Group Objects
Room temperature control panel and External controller:
No. |
Name |
Object function |
Length |
Behavior |
Data Type |
---|---|---|---|---|---|
244 |
Screen 1 Function 1 |
Power on/off |
1 bit |
Sends |
1.001 switch |
245 |
Screen 1 Function 1 |
Current setpoint adjustment |
2 byte |
Sends |
9.001 temperature |
246 |
Screen 1 Function 1 |
Current setpoint adjustment(1bit) |
1 bit |
Sends |
1.007 step |
247 |
Screen 1 Function 1 |
Fan speed |
1 byte |
Sends |
5.001 percentage 5.100 fan stage" |
248 |
Screen 1 Function 1 |
Fan automatic operation |
1 bit |
Sends |
1.003 enable |
249 |
Screen 1 Function 1 |
Heating/Cooling mode |
1 bit |
Sends |
1.100 cooling/heating |
249 |
Screen 1 Function 1 |
Switch Control mode |
1 byte |
Sends |
20.107 DPT ChangoverMode |
250 |
Screen 1 Function 1 |
Operation mode |
1byte |
Sends |
20.102 HVAC mode |
251 |
Screen 1 Function 1 |
Power on/off, status |
1 bit |
Receives |
1.001 switch |
252 |
Screen 1 Function 1 |
External temperature sensor |
2 byte |
Sends, Receives, Updates |
9.001 temperature |
253 |
Screen 1 Function 1 |
Current temperature setpoint, status |
2 byte |
Receives, Updates |
9.001 temperature |
254 |
Screen 1 Function 1 |
Fan speed, status |
1 byte |
Receives |
5.001 percentage 5.100 fan stage" |
255 |
Screen 1 Function 1 |
Fan automatic operation, status |
1 bit |
Receives |
1.003 enable |
256 |
Screen 1 Function 1 |
Heating/Cooling mode, status |
1 bit |
Receives |
1.100 cooling/heating |
256 |
Screen 1 Function 1 |
Control mode, status |
1 byte |
Receives |
20.107 DPT ChangoverMode |
257 |
Screen 1 Function 1 |
Operation mode, status |
1 byte |
Receives |
20.102 HVAC mode |