PKR39809-02

Appendix J.3 ­ flexVUE Engineer Menu Screens

ACR

The Engineer menu for the ACR includes at least four sub-menus.

  1. Protection Menu

  2. Configuration Menu

  3. Telemetry Menu

  4. Measurement Menu

One or two more sub-menus can be added depending on which optional features are made available.

  1. An Automation menu is added if either Loop Automation or Auto-Changeover are made available.

  2. A Power Quality menu is added if one or more of the following four Power Quality features are made available.

    1. Supply Outage Measurement

    2. Waveform Capture

    3. Harmonic Analysis

    4. Sag and Swell Monitoring

When all six menus are available, they are displayed in the following order:

Protection Menu

The Protection menu includes sub-menus as shown below. Sub-menus shown in bold are conditional on feature selection as indicated.

Table 132 flexVUE Protection Menu

Engineer Menu → Protection

1st Sub Menu

2nd Sub Menu

3rd Sub Menu

4th Sub Menu

Feature Selection

PROTECTION GLOBAL

GLOBAL CONTROL

     
 

GLOBAL PICKUP(1)

PHASE

   
   

EARTH

   
   

SEF

   
   

NPS

 

Sequence Components

 

FAULT RESET

     

PROT TRIP SETTINGS

AUTO RECLOSE

TRIP 1

PHASE

 
     

PHASE RESET

Reset Curves

     

EARTH

 
     

EARTH RESET

Reset Curves

     

SEF

 
     

SEF RESET

Reset Curves

     

NPS

Sequence Components

     

NPS RESET

Reset Curves + Sequence Components

     

RECLOSE

 
   

TRIP 2

PHASE

 
     

PHASE RESET

Reset Curves
     

EARTH

 
     

EARTH RESET

Reset Curves

     

SEF

 
     

SEF RESET

Reset Curves

     

NPS

Sequence Components

     

NPS RESET

Reset Curves + Sequence Components

     

RECLOSE

 
   

TRIP 3

PHASE

 
     

PHASE RESET

 
     

EARTH

 
     

EARTH RESET

 
     

SEF

 
     

SEF RESET

 
     

NPS

 
     

NPS RESET

 
     

RECLOSE

 
   

TRIP 4

PHASE

 
     

PHASE RESET

Reset Curves

     

EARTH

 
     

EARTH RESET

Reset Curves

     

SEF

 
     

SEF RESET

Reset Curves

     

NPS

Sequence Components

     

NPS RESET

Reset Curves + Sequence Components

 

SINGLE SHOT

 

PHASE

 
     

PHASE RESET

Reset Curves

     

EARTH

 
     

EARTH RESET

Reset Curves

     

SEF

 
     

SEF RESET

Reset Curves

     

NPS

Sequence Components

     

NPS RESET

Reset Curves + Sequence Components

     

RESET

 
 

WORK TAG

 

PHASE

 
     

PHASE RESET

Reset Curves

     

EARTH

 
     

EARTH RESET

Reset Curves

     

SEF

 
     

SEF RESET

Reset Curves

     

NPS

Sequence Components

     

NPS RESET

Reset Curves + Sequence Components

 

UNDER/OVER FREQ

 

UNDER FREQ

Under/Over Freq Prot

     

OVER FREQ

Under/Over Freq Prot

     

NORMAL FREQ CLOSE

Under/Over Freq Prot

 

ROCOF

   

Under/Over Freq Prot

 

UNDER/OVER VOLT

 

UNDER VOLT

Under/Over Voltage Prot

     

OVER VOLT

Under/Over Voltage Prot

     

UV/OV CONFIG

Under/Over Voltage Prot

 

LOSS OF PHASE

     
 

NVD PROTECTION

   

Neutral Voltage Displacement

 

NVD ALARM

   

Neutral Voltage Displacement

 

BROKEN CONDUCTOR PROT

   

Broken Conductor Avail

 

BROKEN CON ALARM

   

Broken Conductor Avail

PROTECTION CONTROL

 

COLD LOAD PICKUP

   
   

SYNC CHECK

 

Sync Check Available

   

INRUSH RESTRAINT

   
   

HIGH CURRENT LOCKOUT

   
   

Dead Lockout

   
   

Live Load Blocking

   
   

Sequence

   
   

Fault Period

   

DIRECTIONAL ELEMENTS

 

DIRECTIONAL BLOCKING(2)

PHASE FAULT POLARISE

 
     

EARTH FAULT POLARISE

 
     

SEF POLARISE

 
     

NPS POLARISE

 
     

Vzps COMPENSATION

 
     

HIGH Vzps ALARM

 

DIRECTIONAL ELEMENTS

 

DIRECTIONAL PROTECTION

PHASE FAULT POLARISE

Directional Protection ON

     

EARTH FAULT POLARISE

Directional Protection ON

     

SEF POLARISE

Directional Protection ON

     

NPS POLARISE

Directional Protection ON + Sequence Components

FAULT LOCATOR

     

Fault Locator Available

(1) Only displayed when Per Trip Thresholds are not available.

