PKR39809-02

ACR Trip Flags Page

The trip flags for Negative Phase Sequence, Under and Over Voltage as well as Under and Over Frequency will only appear on this page if these features have been made available.

------------------------------------------ TRIP FLAGS ------------------------------------------ S

O/C 00-99 ABC

R

LOP 00-99 ABC

R

EXT 00-99

R

E/F (G/F) 00-99

R

UOV 00-99(1)

R

FRQ 00-99

R

SEF (SGF) 00-99

R

NPS 00-99(3)

R

OPS 0000-9999

R

(1) Only displayed if Under/Over Voltage protection is available.

(2) Only displayed if Under/Over Frequency protection is available.

(3) Only displayed if Sequence Components are available.

The title of this page will change to PICKUP FLAGS and not display EXT if protection is Off.

---------------------------------------- PICKUP FLAGS ---------------------------------------- S

O/C 00-99 ABC

R

LOP 00-99 ABC

R

 

R

E/F (G/F) 00-99

R

UOV 00-99

R

FRQ 00-99

R

SEF (SGF) 00-99

R

NPS 00-99

R

OPS 0000-9999

R

The other pages in this group can be displayed by pressing the left and right arrow keys.

Pressing the right arrow key when the Trip Flags page is displayed will move the display to the Supply Interrupt Flags page if Per Element Protection is available, otherwise it will be the first of three Operator Settings pages.