fan speed control: 1 - Automatic control, 0 - Exit automatic control. After the device restarts, the fan speed automatically sends a read request to the bus. |
1.003 enable |
|
163 |
Window contact |
1 bit |
C, W, U, T |
Displays when Window contact input function is enabled. |
1 - Window open, 0 - Window closed. After the device restarts, the window contact object sends a read request to the bus. |
1.019 Window/door |
|
164 |
Presence detector |
1 bit |
C, W, U, T |
Displays when you enable the presence detector input. |
1 = presence, 0 = no presence After the device restarts, the presence detection object sends a read request to the bus. |
1.018 occupancy |
|
165 |
Power on/off |
1 bit |
C, R, T |
The temperature switch is controlled via the screen. |
|||
166 |
Actual temperature |
2 byte |
C, R, T |
The option is visible when the you choose the combination of internal and external sensor. |
Sends the actual combined temperature to the bus. |
9.001 temperature |
|
167 |
Base temperature setpoint |
2 byte |
C, R, T |
Visible only with Relative setpoint method selected. |
Sends the current reference temperature setpoint to the bus. |
9.001 temperature |
|
169 |
Current temperature setpoint |
2 byte |
C, R, T |
Sends the current temperature setpoint to the bus. |
9.001 temperature |
||
170 |
Heating/Cooling mode |
1 bit |
C, R, T |
Switches between heating and cooling via bus. |
1.100 cooling/heating |
||
171 |
Control mode |
1 byte |
C, R, T |
Switching of heating, cooling, and automatic modes via bus. |
0 = Auto 1 = Cooling only 2 = Heating only 3 – 255 unused |
20.107 DPT ChangoverMode |
|
172 |
Operation mode |
1 byte |
C, R, T |
Control HVAC’s operation mode via bus. 1-bit object receives a value "1" → the corresponding mode activates. 1-bit standby object disables comfort, economy and protection mode. All three = 0. |
Visible when the Operation mode function enabled. |
20.102 HVAC mode |
|
173 |
Comfort mode |
1 bit |
C, R, T |
1.003 enable |
|||
174 |
Economy mode |
1 bit |
C, R, T |
||||
175 |
FCU controller |
Frost/Heat protection mode |
1 bit |
C, R, T |
1.003 enable |
||
176 |
Standby mode |
1 bit |
C, R, T |
||||
177 |
Heating control value |
1 bit/1 byte |
C, R, T |
Sends control values for heating or cooling functions. |
Displays according to control options. |
1.001 switch 5.001 percentage |
|
178 |
Cooling control value |
1 bit/1 byte |
C, R, T |
||||
179 |
Fan speed |
1 byte |
C, R, T |
The object datatype of 1-byte fan speed is displayed according to the parameters. |
Sends automatic control fan speed value to the bus. 1-bit object function for fan speed enabled: When a particular fan speed is activated, only the corresponding 1-bit fan speed status object sends 1. 1-bit object for fan speed off not enabled: When the fan speed is off, all the other fan speed status objects send 0. 1-bit object for fan speed off enabled: When the wind speed is switched to off, only the Fan speed off, status object sends the message 1. |
5.001 percentage 5.100 fan stage |
|
180 |
Fan On/Off |
1 bit |
C, T |
1 level |
1.001 switch |
||
180 |
Fan speed 1 |
1 bit |
C, T |
1.001 switch |
|||
181 |
Fan speed 2 |
1 bit |
C, T |
||||
182 |
Fan speed 3 |
1 bit |
C, T |
||||
183 |
Fan speed off |
1 bit |
C, T |
||||
184 |
Fan Automatic operation |
1 bit |
C, R, T |
This object displays when you choose automatic fan operation. |
Sends automatic control telegrams for the fan speed to the bus. 1 = Auto 0 = Exit automatic operation |
1.003 enable |
Floor heating controller
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
185 |
Floor heating controller |
Power on/off, status |
1 bit |
C, W, U |
Displays the switch status feedback. |
1.001 switch |
186 |
External temperature sensor |
2 byte |
C, W, T, U |
Receives the external sensor temperature value. Periodically sends read requests. After the device restarts, the external sensor sends a read request to the bus. |