(2) Direction Blocking and Directional Protection are mutually exclusive.

AS

The Engineer menu for the AS includes at least four sub-menus.

  1. Detection Menu

  2. Configuration Menu

  3. Telemetry Menu

  4. Measurement Menu

One or two more sub-menus can be added depending on which optional features are made available.

  1. An Automation menu is added if either Loop Automation or Auto-Changeover are made available.

  2. A Power Quality menu is added if one or more of the following four Power Quality features are made available.

    1. Supply Outage Measurement

    2. Waveform Capture

    3. Harmonic Analysis

    4. Sag and Swell Monitoring

When all six menus are available, they are displayed in the following order:

Detection Menu

The Detection menu includes sub-menus as shown below. Sub-menus shown in bold are conditional on feature selection as indicated.

Table 133 flexVUE Detection Menu

Engineer Menu → Detection

1st Sub Menu

2nd Sub Menu

Default Setting

Feature Selection

GLOBAL CONTROL

 

Active Detection Group A

 
   

Copy Off

 
   

Detection On

 
   

Sectionaliser Off

 
   

E/F On, SEF On

Per Element Detection N/Avail

   

Phase Detection On

Per Element Detection Avail

   

Phase Mode SECT

Per Element Detection Avail

   

Earth Detection On

Per Element Detection Avail

   

Earth Mode SECT

Per Element Detection Avail

   

SEF Detection On

Per Element Detection Avail

   

SEF Mode SECT

Per Element Detection Avail

   

SEF Alarm On

 
   

NPS Detection On

Per Element Detection Avail

   

NPS Mode SECT

 
   

Single Shot Mode Off

 
   

Supply Fail 3.0 s

 

SECTIONALISE

 

Trip on Count 1

 
   

Trip on SEF Count 1

 
   

Trip on NPS Count 1

 
   

Seq Reset Time 30 s

 

FAULT DETECTION

PHASE

Phase Set 200 Amp

 
   

Phase Pickup x 1.0

 
 

EARTH

Earth Set 40 Amp

 
   

Earth Pickup x 1.0

 
 

SEF

SEF Set 4 Amp

 
   

SEF Pickup x 1.0

 
 

NPS

NPS Set 40 Amp

Sequence Components Avail

   

NPS Pickup x 1.0

Sequence Components Avail

FAULT RESET

 

Fault Reset 50 ms

 
   

Phase Reset 90%

 
   

Earth Reset 90%

 
   

SEF Reset 90%

 
   

NPS Reset 90%

Sequence Components Avail

 

SECTIONALISE/TRIP 1/PHASE DETECTION

Definite Time

 
   

Definite Time 1.00 s

 
   

No Instantaneous

 

DETECTION SETTINGS

SECTIONALISE/TRIP 1/EARTH DETECTION

Definite Time

 
   

Definite Time 1.00 s

 
   

No Instantaneous

 
 

SECTIONALISE/TRIP 1/EARTH DETECTION

Definite Time

 
   

Definite Time 1.00 s

 
   

No Instantaneous

 
 

SECTIONALISE/TRIP 1/SEF DETECTION

Definite Time

 
   

Definite Time 5.00 s

 
   

No Instantaneous

 
   

Alarm Definite Time 1.00 s

 
 

SECTIONALISE/TRIP 1/NPS DETECTION

Definite Time

Sequence Components Avail

   

Definite Time 1.00 s

Sequence Components Avail

   

No Instantaneous

Sequence Components Avail

 

SINGLE SHOT/PHASE DETECTION

Definite Time

 
   

Definite Time 1.00 s

 
   

No Instantaneous

 
 

SINGLE SHOT/EARTH DETECTION

Definite Time

 
   

Definite Time 1.00 s

 
   

No Instantaneous

 
 

SINGLE SHOT/SEF DETECTION

Definite Time

 
   

Definite Time 5.00 s

 
   

No Instantaneous

 
   

Alarm Definite Time 1.00 s

 
 

SINGLE SHOT/NPS DETECTION

Definite Time

 
   

Definite Time 1.00 s

 
   

