Group Objects
Power on/off group object controls switching on and off.
Power on/off, status object displays on/off status on the screen.
No. |
Name |
Object function |
Length |
Behavior |
Data Type |
---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Power on/off |
1 bit |
Sends |
1.001 switch |
245 |
Screen 1 Function 1 |
Current setpoint adjustment |
2 byte 1 byte" |
Sends |
9.001 temperature 5.010 counter pulses |
247 |
Screen 1 Function 1 |
Fan speed |
1 byte |
Sends |
5.001 percentage 5.100 fan stage |
248 |
Screen 1 Function 1 |
Wind swing (1-swing, 0-stop) |
1 bit |
Sends |
1.010 start/stop |
250 |
Screen 1 Function 1 |
Control mode |
1 byte |
Sends |
20.105 HVAC control mode |
251 |
Screen 1 Function 1 |
Power on/off, status |
1 bit |
Receives |
1.001 switch |
252 |
Screen 1 Function 1 |
External temperature sensor |
2 byte |
Sends, Receives, Updates |
9.001 temperature |
253 |
Screen 1 Function 1 |
Current temperature setpoint, status |
2 byte 1 byte |
Receives, Updates |
9.001 temperature 5.010 counter pulses |
254 |
Screen 1 Function 1 |
Fan speed, status |
1 byte |
Receives |
5.001 percentage 5.100 fan stage |
255 |
Screen 1 Function 1 |
Wind swing, status |
1 bit |
Receives |
1.010 start/stop |
257 |
Screen 1 Function 1 |
Control mode, status |
1 byte |
Receives |
20.105 HVAC control mode |