9.001 temperature |
|
187 |
Current setpoint adjustment, status Base setpoint adjustment, status |
2 byte |
C, W, U |
Modifies the current setpoint temperature value by bus. Modifies the base setpoint temperature by bus. |
9.001 temperature |
|
190 |
Power on/off |
1 bit |
C, R, T |
Controller switch (on the screen) |
1.001 switch |
|
191 |
Floor heating controller |
Actual temperature |
2 byte |
C, R, T |
Sends the actual temperature after the combination of internal and external sensor values. The object is visible when the temperature reference is taken from both sensors (internal and external). |
9.001 temperature |
192 |
Current temperature setpoint |
2 byte |
C, R, T |
Sends the current temperature setpoint to the bus. |
9.001 temperature |
|
193 |
Heating control value |
1 bit/1 byte |
C, R, T |
Sends the control value of the heating or cooling function. |
1.001 switch/5.001 percentage |
Ventilation controller
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
Note |
DPT |
---|---|---|---|---|---|---|---|
210 |
Ventilation controller |
Fan automatic operation |
1 bit |
C, W |
Automatic control of the fan is activated by the bus. |
Displayed when the Ventilation controller enabled |
1.003 enable |
211 |
PM 2.5 value VOC value CO2 value |
2 byte |
C, W, T, U |
Datatype displayed according to parameter setting |
7.001 pulse 9.030 concentration (μ /m3) 9.008 parts/million (ppm) |
||
238 |
Fan speed, status |
1 byte |
C, T |
Displayed according to the parameter Object datatype of 1byte fan speed setting |
5.001 percentage 5.100 fan stage |
Screen – locking
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
Note |
DPT |
---|---|---|---|---|---|---|---|
243 |
Screen 1 Function 1 |
Locking object |
1 bit |
C, W |
For all of the following screen functions, except Air quality display, Weather information and Energy monitoring. |
Lock/unlock icon |
1.003 enable |
Screen – switching
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Switch |
1 bit |
C, T |
1-bit switch for control and status feedback. Switch values alternate during operation. |
1.001 switch |
249 |
Switch, status |
1 bit |
C, W, T, U |
1.001 switch |
Screen – brightness dimming
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Switch |
1 bit |
C, T |
1. Switch: 1-bit control and status feedback, switch values alternates during the operation. 2. 1-byte brightness dimming: control and status feedback. |
1.001 switch |
246 |
Brightness dimming |
1 byte |
C, T |
5.001 percentage (0..100%) |
||
249 |
Switch, status |
1 bit |
C, W, T, U |
1.001 switch |
||
251 |
Brightness, status |
1 byte |
C, W, T, U |
5.001 percentage (0..100%) |
Screen – RGB/W dimming
Nr. |
Name |
Object function |
Length |
Properties |
Note |
Function description |
DPT |
---|---|---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Switch |
1 bit |
C, T |
Controls brightness of multi-color lamps. Color temperature adjustment is also supported. 1. Switch: 1-bit type, control and status feedback. Switch values alternate during the operation. 2. Color adjustment: 3-byte or 3 x 1-byte control and status feedback. 3. White light brightness adjustment: 1-byte control and status feedback. |
1.001 switch |
|
245 |
RGB dimming value |
3 byte |
C, T |
RGB 3-byte |
232.600 RGB value 3 x (0..255) |
||
245 |
RGBW dimming value |
6 byte |
C, T |
RGBW 6-byte |
251.600 DPT_Colour_RGBW |
||
245 |
Red dimming value |
1 byte |
C, T |
RGB or RGBW: 1-byte type |
5.001 percentage (0..100%) |
||
246 |
Green dimming value |
1 byte |
C, T |
||||
247 |
Blue dimming value |
1 byte |
C, T |
||||
248 |
White dimming value |
1 byte |
C, T |
RGBW 1-byte type |
|||
249 |
Switch, status |
1 bit |
C, W, T, U |
1.001 switch |
|||
250 |
RGB brightness, status |
3 byte |
C, W, T, U |
RGB 3-byte |
232.600 RGB value 3x(0..255) |
||
250 |
RGBW brightness, status |
6 byte |
C, W, T, U |
RGBW 6-byte |
251.600 DPT_Colour_RGBW |
||
250 |