No Instantaneous

 
 

SINGLE SHOT/RESET

Single Shot Reset Time 0 s

 
 

UNDER OVER VOLTAGE/UNDER VOLTAGE

UV Detection Off

 
   

UV Mode ALARM

 
   

Phase Logic AND

 
   

Pickup Voltage 0.90 pu

 
   

Definite Time 1.00 s

 
 

UNDER OVER VOLTAGE/OVER VOLTAGE

OV Detection Off

 
   

OV Mode ALARM

 
   

Phase Logic AND

 
   

Pickup Voltage 1.10 pu

 
   

Definite Time 1.00 s

 
 

UNDER OVER VOLTAGE/UV/OV CONFIGURATION

Nom P-E V 6.300 kV

 
   

Definite Time

 
   

Fault Reset 50ms

 
 

BROKEN CONDUCTOR DETECTION

Broken Conductor Detection Off

 
   

Set 1.00 INPS/IPPS

Broken Conductor Available

   

Definite Time 10.00 s

Broken Conductor Available

   

Reset 90%

Broken Conductor Available

   

Reset Time 0.05 s

Broken Conductor Available

COLD LOAD PICKUP

 

CLP Phase Off

 
   

CLP Earth Off

 
   

CLP SEF Off

 
   

CLP NPS Off

Sequence Components Avail

   

Cold Load Time 120 min

 
   

Cold Load Mult x 2.0

 

SYNC CHECK

 

Sync Check Off

Sync Check Available

   

Sync Check Inactive

Sync Check Available

   

Close Retry Off

Sync Check Available

   

Close Retry 300s

Sync Check Available

   

Voltage On

Sync Check Available

   

Voltage Diff 0.02 pu

Sync Check Available

   

Voltage Min 0.50 pu

Sync Check Available

   

Voltage Max 200 pu

Sync Check Available

   

Nom P-E V 6.30 kV

Sync Check Available

   

Frequency On

Sync Check Available

   

Frequency Diff 0.10 Hz

Sync Check Available

   

Frequency Min 45.00 Hz

Sync Check Available

   

Frequency Max 65.00 Hz

Sync Check Available

   

Phase On

Sync Check Available

   

Phase Diff 6 deg

Sync Check Available

INRUSH RESTRAINT

 

Inrush Off

 
   

Inrush Time 0.10 s

 
   

Inrush Mult x 4.0

 
   

Inrush Type Zero Detect

 
   

Inrush Type SOHIR

SOHIR Available

   

SOHIR Logic AND

SOHIR Available

   

SOHIR Thres 20%

SOHIR Available

Live Load Block

 

Off

 

FAULT LOCATOR

 

Fault Locator Off

Fault Locator Available

   

RPPS 0.0001 ohm/km

Fault Locator Available

   

XPPS 0.0001 ohm/km

Fault Locator Available

   

RzPS 0.0001 ohm/km

Fault Locator Available

   

XzPS 0.0001 ohm/km

Fault Locator Available

Fault Period

 

10 s

Close on Fault Trip Available

Per Element Detection Available

DIRECTIONAL ELEMENTS

DIRECTIONAL BLOCK/PHASE FAULT POLARISE

Fault Direction Forward & Reverse

Directional Blocking On

   

Low Polarising Block Off

Directional Blocking On

   

Minimum VQUAD 500 V

Directional Blocking On

   

Characteristic Angle -45 deg

Directional Blocking On

   

Voltage Memory Off

Directional Blocking On

 

DIRECTIONAL BLOCK/EARTH FAULT POLARISE

Decision VZPS

Directional Blocking On

   

Fault Direction Forward and Reverse

Directional Blocking On

   

Low Polarising Block Off

Directional Blocking On

   

Minimum VZPS 500 V

Directional Blocking On

   

Characteristic Angle 135 deg

Directional Blocking On

 

DIRECTIONAL BLOCK/SEF FAULT POLARISE

Decision VZPS

Directional Blocking On

   

Fault Direction Forward and Reverse

Directional Blocking On

   

Low Polarising Block Off

Directional Blocking On

   

Minimum VZPS 500 V

Directional Blocking On

   

Characteristic Angle 135 deg

Directional Blocking On

 

DIRECTIONAL BLOCK/NPS FAULT POLARISE

Fault Direction Forward & Reverse

Directional Blocking On + Sequence Components Available

   

Low Polarising Block Off

Directional Blocking On + Sequence Components Available

   

Minimum VNPS 500V

Directional Blocking On + Sequence Components Available

     

Directional Blocking On + Sequence Components Available

 

