Appendix L.1 ­ Loop Automation Operating Rules

In the following tables, the Sequence (Seq.) column indicates if the rule is applied during Isolation and Reconfiguration (I) or during Auto Restoration (R).

Feeder Device

Table 149 Loop Automation operating rules – Feeder Device

Rule No

Switchgear State

Auto-Restore

Event

Action

Seq.

1

Closed

Off

Source Supply lost for longer than Loop Auto Time.

Switchgear opens and Loop Automation is turned off.

I

2

Closed

On

Source Supply lost for longer than Loop Auto Time.

Switchgear opens.

I

3

Closed

Off

Protection trip to Lockout.

Switchgear opens and Loop automation is turned off.

I

4

Closed

On

Protection trip to end of sequence.

Switchgear opens and Loop Automation stays on.

I

5

Open

On

Source Supply is restored and switchgear was initially tripped by Loop Automation.

Switchgear closes.

R

6

Open

On

Supply is restored to both sides of the switchgear. Either at the source then load or load then source.

Switchgear closes.

R

Mid-Point Device

Table 150 Loop Automation operating rules – Mid-Point Device

Rule No

Switchgear (ACR) State

Auto-Restore

Event

Action

Seq.

7

Closed

On or Off

Source Supply lost for longer than Loop Auto Time.

Switch to reverse Protection Group

I

8

Closed

Off

Protection trip to Lockout.

ACR opens and Loop Automation is turned off.

I

9

Closed

On

Protection trip to end of sequence.

ACR opens and Loop Automation stays on.

I

10

Open

On

Supply is restored to both sides of ACR.

Switch to forward Protection Group and close ACR.

R

Tie Device

Table 151 Loop Automation operating rules – Tie Device

Rule No

Switchgear State

Auto-Restore

Restore Both Ways

Event

Action

Seq.

11

Open

On or Off

On or Off

Supply to both sides is lost for longer than Loop Auto Time.

No Action

I

12

Open

On

On or Off

Supply to load side is lost for longer than Loop Auto Time.

Switchgear closes if alternative supply is present.

I

13

Open

Off

On or Off

Supply to load side is lost for longer than Loop Auto Time.

Switchgear closes if alternative supply is present and turns Loop Automation off.

I

14

Open

On

On

Supply to source side is lost for longer than Loop Auto Time.

Activates reverse Protection Group and closes switchgear.

I

15

Open

Off

On

Supply to source side is lost for longer than Loop Auto Time.

Activates reverse Protection Group, closes switchgear and turns Loop Auto off.

I

16

Open

On or Off

Off

Supply to source side is lost for longer than Loop Auto Time.

No Action.

I

17

Closed

On

On or Off

Protection trip to Lockout.

Switchgear opens and Loop Automation is turned off.

I

18

Closed

On

On or Off

Power flow changes by 50% or more for Loop Auto Time.

Switchgear opens. (If supply is subsequently lost to either side then switchgear closes and Loop Automation turns off.)

R

19

Closed

On

On or Off

Power flow changes by 50% or more but returns to previous level before Loop Auto Time expires.

Switchgear stays closed and Loop Automation is turned off.

R