Red brightness, status |
1 byte |
C, W, T, U |
RGB or RGBW 1-byte type |
5.001 percentage (0..100%) |
||
251 |
Green brightness, status |
1 byte |
C, W, T, U |
||||
252 |
Blue brightness, status |
1 byte |
C, W, T, U |
||||
253 |
White brightness, status |
1 byte |
C, W, T, U |
RGBW 1-byte type |
Screen – color temperature dimming
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Switch |
1 bit |
C, T |
Color temperature and brightness adjustment of monochrome lamps. 1. Switch: 1-bit control and status feedback Switch values alternate during the operation. 2. Color temperature adjustment: 2-byte control and status feedback. You can set upper and lower thresholds for color temperature. 3. Brightness adjustment: 1-byte control and status feedback. |
1.001 switch |
245 |
Color temperature value |
2 byte |
C, T |
7.600 absolute color temperature |
||
246 |
Brightness value |
1 byte |
C, T |
5.001 percentage (0..100%) |
||
249 |
Switch, status |
1 bit |
C, W, T, U |
1.001 switch |
||
250 |
Color temperature, status |
2 byte |
C, W, T, U |
7.600 absolute color temperature |
||
251 |
Brightness, status |
1 byte |
C, W, T, U |
5.001 percentage (0..100%) |
Screen – roller/venetian blind, curtain position
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Open/Close |
1 bit |
C, T |
Curtain step/move. Open and close. On, off, stop |
1.009 open/close |
245 |
Stop |
1 bit |
C, T |
1.007 step |
||
244 |
Up/Down |
1 bit |
C, T |
Roller blind step/move function. Roll-up, down, stop |
1.008 up/down |
|
245 |
Stop |
1 bit |
C, T |
1.007 step |
||
244 |
Open/Close |
1 bit |
C, T |
Curtain position Open and close On, off, stop Position, position status feedback |
1.009 open/close |
|
245 |
Stop |
1 bit |
C, T |
1.007 step |
||
246 |
Curtain position |
1 byte |
C, T |
5.001 percentage (0..100%) |
||
249 |
Curtain position, status |
1 byte |
C, W, T, U |
|||
244 |
Up/Down |
1 bit |
C, T |
Roller blind position feature Roll-up, open, close, stop Position adjustment, position status feedback |
1.008 up/down |
|
245 |
Stop |
1 bit |
C, T |
1.007 step |
||
246 |
Blind position |
1 byte |
C, T |
5.001 percentage (0..100%) |
||
249 |
Blind position, status |
1 byte |
C, W, T, U |
|||
244 |
Up/Down |
1 bit |
C, T |
Venetian blind position and slat. Blinds, on, off, stop Position and angle adjustment, position and angle status feedback |
1.008 up/down |
|
245 |
Stop/Slat adj. |
1 bit |
C, T |
1.007 step |
||
246 |
Blind position |
1 byte |
C, T |
5.001 percentage (0..100%) |
||
247 |
Slat position |
1 byte |
C, T |
|||
249 |
Blind position, status |
1 byte |
C, W, T, U |
|||
250 |
Slat position, status |
1 byte |
C, W, T, U |
Screen – scene
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
Note |
DPT |
---|---|---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Scene |
1 byte |
C, T C, W, T |
Short press calls a scene. Long press (2 s optional) saves the scene. |
Enabled Object with status feedback function gives the Scene object (in addition to the C and T) the W property |
18.001 scene control |
Screen – air quality display
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Ext. temperature value |
2 byte |
C, W, T, U |
Data received from the bus Optional functions: 1. Temperature: 2-byte floating point value 2. Humidity: 2-byte, floating point value 3. PM2.5: 2-byte unsigned integer or floating point value (μg/m3) 4. PM10: 2-byte unsigned integer or floating point value (μg/m3) 5. CO2: 2-byte (ppm) 6. VOC: 2-byte unsigned integer or floating point value (μg/m3) 7. Brightness: 2-byte integer or floating point value (lux) |
9.001 temperature |
244 |
Humidity value |
2 byte |
C, W, T, U |
9.007 humidity |
||
244 |
PM2.5 value |
2 byte |
C, W, T, U |
7.001 pulse 9.030 concentration (μg/m3) |
||
244 |
PM10 value |
2 byte |
C, W, T, U |
|||
244 |
VOC value |
2 byte |
C, W, T, U |
|||
244 |
CO2 value |
2 byte |
C, W, T, U |
7.001 pulse 9.008 parts/million (ppm) |
||
244 |