VZPS COMPENSATION

VZPS Balancing Off

Directional Blocking On

 

HIGH VZPS ALARM

High Alarm Mode Off

Directional Blocking On

   

High Time 10 s

Directional Blocking On

   

High Set-point 500 V

Directional Blocking On

 

DIRECTIONAL DETECTION/PHASE FAULT POLARISE

Low Polarising Voltage Action – No Action

Directional Detection On

   

Minimum VQUAD 500 V

Directional Detection On

   

Characteristic Angle -45 deg

Directional Detection On

   

Forward Sector 90 deg

Directional Detection On

   

Reverse Sector 90 deg

Directional Detection On

   

Voltage Memory Off

Directional Detection On

 

DIRECTIONAL DETECTION/EARTH FAULT POLARISE

Decision VZPS

Directional Detection On

   

Low Polarising Voltage Action – No Action

Directional Detection On

   

Minimum VZPS 500 V

Directional Detection On

   

Characteristic Angle 135 deg

Directional Detection On

   

Forward Sector 90 deg

Directional Detection On

   

Reverse Sector 90 deg

 
 

DIRECTIONAL DETECTION/SEF FAULT POLARISE

Decision VZPS

Directional Detection On

   

Low Polarising Voltage Action – No Action

Directional Detection On

   

Minimum VZPS 500 V

Directional Detection On

   

Characteristic Angle 135 deg

Directional Detection On

   

Forward Sector 90 deg

Directional Detection On

   

Reverse Sector 90 deg

Directional Detection On

 

DIRECTIONAL DETECTION/NPS FAULT POLARISE

Low Polarising Voltage Action – No Action

Directional Detection On + Sequence Components Available

   

Minimum VNPS 500 V

Directional Detection On + Sequence Components Available

   

Characteristic Angle 120 deg

Directional Detection On + Sequence Components Available

   

Forward Sector 90 deg

Directional Detection On + Sequence Components Available

   

Reverse Sector 90 deg

Directional Detection On + Sequence Components Available

 

VZPS COMPENSATION

VZPS Balancing Off

Directional Detection On

 

HIGH VZPS ALARM

High Alarm Mode Off

Directional Detection On

   

High Time 10 s

Directional Detection On

   

High Set-point 500 V

Directional Detection On

NOTE: Directional Blocking and Directional Detection are mutually exclusive features.

Configuration Menu (ACR and AS)

The Configuration menu consists of at least 5 sub-menus some of which have another level of sub-menus. When IOEX is made available, a sixth first level sub-menu is created which has its own sub-menus for IOEX-A and IOEX-B.

Table 134 flexVUE Configuration Menu

Engineer Menu → Configuration Menu

1st Sub Menu

2nd Sub Menu

Feature Selection

SYSTEM SETTINGS

DISPLAY

 
 

NETWORK PARAMETERS

 
 

METERING PARAMETERS

 

FEATURE SELECTION

PROTECTION/DETECTION(1)

 
 

AUTOMATION

 
 

GENERAL

 
 

COMMUNICATIONS

 
 

POWER QUALITY

 
 

FAULT LOCATOR

 

RADIO SETTINGS

   

MAINTENANCE

BATTERY TEST

 

IOEX STATUS

IOEX Module A

IOEX Available

 

IOEX Module B

IOEX Available

USER DEFINED CONTROL

   

(1) An ACR has a Protection sub-menu in Feature Selection, an AS has a Detection sub-menu.

Power Quality Menu (ACR and AS)

The Power Quality is not displayed unless at least one of the three power quality features supported by the operator interface has been made available. These features are:

  1. Supply Outages

  2. Sag and Swell

  3. Waveform Capture

A fourth feature, Harmonic Analysis can only be configured and monitored using WSOS. If Harmonic Analysis is the only power quality feature that’s available, the Power Quality menu will not be displayed on the operator interface.

Table 135 flexVUE Power Quality Menu

Engineer Menu → Power Quality Menu

1st Sub Menu

2nd Sub Menu

Feature Selection

SUPPLY OUTAGES

Supply Outage Available

SAG SWELL MENU(1)

SAG/SWELL MONITORING

Sag/Swell Available

SAG MONITORING

Sag/Swell Available

SWELL MONITORING

Sag/Swell Available

WAVE CAPTURE MENU

WAVEFORM CAPTURE

Waveform Capture Available

WAVEFORM TRIGGER

Waveform Capture Available

(1) Not supported when the controller is configured as an AS.