Brightness value |
2 byte |
C, W, T, U |
9.004 lux (lux) 7.013 brightness (lux) |
Screen – air conditioner
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Power on/off |
1 bit |
C, T |
Switches the Air conditioner via the bus. |
1.001 switch |
245 |
Current setpoint adjustment |
2 byte 1 byte |
C, T |
Adjusts current temperature setpoint. Datatype according to the Object datatype of setpoint setting. |
9.001 temperature 5.010 counter pulses |
|
247 |
Fan speed |
1 byte |
C, T |
Controls the fan speed. Datatype according to the parameter Object datatype of 1byte fan speed setting. |
5.001 percentage 5.100 fan stage |
|
248 |
Wind swing (1-swing, 0-stop) |
1 bit |
C, T |
Controls the swing. Visible when Swing function is enabled. |
1.010 start/stop |
|
250 |
Control mode |
1 byte |
C, T |
Controls the mode of the air conditioning (Auto, Heating, Cooling, Fan, Dehumidification). |
20.105 HVAC control mode |
|
251 |
Power on/off, status |
1 bit |
C, W |
Displays switch status on the screen. |
1.001 switch |
|
252 |
External temperature sensor |
2 byte |
C, W, T, U |
External sensor object is visible. Receives room temperature from the bus. Periodically sends read requests. |
9.001 temperature |
|
253 |
Current temperature setpoint, status |
2 byte 1 byte |
C, W, U |
Displays the current set temperature on the screen. Datatype according to the Object datatype of setpoint setting. |
9.001 temperature 5.010 counter pulses" |
|
254 |
Fan speed, status |
1 byte |
C, W |
Displays the fan speed on the screen. Datatype according to the parameter Object datatype of 1byte fan speed setting. |
5.001 percentage 5.100 fan stage |
|
255 |
Wind swing, status |
1 bit |
C, W |
Displays swinging status on the screen. |
1.010 start/stop |
|
257 |
Control mode, status |
1 byte |
C, W |
Displays current control mode on the screen. |
20.105 HVAC control mode |
Screen – room temperature control and external controller
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
Note |
DPT |
---|---|---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Power on/off |
1 bit |
C, T |
Controls the RTU switching via the screen. |
1.001 switch |
|
245 |
Current setpoint adjustment |
2 byte |
C, T |
Displays when the Object datatype of setpoint adjustment parameter is set to 2-byte DPT. |
Adjust the set temperature value on the screen. Usually 2-byte object is for absolute adjustment, 1-bit object is for relative adjustment. |
9.001 temperature |
|
246 |
Current setpoint adjustment (1bit) |
1 bit |
C, T |
Displays when the Object datatype of setpoint adjustment parameter is set to 1-bit DPT. |
1.007 step |
||
247 |
Fan speed |
1 byte |
C, T |
Displayed according to the parameter Object datatype of 1-byte fan speed setting. |
Controls fan speed via the screen. |
5.001 percentage 5.100 fan stage |
|
248 |
Fan automatic operation |
1 bit |
C, T |
Controls the fan speed when Automatic operation function is enabled. |
Activates the automatic control of the fan speed via the screen. 1 = active, 0 = inactive |
1.003 enable |
|
249 |
Heating/Cooling mode |
1 bit |
C, T |
Switches heating/cooling via the screen. |
1.100 cooling/heating |
||
250 |
Operation mode |
1 byte |
C, T |
Visible when the Operation mode is enabled. |
Controls HVAC operation mode via screen. |
20.102 HVAC mode |
|
251 |
Power on/off, status |
1 bit |
C, W |
Displays the switch feedback status on the screen. |
1.001 switch |
||
252 |
External temperature sensor |
2 byte |
C, W, T, U |
Visible when the External sensor is allowed for a reference. |
Receives room temperature from the bus. Periodically sends read requests. Displayed on the screen. |
9.001 temperature |
|
253 |
Screen 1 Function 1 |
Current temperature setpoint, status |
2 byte |
C, W, U |
Displays current temperature setpoint on the screen. |
9.001 temperature |
|
254 |
Fan speed, status |
1 byte |
C, W |
Properties according to the parameter Object datatype of 1byte fan speed setting. |
Fan speed status displayed on the screen. |
5.001 percentage 5.100 fan stage |
|
255 |
Fan automatic operation, status |
1 bit |
C, W |
Automatic fan speed status control displayed screen. |
1 = activated, 0 = inactive |
1.003 enable |
|
256 |
Heating/Cooling mode, status |
1 bit |
C, W |
Displays the current control mode on the screen. |
1.100 cooling/heating |
||
256 |
Control mode, status |
1 byte |
C, W |
Heating and Cooling (with auto mode). |
Heating and Cooling (with auto mode). |
||
257 |
Operation mode, status |
1 byte |
C, W |
20.102 HVAC mode |
Screen – ventilation control panel
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Power on/off |
1 bit |
C, T |
Switch control of the ventilation system. |
1.001 switch |
245 |
Filter timer counter |
2 byte |
C, T |
Available when the Filter timer counter function is allowed. Counts filter usage hours. Sends the value to the bus every time the value changes. |
7.007 time (h) |
|
246 |
Filter alarm |
1 bit |
C, T |
If the filter is used for longer than the set time, the filter sounds an alarm. |
1.005 alarm |
|
247 |
Fan speed |
1 byte |
C, T |
Controls fan speed via the screen. DPT is displayed according to the parameter Object datatype of 1-byte fan speed setting. |
5.001 percentage 5.100 fan stage |
|
248 |
Fan automatic operation |
1 bit |
C, T |
Available when Automatic operation function is enabled. Activates the automatic control of fan speed via the screen. 1 = active, 0 = inactive |
1.003 enable |
|
249 |
Heat recovery |
1 bit |
C, T |
Available when Heat recovery function is enabled. Controls the heat recovery mode via the screen. 0 - inactive, 1 - active |
1.003 enable |
|
251 |
Power on/off, status |
1 bit |
C, W |
Switch status. |
1.001 switch |
|
252 |
Filter timer counter change |
2 byte |
C, W |
Available when the Filter timer counter function is allowed. Changes the filter usage time via the bus. |
7.007 time (h) |
|
253 |
Filter timer reset |
1 bit |
C, W |
Resets the filter usage time. |
1.015 reset |
|
254 |
Fan speed, status |
1 byte |
C, W |
Feedback on the currently controlled fan speed to the screen. DPT is displayed according to the parameter Object datatype of 1-byte fan speed setting. |
5.001 percentage 5.100 fan stage |
|
255 |
Fan automatic operation, status |
1 bit |
C, W |
Available when Automatic operation function is enabled. Feedback on the automatic control fan speed to the screen. 1 = active, 0 = inactive |
1.003 enable |
|
256 |
Heat recovery, status |
1 bit |
C, W |
Available when Heat recovery function is enabled. Feedback on heat recovery status to the screen. 0 - inactive, 1 - active |
1.003 enable |
|
257 |
Scene |
1 byte |
C, W |
Visible when Scene function is enabled. |
18.001 scene control |
Screen – audio control
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Power on/off |
1 bit |
C, T |
Switch control via the screen. |
1.001 switch |
245 |
Play = 1/Pause = 0 |
1 bit |
C, T |
Play/pause the track. |
1.010 start/stop |
|
246 |
Next track = 1/Previous track = 0 |
1 bit |
C, T |
Previous/next song. |
1.007 step |
|
247 |
Volume+ = 1/Volume- = 0 Absolute volume |
1 bit 1 byte |
C, T |
Volume increase/decrease 1-bit relative control 1-byte absolute control Displayed according to the data point type. |
1.007 step 5.001 percentage 5.004 percentage |
|
248 |
Mute |
1 bit |
C, T |
Displayed when Mute parameter is enabled. |
1.003 enable |
|
250 |
Play mode |
1 byte |
C, T |
The play mode parameters are displayed when Play mode function is enabled. |
5.010 counter pulses |
|
251 |
Power on/off, status |
1 bit |
C, W |
Switch control status on the screen. |
1.001 switch |
|
252 |
Play = 1/Pause = 0, status |
1 bit |
C, W |
Play/Pause status feedback on the screen. |
1.010 start/stop |
|
253 |
Volume, status |
1 byte |
C, W |
1-byte volume status on the screen. |
5.001 percentage 5.004 percentage |
|
255 |
Mute, status |