Telemetry Menu (ACR and AS)

The Telemetry Menu has two sub-menus:

  1. Configure Ports Menu

  2. Configure Communications

Configure Ports

The Configure Ports sub-menus are slightly different for PowerLogic ADVC Controller due to the different communications ports available on this controller.

Table 136 PowerLogic ADVC flexVUE Telemetry Menu

1st Sub Menu

2nd Sub Menu

CONFIGURE PORTS MENU

IOEX/WSOS

Modem

10BASE-T

10BASE-T 2

USB 1

USB 2

USB 3

Configure Communications (ACR and AS)

The Configure Communications menu has three sub-menus by default but more are created when additional features are made available through Feature Selection.

Table 137 flexVUE Configure Communications Menu

Engineer Menu → Telemetry Menu → Configure Communications

1st Sub Menu

2nd Sub Menu

Feature Selection

WSOS MENU

WSOS COMMS

 
 

WSOS COMMS STATS

 

DNP3 MENU

DNP COMMS

 
 

DNP COMMS STATS

 
 

DNP TRANS SERVICES

 
 

DNP UNSOLICITED

 
 

DNP DIAGNOSTICS

 
 

DNP DATABASE CONFIG

 

TRACE MENU

COMMS TRACE

 
 

COMMS TRACE STATS

 

IOEX MENU

IOEX Module A

IOEX Available

 

IOEX Module B

IOEX Available

IEC 60870-5-101/4

IEC-101 COMMS

IEC 60870-5-101/4 Available

 

IEC-101 COMMS STATS

IEC 60870-5-101/4 Available

 

IEC-101 TRANS SRVCS

IEC 60870-5-101/4 Available

 

IEC-101 CONFIG

IEC 60870-5-101/4 Available

MODBUS MENU

MBUS COMMS

Modbus Available

 

MBUS COMMS STATS

Modbus Available

NTP MENU

NTP OFF

NTP + Time Zone Available

 

NTP SERVER 1

NTP + Time Zone Available

 

NTP SERVER 2

NTP + Time Zone Available

 

NTP SERVER 3

NTP + Time Zone Available

Automation Menu (ACR and AS)

The Automation menu is similar to the Power Quality menu in that it is not displayed unless at least one applicable feature is available. In the case of automation, applicable features are:

  • Loop Automation

  • Auto-Changeover

These two features are mutually exclusive so the Automation menu will be displayed if either of them is available.

Table 138 flexVUE Automation Menu

Engineer Menu → Automation Menu

1st Sub Menu

2nd Sub Menu

Feature Selection

LOOP AUTOMATION MENU

LA CONFIGURATION

Loop Automation Available

LA COMMUNICATIONS

Loop Automation Available + LA Logic Intelligent

OVERLOAD CONTROL

Loop Automation Available + LA Logic Intelligent + Tie Control Message

AUTO-CHANGEOVER MENU

ACO CONFIG

Auto-Changeover Available

ACO COMMS

Auto-Changeover Available

ACO COMMS STATS

Auto-Changeover Available

ACO TIMERS

Auto-Changeover Available

Measurement Menu (ACR and AS)

The Measurement menu has 6 first level sub menus. Sequence Components available adds a Sequence sub-menu to Voltage.

Table 139 flexVUE Measurement Menu

Engineer Menu → Automation Menu

 

1st Level Sub Menu

2nd Level Sub Menu

3rd Level Sub Menu

Feature Selection

CURRENT

MAGNITUDE AND ANGLE

A PHASE

 
   

B PHASE

 
   

C PHASE

 
   

EARTH

 
 

SEQUENCE

IPPS

Sequence Components

VOLTAGE

PHASE/LINE SRC-LD

INPS

Sequence Components

   

A-E (A-B) Volts(1)

 
   

B-E (B-C) Volts

 
   

C-E (C-A) Volts

 
   

A-E (A-B) Angles

 
   

B-E (B-C) Angles

 
   

C-E (C-A) Angles

 

SEQUENCE

Vpps

Sequence Components

Vnps

Sequence Components

Vzps

Sequence Components

FREQUENCY

Frequency

Source Frequency

Load Frequency

POWER

THREE PHASE

A PHASE

B PHASE

C PHASE

ENERGY

Total

Forward

Reverse

SYNCHRONIZATION

Global In Sync

Sync Check Available

Voltage In Sync

Sync Check Available

Frequency In Sync

Sync Check Available

Phase In Sync

Sync Check Available

DEMAND

DAILY MAX DEMAND

WEEKLY MAX DEMAND

MONTHLY MAX DEMAND

(1) Voltages can be displayed as Phase to Earth or Phase to Phase values.

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.