1 bit |
C, W |
Displayed when Mute parameter is enabled. |
1.003 enable |
|
256 |
Play mode, status |
1 byte |
C, W |
The play mode status is displayed when Play mode function is enabled. |
5.010 counter pulses |
|
257 |
Track name |
14 byte |
C, W |
Displays the track name. |
16.001 character string (ISO 8859-1) |
Screen – functions
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
272 |
Screen 1 Function 2 |
|||||
287 |
Screen 1 Function 3 |
|||||
302 |
Screen 1 Function 4 |
|||||
317 |
Screen 1 Function 5 |
|||||
332 |
Screen 1 Function 6 |
|||||
347 |
Screen 2 Function 1 |
|||||
362 |
Screen 2 Function 2 |
|||||
377 |
Screen 2 Function 3 |
|||||
392 |
Screen 2 Function 4 |
|||||
407 |
Screen 2 Function 5 |
|||||
422 |
Screen 2 Function 6 |
|||||
437 |
Screen 3 Function 1 |
|||||
452 |
Screen 3 Function 2 |
|||||
467 |
Screen 3 Function 3 |
|||||
482 |
Screen 3 Function 4 |
|||||
497 |
Screen 3 Function 5 |
|||||
512 |
Screen 3 Function 6 |
|||||
527 |
Screen 4 Function 1 |
|||||
542 |
Screen 4 Function 2 |
|||||
557 |
Screen 4 Function 3 |
|||||
572 |
Screen 4 Function 4 |
|||||
587 |
Screen 4 Function 5 |
|||||
602 |
Screen 4 Function 6 |
|||||
617 |
Screen 5 Function 1 |
|||||
632 |
Screen 5 Function 2 |
|||||
647 |
Screen 5 Function 3 |
|||||
662 |
Screen 5 Function 4 |
|||||
677 |
Screen 5 Function 5 |
|||||
692 |
Screen 5 Function 6 |
|||||
707 |
Screen 6 Function 1 |
|||||
722 |
Screen 6 Function 2 |
|||||
737 |
Screen 6 Function 3 |
|||||
752 |
Screen 6 Function 4 |
|||||
767 |
Screen 6 Function 5 |
|||||
782 |
Screen 6 Function 6 |
|||||
797 |
Screen 7 Function 1 |
|||||
812 |
Screen 7 Function 2 |
|||||
827 |
Screen 7 Function 3 |
|||||
842 |
Screen 7 Function 4 |
|||||
857 |
Screen 7 Function 5 |
|||||
872 |
Screen 7 Function 6 |
|||||
887 |
Screen 8 Function 1 |
|||||
902 |
Screen 8 Function 2 |
|||||
917 |
Screen 8 Function 3 |
|||||
932 |
Screen 8 Function 4 |
|||||
947 |
Screen 8 Function 5 |
|||||
962 |
Screen 8 Function 6 |
|||||
977 |
Screen 9 Function 1 |
|||||
992 |
Screen 9 Function 2 |
|||||
1007 |
Screen 9 Function 3 |
|||||
1022 |
Screen 9 Function 4 |
|||||
1037 |
Screen 9 Function 5 |
|||||
1052 |
Screen 9 Function 6 |
User interface
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
1053 |
Screen |
Screen locking |
1 bit |
C, W |
Locks the screen. The screen can not be operated. It only processes the received. |
1.003 enable |
1054 |
Screen on/off |
1 bit |
C, W |
When Turn off screen after [0...255,0=inactive] function is set to 0 s, the screen does not turn off. However, the screen can be turned on/off via this object. |
1.001 switch |
|
1055 |
Screen brightness |
1 byte |
C, W |
Adjusts the screen brightness in the current mode without affecting the screen brightness of other modes. The brightness has to be adjusted for each mode separately. |
5.001 percentage (0..100%) |
|
1057 |
Security |
Password trigger, 1bit value/1byte value/scene No. |
1 bit 1 byte |
C, T |
Displayed according to the Output object type for pin code setting |
1.001 switch 5.010 counter pulses 5.001 percentage 17.001 scene number |
Night mode
Nr. |
Name |
Object function |
Length |
Properties |
Function description |
DPT |
---|---|---|---|---|---|---|
1056 |
Night mode |
Night mode input |
1bit |
C,W,T,U |
Receives day/night messages from the bus. |
1.024 day/night |
Proximity
Nr. |
Name |
Object function |
Length |
Properties |
DPT |
|
---|---|---|---|---|---|---|
1058 |
Proximity function |
Dis/En Proximity function |
1bit |
C,W |
Visible when the Proximity function triggered via is not set to Never. |
1.003 enable |
1059 |
Proximity input |
1bit |
C,W |
Visible when the Proximity function triggered via is set to Proximity object. |
1.001 switch |
|
1060 |
Proximity output |
1bit 1byte |
C,T |
Displayed according to the Object type of output value setting. |
1.001 switch 5.010 counter pulses 17.001 scene number 5.001 percentage |